MAINTENANCE 

To keep the boiler/hot water tank unit in perfect working order, both appliances should by inspected 
yearly by 

DOMUSA TEKNIK

 authorised technicians. In particular, the following are recommended: 

-  The  inside  of  the  hot  water  tank  should  be  thoroughly  cleaned  once  a  year.  The  primary  circuit 

should be drained first, before draining the hot water tank. 

- If the hot water tank includes electronic cathode protection, this should be inspected once a year 

to ensure it is functioning correctly. 

- The pressure of the primary installation must be kept between 1 and 1.5 bars. 

- Make sure the safety valve and the drain valve are working correctly. 

-  If  the  installation  has  been  out  of  use  for  a  long  time,  check  the  hot  water  tank  feed  pump  is 

working correctly. 

It is recommended for the user to periodically check the pressure and temperature levels of the hot 
water tank and the state of the valves, connections and accessories. 

5

 

START-UP 

For the 

guarantee to be valid

, the hot water tank must be started up by an 

Official DOMUSA TEKNIK 

Technical Assistance Service

. Before starting it up, the following must be ensured: 

- The installation is filled with water and the draining has been done correctly. 

-  The  primary  flow  and  return  connections  and  the  hot  and  cold  water  connections  have  been 

correctly made. 

- There are no leaks from the splices and connections. 

6

 

DELIVERY OF THE INSTALLATION 

After the initial start-up of the appliance, the Technical Assistance Service will explain to the user how 
the hot water tank works, making any observations they consider relevant. 

It  is  the  responsibility  of  the  installer  to  explain  to  the  user  the  functioning  of  any  control  devices 
belonging to the installation and not supplied with the hot water tank. 

Содержание Sanit S 1000

Страница 1: ...INSTALLATION AND OPERATING INSTRUCTIONS SANIT S 500 SANIT S 750 SANIT S 1000 SANIT S 1000 SBH ...

Страница 2: ... given to the user Read the warnings and recommendations in the manual carefully as they contain important information on the safety use and maintenance of the installation These hot water tanks are to be installed by skilled personnel only in accordance with the legislation in force and following the manufacturer s instructions The start up of these hot water tanks and any maintenance operations ...

Страница 3: ... 2 1 Equipment options 7 3 2 2 Cathodic protection 7 3 2 3 Electrical element 7 3 2 4 18L DHW expansion tank 7 3 2 5 1 dielectric sleeves 8 3 2 6 DHW safety valve 8 4 MAINTENANCE 9 5 START UP 9 6 DELIVERY OF THE INSTALLATION 9 7 DRAINING THE TANK 10 8 SPARES LIST 11 8 1 HOT WATER TANK 11 8 2 PLUGS AND EMBELLISHER 13 9 DIAGRAMS AND MEASUREMENTS 14 10 TECHNICAL CHARACTERISTICS 16 ...

Страница 4: ... very low temperatures precautions will need to be taken to prevent damage to the installation It is recommendable to add anti freeze to the water in the primary circuit of the tank The anti freeze used must be compatible with public health regulations and it must not be toxic DOMUSA TEKNIK recommends the use of propylene glycol consulting the product manufacturer before use If the installation is...

Страница 5: ...P SP V ES C Sa R Tpr SS EP Primary inlet SP Primary outlet ES Domestic cold water inlet SS Domestic hot water outlet V Drain socket R Resistance socket C Recirculation socket Sa DHW tank temperature probe Tpr Cathode protection connector ...

Страница 6: ...it 4 SANIT S 750 ES SS EP SP V SP C R 1 1 Bridge cover SP Primary outlet EP Primary inlet ES Domestic cold water inlet SS Domestic hot water outlet V Drain socket R Resistance socket C Recirculation socket ...

Страница 7: ...NIT S 1000 1000 SBH ES SS EP V SP C R 1 1 Bridge cover SP Primary outlet EP Primary inlet ES Domestic cold water inlet SS Domestic hot water outlet V Drain socket R Resistance socket C Recirculation socket ...

Страница 8: ...ter circuit After doing so proceed to fill the primary circuit Ensure the secondary circuit is full before filling the primary circuit Place dielectric sleeves on the secondary circuit connections If the cold water pressure is higher than the pressure the appliance is designed for a pressure reducer should be installed calibrated to no higher than the design pressure To prevent heat loss through t...

