  The RM-ED lintel-mounted smoke detector is 

installed directly above the door opening (min. 

10 mm). The vertical distance above the bottom 

edge of the lintel/transom must not be more than max. 

0.1 m.

      Mark and drill the fixing holes and the necessary cable 

lead-throughs for connection of swing door operator, 

hold-open device, ceiling-mounted detectors and 

manual pushbutton. 

Install the necessary cabling. 

Fit end caps and fix the RM-ED smoke detector.

 2 

  Terminal assignment 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

24 V DC from 

swing door operator 

Connection of external 

detectors with terminal 

resistor

 2)

12
14

2

External manual release 

with terminal resistor

 2)

10

7 NO

Connection of swing door operator 

ED 200

8 NC
9  C

1

Connection of swing door operator 

ED 100, ED 250

11

Floating terminal

16

Bus

   

Functions DIP switch

 

1

  OFF  = automatic reset 

  ON   = manual reset 

2

  OFF  = 1 radial operation (line) 

  ON   = 2 radial operation (star) 

3

  OFF  = without ceiling-mounted detector 

  ON   = with ceiling-mounted detector 

4

  OFF  = without manual push-button 

  ON   = with manual push-button.

      Connect swing door operator. 

Connect any ceiling-mounted detectors  

and/or manual pushbuttons – see connection diagrams.

 

Terminal resistors must be properly installed!

 3 

 

Set the reset via the DIP switch.

   

Automatic reset (ED 100, ED 250)

 

The RM-ED smoke detector automatically resets 

following an alarm trip and as soon as there is no 

smoke or test gas in the smoke chamber. Status display 

returns to green. 

Reset of the hold-open system is performed by the 

swing door operator (see instruction ED 100, ED 250).

EN

Fixing Instructions 

Technical Data RM-ED

Input: 

24 V DC −10% / +15%

 

Smoke switch:  24 V DC / 50 mA 

Temperature:  –20°C / +40°C

 

Rel. air humidity:   max. 93% without condensation

 

  Work on electrical equipment and systems may only be 

performed by properly trained specialist personnel.

 

Check to ensure that the line power supply (230 V AC) 

to the swing door operator has been disconnected and 

is no longer live.

 

Fire/smoke detectors controlling hold-open systems 

must not be used to actuate any further alarm devices 

(e.g. fire alarm transmission systems).

 

+

 

1)

 

The RM-ED smoke detector should only be installed 

as a lintel-mounted unit, and should only be 

commissioned once firmly fixed to the wall.

 

À

  RM-ED smoke detector  

Á

  RM smoke detector

 a 

  Installation arrangement of the RM-ED lintel-mounted 

smoke detector for applications where the bottom 

surface of the ceiling is less than 1 m above the bottom 

edge of the lintel on one or both sides of the door. 

+

 1) 

See separate sheet for associated connection 

diagrams.

 b 

  If the bottom surface of the ceiling is more than 1 m 

above the bottom edge of the lintel on one or both 

sides of the door, two ceiling-mounted smoke detectors 

must be installed in addition to the lintel-mounted 

detector. 

+

 1) 

See separate sheet for associated connection 

diagrams.

1)

  AAuPZF of the Deutsches Institut für Bautechnik, Berlin

2) 

See connection diagrams.