Troubleshooting 

Universal Air Conditioning Unit

Problem

Possible Reason

Possible Solution

There is no cooling or 

heating.

The temperature set point is satisfied.

Lower or raise the set point using the Q3 control.

The condenser air flow is obstructed.

Check for any obstructions at the condenser. free the 

condenser of any obstructions and clean the condenser if 

necessary.

There has been a loss of refrigerant gas.

Check the air conditioning unit for refrigerant leaks. If leaks 

are found, call a service technician for repair.

The outside temperature is too high for 

efficient cooling.

The outside air temperature will directly affect the air 

conditioning unit’s efficiency. This air conditioning unit can 

effectively cool temperatures up to 95 °F (35 °C).

The evaporator coil is iced (in cooling).

Refer to “Troubleshooting” on page 25.

The fan is not running.

•  Refer to “Digital-Controls Troubleshooting” on page 26.

•  Check the capacitor, connections, and motor.

•  Call a qualified Dometic service technician.

The control is in fan-only mode.

Set the system for Cool Mode or for Aux Heat/Heat Mode.

The digital control is programmed for 

Cool or Aux Heat/Heat only.

Refer to “Digital-Controls Troubleshooting” on page 26.

The high-pressure switch is open (in 

cooling) due to improper air flow.

The intake may be plugged. Verify the condenser fan 

operation.

The compressor’s thermal overload is 

open due to lack of air flow though the 

condenser.

Allow the compressor to cool. Turn the system off for a while 

(it may take up to three hours to reset the thermal overload).

10 .2 Digital-Controls Troubleshooting

 

WARNING: ELECTRICAL SHOCK HAZARD .

The control board operates at 115 VAC or 230 VAC. 
Ensure the power is off before removing the cover 
of the control box. Failure to obey this warning 
could result in death or serious injury.

Use this table to troubleshoot problems with the Q3 
control. Refer also to “General System Troubleshooting” 
on page 25.

Problem

Possible Reason

Possible Solution

The evaporator fan is 

not running when the 

Compressor shuts off.

The Q3 control is programmed for fan 

cycling with the compressor.

Change Programmable Function 7. Refer to “Programmable 

Functions, Ranges, and Factory Defaults” on page 18.

The evaporator fan runs 

continuously at various 

speeds.

The Q3 control is programmed for 

continuous operation which is the 

preferred factory default.

Change Programmable Function 7. Refer to “Programmable 

Functions, Ranges, and Factory Defaults” on page 18.

The evaporator fan is 

not running but the 

Compressor is running.

The circuit board failed. 

Send for repair or call a local service technician.

The Q3 control 

display panel is not 

illuminated.

There is no power to the Q3 control.

Turn the circuit breaker on.

Check the control and temperature 

sensor cables and connections.

Replace the digital or temperature sensor cables if necessary.

The Q3 control failed.

Contact an authorized Dometic servicing dealer for 

replacing the Q3 control.

Содержание ASCDU15HV 1161

Страница 1: ...S AIR CONDITIONER L 5005 Form No 340813 20200305 2020 Dometic Corporation AUTO DEHUMIDIFY ASCDU15HV 1161 Q3 Control EN Universal Self Contained Air Conditioning Unit and Q3 Control Installation and Op...

Страница 2: ...9 Installing the Optional Outside Air Temperature Sensor 13 6 10 Start Up Checklist 14 7 Operation 15 7 1 Understanding Button Functions 15 7 2 Normal Heating or Cooling Cycle 16 7 3 Modes and Progra...

Страница 3: ...tand these instructions before installing or operating this product The installation must comply with all applicable local or national codes including the latest edition of the following standards U S...

Страница 4: ...luorocarbon HFC refrigerant R 410A refrigerant operates at a higher pressure than R 22 Ensure that the servicing equipment and replacement components used are designed to operate with R 410A I IRefer...

Страница 5: ...ressor Start Capacitor yHigh Pressure Switch HPS 1 Compressor Run Capacitor uLow Pressure Switch LPS 1 Evaporator Blower Capacitor i10 ft 3 m Interconnect Cable 2 Condenser Blower Capacitor oElectrica...

Страница 6: ...able Functions Ranges and Factory Defaults on page 18 12 Off Mode Indicator Lights when the system is off Note that the Data Display remains on You can continue to adjust the set point display reading...

Страница 7: ...esulting from mechanical influences and excess voltage Alterations to the product without express permission from the manufacturer Use for purposes other than those described above Dometic Corporation...

Страница 8: ...4 18 38 in 46 cm 5 20 37 in 51 cm 6 20 13 in 51 cm Evaporator Side View 7 17 75 in 45 cm 8 14 88 in 38 cm 4 3 Electrical Box Dimensions i t u y r e w q d f o s a Top Front Side 5 Electrical Box Dimen...

