The sensors must be connected to the exact ports on the screw terminals as illustrated below. Max current per port is
83 mA.
Minimum cable size depends on the distance to the sensor, please refer to the table below:
Distance
mm
2
AWG
<50 m
Min. 0.5 mm
2
Min. 20 AWG
50-100 m
Min. 0.75 mm
2
Min. 18 AWG
100-150 m
Min. 1.0 mm
2
Min. 17 AWG
Front LED
On completion of mounting, installation and powering up, the tree LEDs on the front will indicate the status of the iDOL 63.
Power LED
– Green, ON
iDOL 63 is powered
Status LED
– Green, ON
iDOL 63 is connected to the internet
Status LED
– Green, flashing
No connection to the internet
Status LED
– Red, ON
Internal error
Status LED
– Red, flashing
Inernal memory full
Figure 4: Label with MAC address can be found on the circuit board