6-040401 X2 

3

232i Wiring Diagrams

The diagram to the left shows how to control 
the keypad LED’s using an external alarm 
panel.  To access the keypad’s main circuit 
board, remove the relay board.
To control the LED’s externally cut the four 
traces in the box underneath connector J1.  
Before connecting the alarm panel’s LED 
control lines to J1 verify the traces are cut.  
To verify, measure continuity between the 
end of the wire on the wire harness and the 
square pad on the circuit board below the box 
corresponding to the wire you’re measuring.  

Permanent damage to the keypad may 
result if voltage is connected to J1 when 
the traces are not cut.

The diagram above shows how to connect two keypads to control a single door. Entering your code on keypad 2 unlocks the 
maglock directly.  When you enter your code on keypad 1, it triggers the REX input of keypad 2, which unlocks the door.
When using a propped door or forced door alarms, connect the alarms to keypad 2.  Also use keypad 2 to shunt out an existing 
alarm system with the alarm shunt relay.
Please note that user codes must be programmed into both keypads.