- 8 -

17.- BURNER CONTROL OPERATING SEQUENCE 

The burner’s LMO control box has a reset button 
which is the key element for resetting the burner 
control and activating/deactivating the diagnosis 
functions.  
The multi-colour LED on the reset button is the 
indicator for visual diagnosis. The button and the 
LED are located under the transparent cover of the 
reset button. During normal functioning, the various 
operating statuses are indicated in the form of 
colour codes (see the colour code table below). 
During ignition, the indication is as shown in the 
following table: 

 
 

 
 

Colour code table for multi-colour indicator lights (LEDs) 

Status Colour 

code 

Colour 

Wait time «tw», other standby statuses 

..................................................................

Off 

Fuel pre-heater on 

…………………………………… 

Yellow 

Ignition phase, controlled ignition 

 

Flashing yellow 

Functioning, flame OK 

…………………………………… 

Green 

Functioning, flame not OK 

 

 

Flashing green 

External light during burner ignition 

 

Red/green 

Undervoltage  

 

Yellow/red 

Failure, alarm 

 

…………………………………… 

Red 

Error code output (see «Error code table») 

 

Flashing red 

Interface diagnosis  

 

 

Flashing red light 

 

 

 

…..       

Steady light

 

 

 

Red

 

 

 

 

Off

 

 

 

 

 

Yellow

 

 

 

 

 

 

 

 

 

Green 

 

 

Botón de rearme

 

Reset button

Содержание Domestic D-3

Страница 1: ...D FUNCTIONING INSTRUCTIONS OIL BURNER DOMESTIC D 3 D 4 This instruction manual includes all the details necessary for the proper installation and use of the burner We thank you for having chosen a DOMUSA TEKNIK burner ...

Страница 2: ......

Страница 3: ...ADJUSTMENT Observe the flame If there is not enough combustion air it will be dark and it will produce smoke which will close the uptake On the other hand if there is too much combustion air the flame will be white or white blue coloured reducing the efficiency and therefore not fulfilling the anti pollution norms Besides the excess of air may difficult the ignition process The flame must be kind ...

Страница 4: ... 2 6 DIMENSIONS I G E F H F B A C D L J K DIMENSIONS TABLE DIMENSION A B C D E F F G H I J K L mm 292 265 140 152 215 75 98 290 ø80 205 100 100 ø90 F Domestic D 3 F Domestic D 4 ...

Страница 5: ...tion line blocking screw BL Turn the line adjustment screw RL to the right to increase the airflow and to the left to decrease it After the adjustment has been made screw the combustion line blocking screw BL BL RL 3 mm 0 1 9 CORRECT POSITIONING OF IGNITION ELECTRODES To assure a good ignition of the burner Domestic it is necessary to respect the measures shown in the drawing Besides before mounti...

Страница 6: ... oil line installations without reductions and with a perfect hydraulic sealed It is highly recommended to use copper pipes Depression of maximum 0 4 bar 30 cmHg must not be exceeded In aspiration installation H Pipes length m in 8 mm in 10 mm 0 0 25 60 0 5 21 50 1 0 18 44 1 5 15 38 2 0 12 26 2 5 10 26 3 0 8 20 3 5 6 16 In charge installation H Pipes length m in 8 mm in 10 mm 0 5 10 20 1 0 20 40 1...

Страница 7: ...h 11 8 23 72 47 44 35 58 59 3 kW mmH2O CHAMBER PRESSURE OIL FLOW D 3 D 4 14 OIL FLOW VERSUS NOZZLE AND PUMP PRESSURE GPH 9 Atm Kg h 10 Atm Kg h 11 Atm Kg h 12 Atm Kg h 13 Atm Kg h 14 Atm Kg h 15 Atm Kg h 0 40 1 45 1 55 1 60 1 67 1 75 1 80 1 87 0 50 1 80 1 90 2 00 2 10 2 20 2 27 2 33 0 55 2 00 2 10 2 20 2 30 2 40 2 50 2 60 0 60 2 20 2 30 2 40 2 50 2 60 2 70 2 80 0 65 2 35 2 50 2 60 2 70 2 80 2 90 3...

Страница 8: ... LB RP Black Blue 4 EV2 TC TS Ph N B4 S3 T2 T1 N L1 IG F CH LB 7 TP Brown Pre heater 1 2 5 6 8 10 11 12 3 FR TR MB EV1 LB 4 EV2 TC TS Ph N B4 S3 T2 T1 N L1 IG F CH LB 7 B4 Contact of hour counter S3 Contact of blocking lamp TC Control thermostat TS Safety thermostat CH Hour counter IG General switch F Fuse LB Blocking lamp LB External blocking lamp FR Photocell sensor TR Ignition transformer MB Oi...

Страница 9: ...nect and disconnect the red oil tube to the combustion line proceed as follows Press the connector o ring in the direction of the arrow shown below and simultaneously pull the red tube PRESS O RING RED PIPE OIL OIL EASY CONNECT RACOR ...

Страница 10: ... the form of colour codes see the colour code table below During ignition the indication is as shown in the following table Colour code table for multi colour indicator lights LEDs Status Colour code Colour Wait time tw other standby statuses Off Fuel pre heater on Yellow Ignition phase controlled ignition Flashing yellow Functioning flame OK Green Functioning flame not OK Flashing green External ...

Страница 11: ...use Flashes 2 times On No flame established when ignition safety time ends Fuel valves defective or dirty Flame detector defective or dirty Burner maladjustment no fuel Ignition unit defective Flashes 4 times On External light during burner ignition Flashes 7 times On Excessive flame loss during functioning limited number of repetitions Fuel valves defective or dirty Flame detector defective or di...

Страница 12: ...teban s n 20730 AZPEITIA 20737 RÉGIL Guipúzcoa Tel 34 943 813 899 Fax 34 943 815 666 www domusateknik com DOMUSA TEKNIK reserves the right to make modifications of any kind to its product characteristics without prior notice CDOC000017 CDOC000017 11 19 ...

Отзывы: