Dometic GPC-100-MAX Скачать руководство пользователя страница 9

gpelectric.com  |  [page 9]

6. TROUBLESHOOTING

BEFORE removing and replacing the Converter/charger, perform the following checks:

1.  Disconnect the AC power from the vehicle/device.
2.  Disconnect  the wiring and Battery from the Converter Po output terminal.
3.  Re-connect the AC power to energize the Converter.
4.  Using  a voltmeter, measure the voltage at the Converter  – and + Output terminals. 

>   The Converter is OK if the voltage reading is between 13 VDC and 14 VDC 

      (typically 13.6 VDC).
>   Otherwise check the table below:  

ISSUE

POSSIBLE CAUSE

No 12 VDC output

•  120 VAC not connected to coach or the coach AC circuit breaker is in the 

off 

position.

•  Reversed battery fuses blown. (Battery wiring connections are reversed),

•  Severe overload or shorted load. Remove all loads and retest per above instructions.

• 

Converter/Charger internal failure.

Converter cycles On & Off

• 

Fan air flow is inadequate or blocked. (1” minimum free air space at each end required)

•  Converter/Charger internal failure.

Reversed Battery fuses blown

•  Battery wiring connections are reversed.

•  Defective battery, possible bad cells.

12 VDC output is too low

•  Attached load exceeds rating of the Converter/Charger.

•  Defective battery, possible bad cells.

• 

Converter/Charger internal failure.

Note

Содержание GPC-100-MAX

Страница 1: ...X GPC 45 MAX GPC 55 MAX GPC 75 MAX GPC 100 MAX 2021 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power Dometic 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 2...

Страница 2: ......

Страница 3: ...CHARGE CONTROLLER OPTIONS 8 5 1 GPC CHARGING 8 5 1 1 REDUCED CHARGE TIMES 8 5 1 2 INCREASED BATTERY CAPACITY 8 5 1 3 REDUCED BATTERY STRESS 8 5 2 EXTERNAL GPC DIMENSIONS 8 6 TROUBLESHOOTING 9 7 WARRA...

Страница 4: ...e sure to tighten all connections securely A loose connection can quickly cause terminals and wires to overheat Review unit labels for recommended terminal torque values The battery terminal not conne...

Страница 5: ...ess to the battery ensuring long battery life The GPC will also prevent self discharge of the batteries 3 1 THREE STAGE CHARGING OPTION DESCRIPTION This optional system provides an automatic charging...

Страница 6: ...turn on and off very slowly minimizing unwanted fan starting noise 3 3 ELECTRICAL SPECIFICATIONS GPC 35 MAX GPC 45 MAX GPC 55 MAX GPC 75 MAX GPC 100 MAX DC Output Voltage No Load approx 13 16 5 VDC O...

Страница 7: ...ecting the battery positive to the line side of the breaker and the GPC to the load side Connect Chassis Bonding Lug on the GPC to vehicle chassis or other grounding source 4 2 120 VOLT AC INPUT Plug...

Страница 8: ...and rating After inserting the new fuses tighten the screws firmly DO NOT OVERTIGHTEN 5 1 GPC CHARGING The optional GPC allows the GPC to operate as an automatic three stage smart charger giving the...

Страница 9: ...POSSIBLE CAUSE No 12 VDC output 120 VAC not connected to coach or the coach AC circuit breaker is in the off position Reversed battery fuses blown Battery wiring connections are reversed Severe overlo...

Страница 10: ...a Go Power Product Failure due to fire water neglect improper installation generalized corrosion biological infestations or input voltages that create operating conditions beyond the maximum or minim...

Страница 11: ...hoot common scenarios If applicable warranty will be handled between the End User and the Dealer Go Power will only accept returned items from an End User as a last resort If you are unable to contact...

Страница 12: ...2021 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power Dometic 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 Manual_GPC 35 45 55 75 100 MAX_RevB...

Отзывы: