![Dolphin pro HD+ 24V100A Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/dolphin/pro-hd-24v100a/pro-hd-24v100a_technical-manual_2517344012.webp)
NOT-DOLPROHD-00
NOT-DOLPROHD-00
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
EN
Technical specifications
24V 40A
24V 60A 24V 100A
MAINS POWER CHARACTERISTICS
Mains power voltage
115V 60Hz and/or
230V 50Hz (+/-15%)
230V
(+/-15%)
Power factor
0.9 typ.
Efficiency
87 typ.
Inrush current
< 30A, limited by
soft start
< 60A
Consumption
14A/6A
15A/9A
15A
Active power
1350VA
2000VA
3500VA
Derating @ 115V
Without
derating
70%
Pnom
-
Mains power fuse
T20A
(6.3x32
mm)
T20A
(6.3x32
mm)
2xT20A
(6.3x32
mm)
BATTERY CHARGING CHARACTERISTICS
Number of outputs
3 independent supplies
Number of cycles
10 charge cycles (0 to 9), se-
lectable by rotary selector
Charge curves
In general 3 statuses, type
I.U.Uo
Open lead-acid
V.BOOST = 28.8V
V.FLOAT = 26.4V
Sealed lead-acid
V.BOOST = 28.4V
V.FLOAT = 27.2V
Lead-calcium
V.BOOST = 29.6V
V.FLOAT = 27.6V
“Delphi” type
V.BOOST = 30.8V
V.FLOAT = 27.6V
“Optima”
type
V.BOOST = 29.6V then 31.0V
V.FLOAT = 27.6V
Winter storage open lead-
acid
V.BOOST = 28.8V
V.FLOAT = 26.4V
Winter storage sealed
lead-acid
V.BOOST = 28.4V
V.FLOAT = 27.2V
24V 40A
24V 60A
24V 100A
Gel & AGM
V.BOOST = 28.8V
V.FLOAT = 27.6V
Power supply
V.FLOAT = 27.2V
L integral BMS
V.FLOAT = 28.8V
Temperature
compensation
+/-25mV / °C
(by an external sensor)
Voltage tolerance
+/-2%
Ripple
< 1 % (BW < 20 MHz)
Maximum current
40A
(+/-5%)
60A
(+/-5%)
100A
(+/-5%)
-DC supply fuse
3 x F25A
(miniature automo-
tive fuse)
5 x 30A
(miniature
automo-
tive fuse)
PROTECTION
Overload in output
“Current limited” type
Short circuit in output
“Shutdown” type with automatic
restart when fault is cleared.
Output voltage too high
“Shutdown” type with automatic
restart when fault is cleared.
Battery reverse polarity
Output fuse
Internal temperature
too high
“Shutdown” type with automatic
restart when fault is cleared.
Battery temperature
too high
“Shutdown” type with automatic
restart when fault is cleared.
Temperature sensor
out of service
“Shutdown” type with automatic
restart when fault is cleared.
Mains power supply
general fault
Mains power fuse
Battery supply
general fault
Output fuses on –DC supply
Climatic conditions
Tropicalised electronics board