AH-Passport I/O Control Operations Manual

 

Programming

L-2232 ENGLISH

9

P-15: Electric Heat Option

Units may have an electric heater added to heat a cabin when the chiller system is in cooling mode. Electric heaters are also 
used to supplement the circulated water heating (via the hydronic valve) when necessary. Set to “ELE” for the electric heat 
option or set to “nor” to disable. 

For software revision A12 and older: 

When this parameter is programmed for electric heat, only the electric-heater 

relay located toward the middle of the circuit board is energized during a heating cycle. The electric-heater relay only 
exists on circuit boards with revision E or older. (See “Sample Wiring Diagram” on page 16.) 

For software revision A13 and newer:

 When programmed for electric heat, both the electric-heater relay and the 

compressor relay are energized. This change supports circuit boards with revision F and newer, without the electric-
heater relay. Therefore, circuit boards that do not have electric-heater relays require a display with software revision 
A13 or newer to properly energize the compressor relay. When using this configuration, the electric heater L1 
connection must be connected to the COMP L1 terminal on the AH-Passport I/O circuit board (see “Sample Wiring 
Diagram” on page 16). 

Installation Note: 

Since both the compressor-relay and electric-heat relay outputs only support a maximum of 30 

amps at 115VAC or 20 amps at 230VAC of resistive load, when installing an optional electric heater that exceeds this 
load, it is necessary to install an additional contactor that is rated to handle the full load of the electric heater. Please 
consult with Dometic Customer Service or with an authorized service technician for assistance.

P-16: Fan Motor Selection

The “SC” (Split Capacitor) default setting is correct for air handlers with high-velocity blowers. Only change the setting to “SP” if 
your unit has a Shaded Pole fan motor, recognizable by a blower-motor overhang and “F” in the model number (such as 
AT12FZ). The SC motor of a high-velocity unit is inside the blower, and the unit has

 

“HV” in the model number (such as 

AT12HVZ). 

If your air handler model has a Shaded Pole fan motor, you must change parameter P-16 to “SP” prior to 

operating the equipment.

 Save this change as a new default by simultaneously pressing and releasing the Up and Down 

buttons prior to exiting the program mode. Make note of new default in the Programmable Parameters table.

P-17: Reset Memorized Defaults

To reset all programming parameters set this parameter to “rSt”. This restores all programmable parameters to the 

last saved 

default values

. Once new values are entered and memorized the factory defaults are overwritten, and the new parameters 

become the default values. To restore the original factory default parameters manually, refer to Table 2, page 10.

P-18: Hydronic Water Valve Forced Open

This parameter opens the water valve to bleed air from the system. “OPn” forces the valve open for 4 hours while the AH-
Passport I/O control is turned off. If you want to utilize the system in its normal operating mode prior to completion of the 4-hour 
period, before turning on the AH-Passport I/O you must return the valve to its normal position by changing P-18 back to “nor” 
manually.

P-19: Water Temperature Differential

This parameter sets the temperature differential between ambient air temperature and hydronic water temperature that controls 
the water valve. For example, selecting 10° F opens the valve when water temperature is ten degrees less than ambient in 
cooling mode and 10°F greater than ambient in the heating mode.

Careful selection of the temperature differential can fully utilize the ship’s heating and cooling resources. For example, while in 
cooling mode and using a ten degree value, the valve will open to allow some cooling while the hydronic system is coming down 
to temperature. See Figure 2 on page 11 for a graphical explanation of this parameter.

P-20: Air Filter Cleaning/Replacement Timer Setting

(Available only in software revision A21 and newer.) 

Use this feature for a reminder to clean or replace the unit’s air filter. 

The parameter entered represents that number times 10 hours. Select the number of operating hours until the filter reminder 
appears. Parameter choices are between 10 (100 hours) and 250 (2500 hours). Dometic recommends that you check the air 
filter at least every 500 hours of operation. The default setting is off, designated with “00”. 

P-21: Filter Cleaning/Replacement Timer Value & Reset

(Available only in software revision A21 and newer.) 

This parameter displays the current elapsed time (in hours times 10) 

since the timer was started or reset. For example, if the value of P-21 is “30”, then between 300-399 hours have elapsed since 
the timer was started or reset. Once the value of P-21 reaches the value set in P-20 (explained above), “FIL” flashes on the LED 
display every 10 seconds until it is cleared. To clear the “FIL” reminder, press either the Up or Down button while viewing the P-
21 parameter. This resets P-21 to 0 and restarts the timer.