Страница 9: ...udes the drill and cut template P N 086812 4 5 Cable Lengths Description Size Display Cable 15 ft 5 m Typical Indoor Air Sensor 15 ft 5 m Standard on Self Contained Systems Outside Air Sensor optional...

Страница 10: ...9 7 2 10 18 19 11 3 1 6 17 16 5 4 12 13 15 14 8 19 2 7 18 10 9 17 6 1 3 11 12 4 5 16 15 13 14 2 IF PRESENT ON BOARD JUMPER CSNB MUST BE CUT WHEN USING A CONTACTOR OR SOLID STATE RELAY ON THE COMPRESS...

Страница 11: ...icing Dometic equipment to prevent any loss of refrigerant Failure to obey this caution could result in minor or moderate injury NOTICE This product contains R 410A fluorinated greenhouse gas in seale...

Страница 12: ...oper use and may cause damage to the electrical components I IConnect the wiring as per the wiring diagram located on the unit 1 Connect the vehicle s power supply to the unit 2 Install a ground fault...

Страница 13: ...lug the cable into the port labeled INSIDE on the circuit board located in the electrical box 6 8 Installing the Q3 Control 1 Plan the location of the display using the drill and cut template P N 0868...

Страница 14: ...including the main power supply tight Y N 6 10 2 Starting the Unit 1 Turn the circuit breaker for the air conditioner to the On position 2 Turn the control on 3 Use the Q3 control to set the system f...

Страница 15: ...refrigerants must by law be reclaimed If an indoor leak is suspected thoroughly ventilate the area before beginning work Never burn refrigerant as poisonous gas will be produced Always follow EPA gui...

Страница 16: ...n operation When in Auto fan mode the fan speed will return to low speed once the set point temperature has been satisfied and the cooling or heating cycle has ended 7 3 Modes and Programmable Functio...

Страница 17: ...inside temperature If inside temperature is greater than 99 F 37 C or less then 0 F 17 C the display shows either 99 F 37 C or 0 F 17 C respectively as the maximum or minimum inside temperature 7 3 7...

Страница 18: ...C 2 31 4 Fan Response Differential 8 8 8 1 F 0 6 C 2 31 5 Low Fan Speed 38 2 57 6 High Fan Speed 85 41 99 7 Fan Mode C Continuous C Continuous I Intermittent 8 AC Line Voltage Calibration Plus or min...

Страница 19: ...e delay before the display shows readings If an attempt is made to change the five minute time delay the changes will not be recognized by the system 2 Fahrenheit Celsius or Auto Selection Select F fo...

Страница 20: ...antly The high fan speed adjustment allows you to set the maximum high speed voltage to the threshold of the blower high speed response The Q3 control system divides the fan speed voltage steps into f...

Страница 21: ...boats For very humid climates shorten the overall time period and extend the dehumidification time In dry climates select a longer overall time period between cycles and a shorter dehumidification ti...

Страница 22: ...and the display will show OA closed circuit if the high pressure switch circuit is OK or FA open circuit if the high pressure switch circuit has a fault or system is overcharged or has loss of condens...

Страница 23: ...in aux heat heat mode I IWhen you enable the aux heat heat function h1 the fan will delay turning off for 30 seconds to allow the auxiliary heater to cool down The delay occurs when the auxiliary heat...

Страница 24: ...faults on page 18 3 Press the Mode button to access the programmable value of the displayed function number The function s current value flashes on the display 4 Press the Up or Down buttons to change...

Страница 25: ...reduced There is low airflow through the system The airflow through the evaporator is blocked Inspect for and remove any obstructions in the return air stream Clean the return air filter and grille C...

Страница 26: ...oad is open due to lack of air flow though the condenser Allow the compressor to cool Turn the system off for a while it may take up to three hours to reset the thermal overload 10 2 Digital Controls...

Страница 27: ...before reprogramming the Q3 control Change Programmable Function 21 to increase the duration of the Anti Icing Routine If the anti icing cycle does not melt the ice switch the air conditioning unit t...

Страница 28: ...ntrol board The low pressure switch opens when the suction pressure drops below a preset minimum limit If the low pressure switch opens the unit will first run for two minutes and then shut down for 5...

Страница 29: ...conds the Q3 control shows a constant Cool or Heat Mode may be selected for emergency operation and the display will show a constant Emergency Operation Ar FL The Q3 control flashes Ar FL for 15 secon...

Страница 30: ...aning the Return Air Filter Check the Return Air Filter once a month or more often if local conditions and usage patterns dictate and replace or clean as necessary To clean the filter Remove the filte...

Страница 31: ...coils may result in reduced performance Avoid the use of the following Coil brighteners High pressure washers Poor quality water for cleaning Use of non recommended coil cleaners is strongly discoura...

Страница 32: ...Mobile living made easy dometic com YOUR LOCAL DEALER dometic com dealer YOUR LOCAL SUPPORT dometic com contact YOUR LOCAL SALES OFFICE dometic com sales offices...

Отзывы: