DORMA
ED 200 ESR
WN 056461 45532
06/12
INSTALLATION / ADJUSTMENT /
COMMISSIONING
Electrical installation:
Electrical installation work must only be
performed by suitably qualified and trained
personnel.
Ensure compliance with local regulations.
The electrical installation work (230 vAC ± 10%, 50/60
Hz) has to be performed by others.
According to German regulations
1)
, an Emergency-Off
pushbutton (VDE 0660, part 207) must be installed in the
power supply line (feeder cable) close to the door. Check
also local regulations.
The operator (drive unit) is supplied complete with a
2-pole-and-earth mains plug (German Schuko type
available). An earthed outlet socket fused at 10 A must be
provided by others.
If earthed outlet sockets are not available, the mains
feeder cable must be externally positioned to install a
lockable main switch. From the main switch the feeder
cable is connected to the operator through the baseplate.
The mains switch must disconnect all poles from the
mains.
Fire and smoke doors:
The ED 200 is approved for installation on fire and smoke
rated doors according to the German Institute for Civil
Engineering, Berlin. An approval certificate for the fire /
smoke rated door is additionally required. The ED 200
must be installed in accordance with the approved and
certificated drawings and templates provided by the
manufacturer of the fire and smoke door.
Where the ED 200 is used in conjunction with hold-open
systems, a smoke detector is required (acc. to the German
regulations for hold-open devices – check also local
regulations). The smoke detectors can be connected
directly to the ED 200 with control unit B, and powered
with a supply of 24 VDC (stabilised). Where the ED 200 is
operated with control unit A, use only the smoke detector
RMZ 2 (power supply 230 V AC) .
Dynamic force limitation according to DIN 18650
DIN 18650 prescribes that the dynamic forces at the
closing edges have to be observed. (This standard is not
compulsory in all countries.)
Where DIN 18650 is compulsory: it has to be observed as
long as no tested light barriers or similar safety equipment
is applied.
The force limitation according to DIN 18650 does not
suffice as the only safety measure. The main closing edge
and the secondary closing edges have to be protected by
further safety equipment. (Safety screens/sensors)
In order to comply with this standard, the static force
limitation, the driving phase for the low (creep) speed
cycles and the speed have to be adjusted according to the
door leaf weight. The dynamic forces have to be checked
on site with the aid of a dynamometer or similar and the
respective settings have to be adjusted if required.
Further information:
Instruction sheet relating to the use and
application for hold-open devices.
2)
Guidelines for hold-open devices published by
the Institute for Civil Engineering Berlin
2)
or
equivalent national guidelines.
Installation on double-leaf doors
When mounting the ED 200 ESR to double-leaf
doors, it is important to ensure that the ED 200 is
installed with control unit A on the inactive leaf and
with control unit B on the active door leaf.
On-site requirements
The following accessories are available for special
on-site installations:
Mounting plate -
Where a direct installation is impossible due to
presence of glass panes, narrow frame, etc. .
Various sizes of axle extension -
for overcoming height differentials.
Arm variants -
for accommodating different.
Wear and tear parts have to be checked and
replaced if required.
ED 200 with standard arm
ED 200 with slide channel
ED 200 with control unit B and
standard arm on the opposite hinge
side (push side) is suitable on
fire and smoke doors
ED 200 with standard arm -
Installation on push side (opposite hinge side)
ED 200 with slide channel -
Installation on push side (opposite hinge side)
ED 200 with slide channel -
Installation on pull side (hinge side)
Preparation
Remove cover from the operator.
Position and fix the mounting screws with the aid of
the provided template
Please check whether the ordered and delivered ED
200 SFR 1/2 is suitable for the intended way of
mounting.
Active door leaf:
Left-handed version with standard arm
Left-handed version with slide channel
(push-version)
Right-handed version with slide channel
(pull-version)
Active door leaf:
Right-handed version with standard arm
Right-handed version with slide channel
(push-version)
Left-handed version with slide channel
(pull-version)
a
b
1
2
3A
c
3B
1 )
1 )
1 )
1 )
1 )
As specified in German guidelines for power-operated
windows, doors and gates.
2 )
2 )
2 )
2 )
2 )
These documents are only printed in German as they refer
exclusively to German market.
05