EN
SinePower
Connecting the inverter
19
9.5
Connect multiple appliances
The device is equipped at delivery with galvanic isolation. For the safe operation of
multiple appliances, it is essential that a circuit breaker (residual current circuit
breaker) is built into the socket distribution circuit, see sample circuit diagram in
fig.
6
, page 5.
Sample circuit diagram legend:
!
➤
Install a residual current circuit breaker in the socket distribution circuit.
9.6
Setting the earthing bridge (fig.
5
5, page 4)
➤
Remove the earthing screw from the bottom hole.
➤
Screw the screw into the top hole.
No. in
fig.
6
,
page 5
Explanation
1
230 V
w
power source
2
additional devices, e.g. battery charger, refrigerator
3
DC power source (battery)
4
Inverter
5
Set grounding bridge (At delivery: not set, shown by dotted line)
6
Circuit breaker (residual current circuit breaker)
7
Socket distribution circuit for appliances
WARNING! Danger of electrocution!
If you wish to connect more than one appliance to the inverter and install
a socket distribution circuit, you must arrange a circuit breaker (residual
current circuit breaker) and set a grounding bridge in the inverter.
MSI2300-3500--IO-16s.book Seite 19 Mittwoch, 3. August 2016 5:46 17