Aquasun 2 Instuction_rB1

 

3

achieves  temperature  limit  during  the  2

nd

 

heat cycle then it will start an economy/sleep 
mode,  which  will  prevent  the  pump  from 
starting for the rest of the day. 

MANUAL PUMP MODE 

Holding  the  UP  button  to  go  above  40°C  will 
toggle the pump from Off to On or vice versa, 
Manual mode will time out after 30 minutes of 
being  selected,  with  a  default  temperature 
limit of 30°C 

WINTER MODE 

Holding  the  DOWN  button  to  go  below  20°C 
will  set  the  unit  into  WINTER  mode,  on 
selection of winter mode the pump will run for 
3 minutes and will repeat this every day at the 
same  time  unless  the  power  fails.  Should 
there  be  an  interruption  to  power  then  an 
exception  takes  place  to  prevent  the  pump 
starting  at  night,  the  sensors  are  tested  to 
check  that  the  roof  sensor  is  5°C  or  more 
above  the  pipe  sensor,  if  this  temperature 
condition  is  not  met  the  display  will  show 
“waiting  for  roof  to  warm”,  once  the  pump 
starts  the  controller  will  wait  24  hours  to 
perform  another  unconditional  flush  of  the 
system. 

SUMMER MODE 

Summer  mode  is  the  default  mode  of 
operation; if tropical mode has been selected 
you  can  change  back  to  summer  mode  push 
both buttons and when SUMMER is displayed, 
released  the  buttons  and  use  the  up or  down 
buttons  to  set  the  desired  temperature.  The 
controller  will  automatically  heat  the  pool  to 
this  temperature  when  solar  conditions  are 
favourable. 

TROPICAL MODE 

To activate tropical mode, push and hold both 
buttons  and  when  “TROPICAL”  is  displayed, 
release  the  buttons  and  use  the  up  or  down 
button  to  set  the  desired  temperature.  In 
tropical  mode  the  controller  will  attempt  to 
heat  the  pool,  if  the  pool  exceeds  the 
temperature  limit  while  heating  then  the 
controller  turns  off  the  pump  and  waits  for 

the roof to cool so the controller can cool the 
pool down by dissipating the heat on the cold 
roof (most likely to occur at night). In tropical 
mode  the  controller  attempts  to  keep  the 
pool  at  the  temperature  limit  by  either 
heating or cooling as required. 

NOTES 

1.

 

If a sensor fault is detected the controller 
will  display  which  sensor  failed  (POOL 
and/or ROOF) and the type of failure. 

2.

 

After  a  power  outage  all  configurable 
items  are  retained  &  the  clock  (if  used) 
will keep time for up to 14 days. 

3.

 

The sensor cable with  the red  trace is the 
positive  and  is  usually  fitted  to  the  right 
hand  side  of the  plug  when looking at the 
plug  screws,  incorrect  polarity  may  be 
displayed as a short circuit fault. 

4.

 

If the controller has stopped pumping and 
is  displaying  a  higher  temperature  than 
expected  it  may  be  caused  by  a  pump 
which  is  failing  to  prime,  check  the  pump 
and  if  necessary  prime  the  pump  as  per 
the  pump  manufacturers’  instructions 
then  reset  the  controller  by  turning  it 
off/on. 

5.

 

Maximum  rated  output  load  for  the  240V 
socket is 9.98 Amps / 2395 Watts. 

6.

 

Degree  of  protection  against  moisture: 
IP23 

 

 

 

 