background image

P/N DKML-065 REV C 5/02 

IMPORTANT! – Magnetic locks must be supplied with DC power for proper operation.  Use 
only a UL listed (or equivalent) DC power transformer that supplies the proper voltage and 
amperage. 

• 

P/N 1812-035 – 24-Volt DC power transformer.  .5 amp maximum power output. 

• 

P/N 1812-037 – 12-Volt DC power transformer.  1 amp maximum power output.

 

 

12 VDC POWER 

• 

Requires .5-amp power. 

• 

Connect 12 Volt DC POSITIVE to terminal 1. 

• 

Connect 12 Volt DC NEGATIVE to terminal 2. 

• 

Be sure power select jumpers are set for 12 VDC operation.

 

 

24 VDC POWER 

• 

Requires .25-amp power. 

• 

Connect 24 Volt DC POSITIVE to terminal 1. 

• 

Connect 24 Volt DC NEGATIVE to terminal 2. 

• 

Be sure power select jumpers are set for 24 VDC operation.

 

 

Lock Status LED and Relay (DKML-S12-1L and DKML-S12-1LT only) 

• 

LOCKED CONDITION - LED glows green and relay activates. 

• 

UNSECURE CONDITION – LED glows red and relay is deactivated. 

• 

Relay contacts are rated for 1 amp at 24 VDC maximum.  Do not exceed this rating.

 

 

Timer (DKML-S12-1LT only) 

• 

Adjustable from 0-90 seconds. 

 

1

+

3

NO

5

NC

4

C

2

-

LED1

J1

J2

L1

L2

12 or 24 VDC POSITIVE

12 or 24 VDC NEGATIVE

RELAY NORMALLY OPEN

RELAY COMMON

RELAY NORMALLY CLOSED

GRN
BLK
RED

FROM MAGNET

TIMER

INCREASE

IMPORTANT!

12 VDC

24 VDC

J1

J2

TO

 MA

G

N

E

T

TO LED

WH

T

BLK

GR

N

RED

Отзывы: