Donaldson Torit Checker SDF Скачать руководство пользователя страница 10

10

   Donaldson Company, Inc. © 1996

SERVICE

INTERVAL

LIGHT

RESET

DOWN

TIME

CLEAN

Figure 7

Unlabeled Window

CONSTANT

CLEAN

12345

12345

12345

12345

12345

12345

12345

12345

12345

12345

NOTE

All lights in the Maintenance
Required  window are red.

1.2.6   Unlabeled Window (Figure 7)

   The unlabeled window below the Set Point
Adjustments window provides the operator with the
ability to modify the filter cleaning mode. The normal
cleaning mode provides cleaning only when the
pressure drop is within the range defined by the
Start Clean and Stop Clean set points.

CONSTANT CLEAN—This mode ignores

the set point for Start Clean and Stop Clean
and operates the filter cleaning system
continuously while the blower is running.
Activate this mode by pressing and holding
the Constant Clean button until the indicator
light (GREEN)  illuminates. Deactivate the
mode by holding the button down until the
light goes out.

DOWN TIME CLEAN—This mode allows

the filter cleaning to continue after the blower
motor is turned off. After a delay  to allow the
blower to stop rotating, the cleaning mode will
then start, sequentially pulse cleaning until
the end of the preset cycle. At the end of the
cleaning cycle, the system shuts down and
remains dormant until the system is
reactivated. This cleaning mode will remain in
effect until turned off, initiating down time
cleaning each time the OFF button shuts the
system down. To activate this mode, press
and hold the DOWN TIME CLEAN button until
the indicator light illuminates (GREEN).
Deactivate the mode by holding the button
down until the light goes out.

SERVICE INTERVAL LIGHT RESET—

This button resets the indicator light located in
the Maintenance Required window.
The system logic requires that the system
be shut down before the reset button will
function.
 If the system is on, the reset button
will have no effect. To reset the indicator light,
turn the system off, perform the necessary
maintenance (i.e. emptying the hopper/drum
or changing filters), and reset the light before
restarting the blower.

1.2.7   Maintenance Required (Figure 8)

   The Maintenance Required window contains a
group of diagnostic functions which, with the
exception of Service Interval, indicate an abnormal
condition exists. The Service Interval indicator will
allow you to schedule routine service as required by
your system. Each of the fault indicator lights, again
with the exception of the Service Interval, is either
reset each time you press the OFF button or reset
automatically when the abnormal condition ends. A
fault light that resets at shut down remains off only if
the fault condition has been corrected. The Service
Interval light has a separate reset button.

PANEL—This indicates that either the

microprocessor-based printed circuit board
has self-diagnosed a fault in its operation or
the power supply voltage applied to the board
is not within acceptable limits.

CLEANING FAILURE—This indicates that

either a solenoid valve, diaphragm valve, or
relay failed to operate resulting in an improper
cleaning pulse. This light will also indicate
either low pressure or complete lack of
compressed air for the cleaning system.

FILTER RUPTURE—This indicates an

unexplained, sudden decrease in pressure
drop across the filter element. Verify this fault
condition by examining the air discharge from
the collector. The fault light may also come on
as a result of either a sudden closure of an
inlet or discharge damper, or other system
changes that cause a rapid decrease in air
flow.

Содержание Torit Checker SDF

Страница 1: ...TIONAND OPERATIONMANUAL IMPORTANT PANEL 123 123 123 123 123 123 123 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 CLEANINGFAILURE FILTERRUPTURE TEMPERATURE SERVICEINT...

Страница 2: ...ly All electrical power must be shut off during installationoftheChecker board APPLICATIONOFELECTRICALEQUIPMENT Do not initiate any circuits before all connectionshavebeenmade TORIT PRODUCTS is the le...

Страница 3: ...ration Airflow Bar Graph 22 23 4 2 Blower Rotation 23 4 3 Start Clean Stop Clean Adjustments 23 4 4 Service Interval 23 7 0 Troubleshooting Guide 24 27 Parts Ordering Information 3 28 Warranty 28 Figu...

Страница 4: ...on RemoteEnclosure Thermistor Twisted Pair CheckerBoard ControlVoltage andNeutral SolenoidWiring MotorPhase Leads ElectricalDisconnect Power 3Phase Regulator CoalescingFilterwith AutomaticDrain Shut O...

Страница 5: ...Reset Button Section 1 2 6 Section 1 2 4 Section 1 2 7 Section 1 2 5 Adjusts Set Point Upward Indicates Blower Operating Activates Set Point Adjustment Adjusts Set Point Downward Will Clean Filter Ca...