Страница 9: ... of storage heaters To install it carefully read the assembly instructions supplied with the cathodic protection Figure 1 3 2 3 Electrical element All Sanit hot water tanks have a socket for connecting an electrical element DOMUSA TEKNIK optionally supplies three elements of 1 5 2 5 and 3 5 kW To install them carefully read the assembly instructions supplied with the elements Figure 2 3 2 4 18L DH...

Страница 10: ...e of stainless steel To install the dielectric sleeves carefully read the assembly instructions supplied with them Figure 4 3 2 6 DHW safety valve All Sanit hot water tanks are designed to work at a maximum DHW pressure of 0 7 MPa 7 bar To prevent this pressure from being exceeded DOMUSA TEKNIK recommends fitting a safety valve to the DHW circuit calibrated to a maximum of 0 7 MPa 7 bar The safety...

Страница 11: ...ommended for the user to periodically check the pressure and temperature levels of the hot water tank and the state of the valves connections and accessories 5 START UP For the guarantee to be valid the hot water tank must be started up by an Official DOMUSA TEKNIK Technical Assistance Service Before starting it up the following must be ensured The installation is filled with water and the drainin...

Страница 12: ...then connect a hose to the drain socket on the bottom of the tank Check the hose is correctly connected to the tank drain socket Run the hose to a nearby floor drain This must be at a lower level than the tank The water begins to flow and wait until it drains completely SANIT S 500 750 1000 1000 SBH ...

Страница 13: ... Hot water tank COMMONS SPARE PARTS 1 2 3 4 5 SANIT S 750 SANIT S 1000 1000 SBH Pos Name Code 1 Elliptical plug SCON000090 SCON000430 2 Bridge SPIN000006 3 M8 washer CTOR000080 4 M8 nut CTOR000092 5 Bridge cover SOPE000025 ...

Страница 14: ...Sanit 12 SANIT S 1000 1 2 3 4 6 5 Pos Code Name 1 Screw M14 x 35 2 Lateral joint 3 Lateral inox cover 4 M14 Nut 5 SCON001743 Lateral cover support 6 SCON001748 Lateral cover ...

Страница 15: ...ck embellisher 2 2 2 3 CFER000085 black embellisher 3 2 4 CFER000084 black embellisher 2 5 CFER000134 1 red tapered plug 2 2 2 6 CFER000082 red tapered plug 1 1 1 7 CFOV000158 seal 1 1 1 8 CFOL000037 F brass plug 1 1 1 9 CFOL000021 M 1 chromed plug 1 1 1 10 CFER000090 Nut cover 1 1 1 11 CFER000083 Seal 1 1 1 12 CFER000080 F 1 red plug 2 2 13 CFER000008 F 1 red plug 2 ...

Страница 16: ...Sanit 14 9 DIAGRAMS AND MEASUREMENTS V SP EP ES C Sa R Spc C SS EP ES R SP V V SP EP ES C R SS ...

Страница 17: ...H 1 H Cold water inlet ES mm 220 270 305 Ø 1 M 1 M 1 M Recirculation socket C mm 600 1220 595 Ø H H H Resistance socket R mm 1000 1125 1115 Ø 1 1 4 H 1 1 4 H 1 1 4 H Hot water outlet SS mm 215 1655 1425 Ø 1 M 1 M 1 M DHW tank temperature probe Sa mm H Ø 900 Cathode protection connector Tpr mm H Ø 1200 Base measurement Ø mm 760 860 1060 Height measurement mm 1760 1940 1730 ...

Страница 18: ...ume L 500 745 1000 Max storage temperature ºC 70 70 70 Max working pressure of hot water tank MPa bar 0 7 7 0 7 7 0 7 7 Max primary temperature ºC 85 85 85 Max primary working pressure MPa bar 1 10 1 10 1 10 Empty weight Kg 120 166 240 Full weight Kg 620 916 1240 Exchange surface m2 1 8 2 4 3 2 ...

Страница 19: ...17 NOTES ...

Страница 20: ...5 Bº San Esteban s n 20730 AZPEITIA 20737 ERREZIL Gipuzkoa Telfs 34 943 813 899 www domusateknik com DOMUSA TEKNIK reserves the right to make modifications of any kind to its product characteristics without prior notice CDOC001754 CDOC001754 03 20 ...

Отзывы: