background image

 

domat UC011 

06/2020 Subject to technical changes. 

1

 

 

 

 

UC011 

Room unit for fancoil controller

 

FCR010

 

 

 

 

 

Summary 

The UC011 room unit is a communicative human-machine interface with galvanically 
separated communication for fancoil controller FCR010 or FCR011. 
 
According to production type, each version of the unit may contain display, backlight  
and knob. 
 

UC011 

 basic version with display and knob 

UC011BL 

 version with display, knob and backlight 

UC011DK 

 version without knob and display 

 

Application 

 

Fan coil systems 

 measurement and control of room temperature 

Function 

The unit reads room temperature, temperature correction / setpoint by a knob, and 
required  operation  mode  which  is  set  by  a  short  push  or  in  the  menu.  Data  is 
transmitted to the fancoil controller. The fan coil controller may send to the unit other 
data (heating / cooling mode, fan stage, day / night / standby mode etc.) which are 
displayed on the LCD display.  
 
Connect the room unit to FCR010 over a 4 core cable, the most suitable types are JY(St)Y 
or LAM 2x2x0.8. Use the same type which powers the FCR010 controller as if the room 
unit power is taken from the FCR010 terminals, the cores in a terminal should be of the 
same cross-section. Attention, the FCR011 has a supply voltage 230 V. Please do not 
connect UC011 to the FCR011 power supply.  
 
If  there  is  communication  failure  between  UC011  and  FCR010/FCR011,  there  is  a 
wrench and alarm bell icon at the UC011 display. Check signal polarity (terminals 3, 4), 
bus termination, and correct wiring at the controller side (see FCR010 or FCR011 data 
sheet). 
 

Technical data 

Power supply 

24 V AC +/- 20% 

Consumption 

1 W 

Communication 

RS485, Modbus RTU,  

selectable speed 1200 ... 115200 bps 

Содержание UC011

Страница 1: ... the fancoil controller The fan coil controller may send to the unit other data heating cooling mode fan stage day night standby mode etc which are displayed on the LCD display Connect the room unit to FCR010 over a 4 core cable the most suitable types are JY St Y or LAM 2x2x0 8 Use the same type which powers the FCR010 controller as if the room unit power is taken from the FCR010 terminals the co...

Страница 2: ...ic class 3K5 Storage 5 45 C 5 95 relative humidity non condensing gases and chemically non aggressive conditions according to EN 60721 3 1 climatic class 1K3 Standards conformity EMC EN 61000 6 2 ed 3 2005 EN 61000 6 4 ed 2 2006 A1 2010 industrial environment Electrical safety EN 60950 1 ed 2 2006 A11 2009 A12 2011 A1 2010 A2 2014 Opr 1 2012 Z1 2016 Hazardous substances reduction EN 50581 2012 Ver...

Страница 3: ...e operated easily and measure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At...

Страница 4: ...en changing between the Comfort and Standby modes the controller falls back into automatic fancoil stage control according to the control deviation Operation mode change The operation mode in the Hotel mode used for fancoils in hotels and offices is changed over bus communication or by activating digital inputs The DI1 switches between the Comfort and Standby modes e g card reader while DI2 brings...

Страница 5: ...t temp Heating Night mode Temperature Heating Night are flashing Setpoint temp Heating Off mode Temperature Heating Empty house are flashing Setpoint temp Cooling Day mode Temperature Cooling Day are flashing Setpoint temp Cooling Night mode Temperature Cooling Night are flashing Setpoint temp Cooling Off mode Temperature Cooling Empty house are flashing Select the requested value by a short push ...

Страница 6: ... air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks related to device operation must be considered together with design installation and operation of the entire control system which the device is part of ...

Страница 7: ...nce to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 07 2017 Change of technical data standards and images BL version added 08 2017 Controller description change FC to FCR version 08 2018 Minor changes 06 2020 Added the ability to use the FCR011 controller ...

Отзывы: