5.3Activating the parameterisation mode and
adjusting the settings
Example:
1. Simultaneously press pushbuttons T1 and T2.
2. Press pushbutton T2 five times.
3. Exiting the parameterisation mode
Check the functions of the operating and control
elements while consulting the
"8. Operating instruction manual”
LED 2 error codes (red)
See "7. Troubleshooting”.
Familiarisation
Simultaneously press pushbuttons T1 and T2
on the control board.
·
·
The parameterisation mode is activated.
The open time parameter has been selected
and can be modified.
- LED 1 (green) flashes once-
Parameter 1 (Opening time) is activated.
- LED 2 (red) flashes five times.
From the table we see that the current
opening time is 5.0 s.
The opening time increases with each press of
the pushbutton to the next value up.
(This applies to all parameters and their values).
Once the maximum value has been reached (in this
case 6 seconds), the flash number returns to 1,
indicating the lowest value (in this case 3.0 seconds).
Simultaneously press pushbuttons T1 and T2, or
leave the pushbuttons unused for longer than one
minute. Both activities serve to deactivate the
parameterisation mode.
If a fault or error has occurred, this is indicated by
a flashing code from LED 2 (red) correlating to
the cause or location of the problem.
Once the adjustments, commissioning and
functional checks have been carried out on the door
The current opening time is 5.0 s.
The open time needs to be changed to 4.0 s.
5. Adjustment
6. Functional testing
1
2
3
1
2
3
Sensortest-Pegel
10
Sensortest-Sensor
9
deacticff
low activ
high activ
BS
BGS
BS + BGS
CD 80
Swing Door Operator
DORMA
10
DORMA AUTOMATICS, Inc.
924 Sherwood Drive
Toll-Free: 877-367-6211
DL2862-010
Lake Bluff, IL 60044
Fax: 877-423-7999
Jan. 2007
E-mail: [email protected]
Subject to change without notice