domat UC120 

03/2017 Subject to technical changes. 

-

 

Setpoint  temp.  Cooling  Off  mode  (Temperature,  Cooling,  Empty  house  are 
flashing) 

 
Select the requested value by a short push. Turn knob to change value. Confirm by a 
short push again.  
 
If there is no user activity for 30 s, the controller goes to the basic display mode. 
 
Default values: 
 
The default values as well as all other settings (PI parameters, address, baudrate...) can 
be set by the configuration program, ModComTool.  
 

Dimensions 
 
 
 

 

All dimensions in 

mm

 

Содержание UC120

Страница 1: ...gorithm brought to one 0 10 V DC output All values are displayed on a large LCD display The functionality and control parameters i e P and I constants and hysteresis can be set with ModComTool the configuration software which is free to download at http domat int com en downloads software The controller contains real time clock with a weekly scheduler 6 events per day It changes between three oper...

Страница 2: ...current Resolution 1x 0 10 V DC 10 mA corresponding to 1 kOhm load 50 mA tolerant to permanent short circuit 10 bit D A converter Setpoint correction according to configuration 10 to 1 K Communication RS485 separation Baud rate 2 wire RS485 Modbus RTU slave optically separated up to 1000 V selectable 1200 9600 115200 bps Display LCD 60 x 60 mm Terminals screw terminals for 0 14 1 5 mm2 wires Cover...

Страница 3: ...erator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At the back of the bottom there is an aperture for cabling The bottom should be installed and cabling connected first and the upper part inserted after the construct...

Страница 4: ...m the event selection Turn the knob to select the operation mode Day Night Off Event inactive invoked by this event If the event is not active the operation mode is not changed at the set time Short push to confirm the operation mode setting The event time displays Turn the knob to set the time of the event and confirm by a short push Then turn the knob to select another event or long push and tur...

Страница 5: ...sted value by a short push Turn knob to change value Confirm by a short push again If there is no user activity for 30 s the controller goes to the basic display mode Default values The default values as well as all other settings PI parameters address baudrate can be set by the configuration program ModComTool Dimensions All dimensions in mm ...

Страница 6: ... Belden 8205 cable A terminal is designed for maximum 3 wires of 0 8 mm2 Temperature compensation After switching the unit on allow about 90 mins to dissipate the heat inside of the housing Then the sensor is measuring correctly Do not change the sensor correction variable immediately after powering the device on RoHS notice The device contains a non rechargeable battery which backups the real tim...

Страница 7: ... versions 08 2016 Changed reference to the configuration software Added picture and description of the installation and link on the datasheet with other colours 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...