Страница 6: ...filter element cleaning function Control of the cleaning mode Continuous monitoring and diagnosis of the vital functions of the mechanical and electronic dust collector system components Monitoring of...

Страница 7: ...the host computer to change the settings start or stop the collector and retrieve all current readings With the use of host computer software addressing one computer could provide remote set point ad...

Страница 8: ...ion within the range 1 2 3 Set Point Indicator Figure 4 When using the set point adjustments window the bar display switches to a set point display with one or two lights illuminated When one light is...

Страница 9: ...the three adjustment buttons As an example if the START CLEAN button is pressed the light above the key will indicate successful initiation and the Set Point Indicator bar graph will switch from displ...

Страница 10: ...t located in the Maintenance Required window The system logic requires that the system be shut down before the reset button will function If the system is on the reset button will have no effect To re...

Страница 11: ...justment for Service Interval responds the unit is configured as an elapsed time indicator and is intended to signal proper service intervals for the dust collector The timer can easily signal any rou...

Страница 12: ...12 Donaldson Company Inc 1996 Figure 9 Pneumatic Installation Checkerboard Field Installed Bulkhead Fittings Furnished but Field Installed...

Страница 13: ...Donaldson Company Inc 1996 13 Figure 11 Current Sensor Wiring L1 L2 L3 Fan Motor CheckerBoard Figure 10 Thermistor Thermistor Field Wired by Others Remoted Wired...

Страница 14: ...tions Remote Checker Board The enclosure for the Checker board should be mounted in a location convenient for the operator or maintenance personnel Since the display provides visual warning of problem...

Страница 15: ...alandtheprintsreadily availableduringinstallation Allelectricalworkmustbedonebya qualifiedelectricianaccordingtolocal codes Microprocessor controlled devices with microcomputers and EPROMS require car...

Страница 16: ...Position A A B C JumperPositions Position A Position B Position C Figure 13 Jumper Position SDF 2 5 1 Blower Motor Current Sensor Setup Table See Figures 12 13 The motor amperage located on the motor...

Страница 17: ...ng Voltage hot See Figure 14 IN OUT HOT This is the primary voltage source for the board Acceptable voltages are 90 to 130 or 180 to 260 VAC 50 60Hz 1 The hot or phase wire connects to the IN terminal...

Страница 18: ...s controlled by the internal clock timer EXT IN 1 does not function 2 5 5 SER I O Serial Port Input Output See Figure 15 This RJ 11 socket provides the connection for the monitoring and control of mul...

Страница 19: ...olt AC or 24 Volt DC The 24 VDC version has a transformer to supply DC current to the relays The 24 VDC version leaves Relay 2 blank to provide separation of the 115 or 230 VAC motor starter voltage f...

Страница 20: ...er Board Relay 1 Relay Relay Relay Relay Relay Relay Relay Relay 3 4 5 6 7 8 9 10 24 VOLT POWER SUPPLY 1 2 3 4 5 6 7 8 9 10 Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay SOL 1 SOL 2 SOL...

Страница 21: ...sure to the matching fittings on the SDF An installation drawing has been shipped with the Checker board which will show all of the proper connections 3 0 PRE START UP CHECKLIST Make sure all connecti...

Страница 22: ...utton until the indicator LED immediately above that button is lit see Figure 6 Again use the arrow buttons to locate and light the LED that seems appropriate for displaying the low flow condition Use...

Страница 23: ...should establish an initial setting for filter cleaning to match your system configuration Each light in the bar graph display is equal to approximately 0 75 wg see Figure 4 The system logic limits mo...

Страница 24: ...ontact factory service 5 Complete airflow configuration settings and exit to normal mode 1 Check for proper valve action and repair or replace as necessary 2 Check for proper valve action and repair o...

Страница 25: ...y checking the discharge airflow for visible plume Replace filters if visible discharge 2 Reset to correct damper settings 3 Check fuses circuit breakers and internal reset Repair or replace as necess...

Страница 26: ...h button and return to service 2 Perform service indicated by the external device and reset as above 1 Repair or replace as required 2 Adjust inlet or outlet damper s 3 Close open hopper discharge or...

Страница 27: ...If the pressure sensor is mounted on the top side of the printed circuit board the tube can be remounted with cyanoacrylate adhesive If mounted on the bottom side of the printed circuit board replace...

Страница 28: ...lting from said defects or nonconformity The foregoing does not apply to components which were not manufactured by the Seller and is expressly in lieu of all other warranties expressed or implied incl...

Отзывы: