13- Operating Limits Of Fans
WARNING:
It is not permitted to operate fans at higher speeds other than design speed, without written
permission of DOGU IKLIMLENDIRME A.S., since operating at higher speeds may overload and damage the
motor and fan.
FAN TYPE
ADH
MAXIMUM
INSTALLED
POWER
kW
MAXIMUM
SPEED
rpm
160L, 160R
180L, 180R
200L, 200R
200K
225L, 225R
225K
250L, 250R
250K
280L, 280R
280K
315L, 315R
315K
315K1
355L, 355R
355K
355K1
400L, 400R
400K
400K1
450L, 450R
450K
450K1
500L, 500R
500K
500K1
500K2
560L, 560R
560K
560K1
560K2
630L, 630R
630K
630K1
630K2
710K
710K1
710K2
800K
800K1
800K2
900K
900K1
900K2
1000K
1000K2
3
3
4
4
4
4
4
7.5
5.5
11
5.5
11
18.5
7.5
15
22
7.5
15
22
11
15
30
11
15
30
37
15
18.5
30
45
15
18.5
30
45
22
37
55
22
37
55
30
45
75
37
75
4200
4000
3800
3800
3400
3400
2800
3000
2500
2700
2100
2400
2400
1800
2000
2000
1600
1800
1800
1400
1500
1500
1200
1300
1400
1400
1100
1200
1300
1300
900
1000
1100
1100
850
900
900
750
800
800
650
700
700
600
650
Air Handling Unit Installation, Operation And Maintenance Instructions
www.doguhvac.com
37
FORWARD CURVED BLADE FANS, TYPE “ADH”
Содержание FourSeason KKS 062 - 046
Страница 12: ...10 www doguhvac com Air Handling Unit Installation Operation And Maintenance Instructions ...
Страница 17: ...Air Handling Unit Installation Operation And Maintenance Instructions www doguhvac com 15 ...
Страница 18: ...16 www doguhvac com Air Handling Unit Installation Operation And Maintenance Instructions ...
Страница 19: ...Air Handling Unit Installation Operation And Maintenance Instructions www doguhvac com 17 ...
Страница 51: ...Air Handling Unit Installation Operation And Maintenance Instructions www doguhvac com 49 NOTES ...
Страница 52: ......
Страница 53: ......