EN
Installation
MCS T6, MCS T12, MCS T16
18
8.1
Spacing Allowances and Unit Dimensions
See fig.
3
, page 4:
I
Space allowances (fig.
3
, page 4)
The following space allowances should be considered when mounting the unit:
•
Allow a minimum of 152 mm clearance around the unit in the area of the sea-
water and condensate drain piping.
•
Allow a minimum of 76 mm of air space in front of the evaporator coil for the
return-air intake if it is adjacent to a bulkhead.
•
For flexible ducting connection and for clearance needed behind the supply-
air grille add the following values to get the total clearance distance:
–
51 mm for the duct ring
–
25 mm for the duct bend radius and
–
diameter of the ducting.
•
Allocate enough space for installation and serviceability.
Unit dimensions
NOTE
The blower is rotatable by 270 degrees, to ease installation and improve air
flow.
Unit Capacity
6 T
12 T
16 T
Minimum duct diameter (mm)
102
152
152
Minimum duct area (cm
2
)
81
183
183
Minimum distance return grill (cm
2
)
413
839
1032
Minimum distance supply grill (cm
2
)
206
452
516
MCS-T6-T12-T16--I-16s.book Seite 18 Dienstag, 14. November 2017 11:09 11
Содержание MCS T12
Страница 2: ......
Страница 3: ...3 MCS T6 MCS T12 MCS T16 5 6 1 4 2 2 3 1 2 2 3 6 MR 7 MR 1 4 4x 4x ...
Страница 4: ...MCS T6 MCS T12 MCS T16 4 B A 3 4 1 2 3 4 5 6 1 2 5 ...
Страница 5: ...5 MCS T6 MCS T12 MCS T16 1 2 3 4 5 5 6 6 7 8 9 7 4 3 2 1 5 6 7 4 3 2 1 A B C D 5 6 7 4 3 1 10 10 10 6 ...
Страница 6: ...MCS T6 MCS T12 MCS T16 6 7 8 1 16 2 3 4 5 6 7 8 9 10 11 12 13 14 15 ...
Страница 7: ...7 MCS T6 MCS T12 MCS T16 A 2 3 4 6 7 8 9 10 11 1 12 14 15 16 17 18 20 13 19 5 9 9 ...