P-22: Voltage Calibration

(Available only in software revision A21 and newer.) 

This feature displays the voltage being read by the power and logic 

circuit board. It displays a live reading of the voltage and can be manipulated by pressing the Up or Down buttons. Use a 
reliable voltmeter as a reference when adjusting this parameter.

Содержание AH-Passport I/O

Страница 1: ...ritten consent by Dometic Marine Every precaution has been taken in the preparation of this manual to ensure its accuracy However Dometic Marine assumes no responsibility for errors and omission Neith...

Страница 2: ...Button Functions Dual 6 MODES OF OPERATION 6 Off Mode 6 On Mode 6 Automatic Mode 6 Cool Mode 6 Heat Mode 6 Moisture Mode 6 Fan Modes 6 Program Mode 7 USING PROGRAM MODE 7 Entering Program Mode 7 Exiti...

Страница 3: ...115 230 volt 50 60 Hz AC power supply User friendly four button display panel 5V microcontroller located in the display Option to display temperature in degrees Fahrenheit or Celsius Ambient air sens...

Страница 4: ...ic allowing fan speed to decrease as set point temperature is approached in the Cool Mode The fan operates at low speed when set point is satisfied Normally the automatic fan speed operation is revers...

Страница 5: ...dicators Table 1 AH Passport I O Display Diagram Legend 1 Cool Mode indicator 6 Temperature sensor 2 Fan indicator 7 Down button Lower temperature set point 3 Heat Mode indicator 8 Fan button 4 Digita...

Страница 6: ...Fan Speed is selected For more programming information on this feature see P 1 Operating Mode on page 27 When cooling or heating is required the water valve will not open unless the water temperature...

Страница 7: ...ndler Ensure that sensor makes good contact with the copper pipe DO NOT attach to rubber or plastic hose OPERATION OPERATOR CONTROLS AND DISPLAY PANEL Refer to Figure 1 page 3 for the button locations...

Страница 8: ...as required If the ambient temperature drops below the set point the system will not automatically switch to the Heat Mode HEAT MODE When Heat Mode is selected the Heat LED is lit and the heating syst...

Страница 9: ...l be saved and put into operation after exiting Program Mode and returning the control to the On Mode If you want the programming changes to become the new defaults see Memorizing New Program Paramete...

Страница 10: ...ol is set to display C P 6 through P 9 Reserved for future use P 10 Display Brightness Control The display brightness can be adjusted from 4 to 13 with 4 being the dimmest and 13 the brightest Typical...

Страница 11: ...t saved default values Once new values are entered and memorized the factory defaults are overwritten and the new parameters become the default values To restore the original factory default parameter...

Страница 12: ...n rEF Reversed Fan in Heat Mode P 14 Continuous Fan or Cycle Fan With Compressor con CYC Cycle Fan With Compressor con Continuous Fan Operation P 15 Chilled Water Heating or Electric Heat Option nor n...

Страница 13: ...ating Note that parameter P 19 setting increments are in F even when the control is set to display C Figure 2 Ambient Air to Water Temperature Differentialf IMPORTANT The system s air sensor is locate...

Страница 14: ...ting See the control s Operations Manual for instructions 4 Chilled water loop is inadequately cooled or heated chiller system is not in the proper mode of operation or Electric Heater is disabled If...

Страница 15: ...d triac on circuit board Send for repair or call local service technician Fan runs continuously although it is set to cycle with cooling heating demand Failed triac on circuit board Send for repair or...

Страница 16: ...ay 20 Amps 230 V DIMENSIONS Compact model Display Panel 3 19 82mm X 2 5 64mm Compact model Panel Cut Out 2 4 61mm X 1 8 46mm Legacy model Display Panel 4 5 114mm X 3 86 98mm high Legacy model Panel Cu...

Страница 17: ...Layout Example Diagram Legend 1 Electrical Box 6 Water Inlet Sensor 2 Optional Outside Air Sensor 7 Control Display Panel 3 AC Wire Harness 8 8 Conductor Shielded Display Cable 4 6 Conductor Shielded...

Страница 18: ...ons Manual 16 L 2232 ENGLISH SAMPLE WIRING DIAGRAM Figure 4 Sample Digital Control Wiring Diagram IMPORTANT This is a sample diagram Wire colors may vary See unit s specific diagram located in electri...

Страница 19: ...AH Passport I O Control Operations Manual Sample Wiring Diagram L 2232 ENGLISH 17...

Страница 20: ...Dometic Marine Rev 20090710 L 2232 English www dometicusa com...

Отзывы: