domat UC013 

08/2018 Subject to technical changes. 

1

 

 

 

 

UC013 

Room unit for controller FCR013 

 

 

 

 

 

Summary 

The UC013 room unit is a communicative human-machine interface for EC motors or 
VAV unit controller FCR013. 
 
According to production type, each version of the unit may contain display, backlight  
and knob. 
 

UC013 

 basic version with display and knob 

UC013BL 

 version with display, knob and backlight 

UC013DK 

 version without knob and display 

 

Application 

 

EC  motors  or  VAV  systems 

  measurement  and  control  of  room 

temperature. 

Function 

The unit reads room temperature, temperature correction / setpoint by a knob, and 
required operation mode which is set by a short push. Data is transmitted to the room 
controller.  The  main  controller,  FCR013,  may  send  to  the  unit  other  data  (heating  / 
cooling mode, fan stage, day / night / standby mode etc.) which are displayed on the 
LCD display.  
 
Connect the room unit to FCR013 over a 4 core cable, the most suitable types are JY(St)Y 
or LAM 2x2x0.8. Use the same type which powers the FCR013 controller as if the room 
unit power is taken from the FCR013 terminals, the cores in a terminal should be of the 
same cross-section. 
 
If there is communication failure between UC013 and FCR013, there is a wrench and 
alarm  bell  icon  at  the  UC013  display.  Check  signal  polarity  (terminals  3,  4),  bus 
termination, and correct wiring at the FCR013 side (see FCR013 data sheet). 
 

Technical data 

Power supply 

24 V AC +/- 20% 

Consumption 

1 W 

Communication 

RS485, Modbus RTU,  

selectable speed 1200 ... 115200 bps 

SW 

ModComTool 

Содержание UC013

Страница 1: ... push Data is transmitted to the room controller The main controller FCR013 may send to the unit other data heating cooling mode fan stage day night standby mode etc which are displayed on the LCD display Connect the room unit to FCR013 over a 4 core cable the most suitable types are JY St Y or LAM 2x2x0 8 Use the same type which powers the FCR013 controller as if the room unit power is taken from...

Страница 2: ...ic class 3K5 Storage 5 45 C 5 95 relative humidity non condensing gases and chemically non aggressive conditions according to EN 60721 3 1 climatic class 1K3 Standards conformity EMC EN 61000 6 2 ed 3 2005 EN 61000 6 4 ed 2 2006 A1 2010 industrial environment Electrical safety EN 60950 1 ed 2 2006 A11 2009 A12 2011 A1 2010 A2 2014 Opr 1 2012 Z1 2016 Hazardous substances reduction EN 50581 2012 Ver...

Страница 3: ...e operated easily and measure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At...

Страница 4: ...en changing between the Comfort and Standby modes the controller falls back into automatic fancoil stage control according to the control deviation Operation mode change The operation mode in the Hotel mode used for fancoils in hotels and offices is changed over bus communication or by activating digital inputs The DI1 switches between the Comfort and Standby modes e g card reader while DI2 brings...

Страница 5: ...t temp Heating Night mode Temperature Heating Night are flashing Setpoint temp Heating Off mode Temperature Heating Empty house are flashing Setpoint temp Cooling Day mode Temperature Cooling Day are flashing Setpoint temp Cooling Night mode Temperature Cooling Night are flashing Setpoint temp Cooling Off mode Temperature Cooling Empty house are flashing Select the requested value by a short push ...

Страница 6: ... air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks related to device operation must be considered together with design installation and operation of the entire control system which the device is part of ...

Страница 7: ...hanged the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 07 2017 Change of technical data standards and images BL version added 08 2017 Controller description change FC to FCR version 08 2018 Minor changes ...

Отзывы: