Operation Manual

Note: 

 -The lamp must be installed by professional electrician

 

-Ensure the power supply is switched off before fitting this product

-Do not touch the lamp when in use

-Keep away from hot steam and corrosive gas

Instructions for usage:

  

1. 

Connection

 for CHAMELEON 23 DALI push dimmer. Please view below information.

2. 

Setting address

 

• 

Manual setting (addressing) If you don’t want to assign anaddress automatically via the DALI master controller  

  please manual setting function as below. Please make sure you have the correct power supply connected to  

  the CHAMELEON23 interface unit. Once you see the RED colour LCD display illuminated press any button    

  (Bl or 82) for 2 seconds. At this stage”88” will flash on the digital display. This is now in the mode to set    

  the address. Using (Bl) or (82) please set the address number as required. For example to set the address to  

  858” press (B 1) to the number 5 and then press (82) to the number 8. Please repeat this method for any   

  other interface units. After the address has been entered press any or the buttons (B 1) or (82) for 2 seconds  

  and at this stage the display will stop flashing. The entered address is now saved successfully and even if    

  power is lost the address will remain in its memory.

• 

Assigning an address automatically via DALI master controller

 

  The address of the DALI push dimmer can not only be set manually but it can also receive an assigned address  

  command by the DALI master control I er. This type of addressing is the same as al I other companies DALI  

  products. For detailed operations please review the manual from the supplier of the DALI master controller.  

  Each address will be shown on the digital display.

3. 

Operation under DALI dimming mode

  

  Under this mode the DALI device is just a standard DALI LED dimmer. It can be connected to any DALI master  

  controller. All dimming functions will be controlled via the DALI master controller. 

4. 

Operating as a single 1-button push dimmer

  

  Under this mode the DALI device can be isolated from the DALI system and can be used in stand alone mode.  

  It can be operated as an independent dimmer controller through a momentary (normally open) push button  

  switch with a L-LINE in voltage between (200-240VAC). It can also be connected to all other DALI input ports  

  located on the device. By pressing the button (momentary switch) short press (less then 0.5 seconds) will turn  

  of the LEDs “ON” or”OFF’’. By pressing the button (momentary switch) longer press (greater then 1.5 seconds)  

  will increase or decrease the brightness levels of the LED lighting.

5. 

Switching of 2 modes 

 

  The DALI device can be switched may times between “DALI DIMMER” mode and “PUSH DIMMER” mode but  

  cannot be used at the same time. Please select between either selected mode.

DALI INTERFACE

PRI:

Uin=12-24VDC

Lin=8.3A

SEC:

Uout=1x(12-24)VDC

Iout=1 x 8A

Pout=1x(96-192)W

Temp Range: -20°C - +50°C

OC: 20132

INPUT 12-24VDC

DALI Input 

Signal

V+

V-

SE

C

PRI

V+

V-

0.5-1.5mm

2

6-7mm

PUSH DIM

L

D1

N

D2

23

D1

D2

D1

D2