RMDT10.5(X)T
Installing the refrigerator-oven combination
21
•
If the minimum distance between the air inlet and outlet vents cannot be met, a
roof vent must be installed instead of the air outlet vent.
–
The roof vent should be installed directly above the back of the refrigerator as
far as this is possible. Use an air duct (fig.
1, page 7) if you need to install
the roof vent offset; otherwise, heat will accumulate there.
–
Fit a nonflammable heat conduction plate (fig.
2, page 7) above the
refrigerator so that the refrigerator does not heat up the oven.
–
The distance between the air inlet vent and the roof vent must be at least
1800 mm (fig.
–
If a roof air conditioner is provided, the distance between the roof vent
(fig.
1, page 7) and the air outlet of the roof air conditioner (fig.
page 7) must be at least 300 mm.
•
The distance between the top of the oven and the ceiling must be at least 55 mm
(fig.
•
The distance in front of the oven between the top of the oven to the ceiling must
be at least 90 mm (fig.
•
The distance between the top of the oven and the flue outlet of the roof flue must
be between 250 mm and 1500 mm (fig.
•
If a roof flue (fig.
4, page 5) is being used: Fit a detachable panel (fig.
page 5) above the oven so that you can always reach the flue pipe.
•
If you do not have a roof flue: Fit a panel with a ventilation grille (fig.
above the oven.
•
The refrigerator-oven combination must not be installed at the side of the air inlet
and outlet vents as this leads to poor performance and increases the power con-
sumption of the refrigerator.
•
The air inlet and outlet vents must not be covered by vehicle parts (such as an
open door or by installing accessories such as bicycle racks) while operating.
•
Install the refrigerator-oven combination so that it is protected from excessive
heat, as this leads to poor performance and increases the power consumption of
the refrigerator.
•
The refrigerator-oven combination must be installed in a draft-proof location, see
chapter “Installing the refrigerator-oven combination in a draft-proof location” on
page 22.
•
The electrical installation must comply with national and local regulations.
European standards: EN 60335-1, EN 60335-2-24, EN 1648-1 and EN 1648-2.
•
The gas installation must comply with national and local regulations.
European standard: EN 1949.
DometicRMDT10_INM_4445103409_EMEA18_2021-xx-xx.book Seite 21 Dienstag, 25. Mai 2021 1:08 13
Содержание RMDT10.5T
Страница 211: ...RU RMDT10 5 X T 211 A DometicRMDT10_INM_4445103409_EMEA18_2021 xx xx book Seite 211 Dienstag 25 Mai 2021 1 08 13...
Страница 222: ...RU RMDT10 5 X T 222 5 5 1 A I DometicRMDT10_INM_4445103409_EMEA18_2021 xx xx book Seite 222 Dienstag 25 Mai 2021 1 08 13...
Страница 335: ...DometicRMDT10_INM_4445103409_EMEA18_2021 xx xx book Seite 335 Dienstag 25 Mai 2021 1 08 13...