SIR 16 L
Load output 15/18 (1.1/1.5)

Type of contact

1 NOC (electrically isolated)

Switching voltage

230 V AC

Continuous current

max. 16 A

Switching capacity 
cos φ = 1

max. 4,000 W

Switching capacity 
cos φ = 0.5

max. 3,200 VA

Switching capacity 
with lead-lag circuit or 
series compensation

max. 4,000 VA

Capacitor for paral-
lel compensation

64 μF

Switch status 
indicator

by internal LED

M

echanical 

 endurance

> 30 × 10

6

 cycles

Ohmic load  
at nominal load

> 70,000 cycles

I

ncandescent lamp 

load

15 × 150 W = 2,250 W: > 125,000 cycles 

5 × 60 W = 300 W: approx. 400,000 cycles

H

igh-voltage 

 halogen lamp load

5 × 500 W = 2,500 W: > 10,000 cycles 

5 × 60 W = 300 W: approx. 400,000 cycles

M

onitoring load  

TV8 (UL508)

approx. 25,000 cycles

Fluorescent lamps

uncomp./series compensated: 18 × 58 W: approx. 50,000 cycles

lead-lag circuit: 9 × (2 × 58 W): approx. 50,000 cycles

parallel compensated: 2 × 58 W (7 μF): approx. 50,000 cycles

E

nergy-saving lamps

with conventional ballast type Opal Compacta 4 x 25 W: 

approx. 50,000 cycles

with electronic ballast type Dulux: approx. 50,000 cycles

Small DC loads 
100 mA / 20 V DC

> 10

7

 cycles

H

QL lamp loads

with conventional ballast 8 × 125 W: approx. 30,000 cycles 

with parallel compensation 64 μF: approx. 30,000 cycles

Terminals

Type

screw terminal with strain-relief clamp

Tightening torque

max. 0.6 Nm

Terminal 
 cross-section

0.4 mm – 2.5 mm²

Housing

Type

Distribution board housing for mounting on DIN rail

D

imensions

17.8 × 85 × 58 (W × H × D in mm) / 1 module width

M

aterial

Polycarbonate (PC)

General data

Operating tem-
perature

-10 °C to +45 °C

H

umidity

max. 85% (exposure to dew not permissible)

Type of protection

IP 40 after installation in distribution board

D

esign requirements

DIN EN 60669

M

ass

78 g

I

tem No

09500153

Connection diagram

A4

B1

A3

B2

A1

A2

SIR 16 L

15

18

~230 V

16 A

24 V DC
  0 V DC

L1
N

monostabil ein

Wechsel ein/aus

ein 

(on)

aus 

(off)

externe Anzeige

(one-shot on)

(two-way on/off)

2,2 - 5,6 

k

(external display)

1.1

1.5

1.2

1.6

1.3

1.7

1.4

1.8

Installation and Operating Manual

Impulse Relay SIR 16 L

General

The SIR 16L impulse relay is a component of the SI Building Management System and 
can also be employed for non-system-dependent control duties. As a standard mon-
ostable/single-shot relay or as impulse relay the SIR 16L can be activated via various 
inputs. These inputs are triggered by a control voltage of 24 V DC.

Input/output functions

Only momentary control voltage pulses affect a change in switch status at the im-
pulse inputs A2-A4.  A control voltage permanently applied at one or more impulse 
inputs will not cause a change in switch status and does not affect the function of any 
other inputs. Activation via the monostable input A1 by a permanently applied con-
trol voltage takes precedence over all other control commands at the impulse inputs.

Terminal

Function

A1 / 1.2

Control input for monostable function, output for connecting 
an external switch status indication.

A2 / 1.6

Control input, alternating on/off

A3 / 1.7

Control input, off only

A4 / 1.3

Control input, on only

15,18 / 1.1,1.5

Load contact, electrically isolated NOC

B1 / 1.4

Power supply 0 V DC

B2 / 1.8

Power 24 V DC

Mounting

Installation may only be carried out by an authorized, trained technician. Assembly 
occurs by means of quick fastening on mounting rails, whereby any installation posi-
tion may be used. While installing please comply with the connection diagram. All 
leads to be connected must be dead.

Command Devices

Devices suitable as control units are all those whose output corresponds to the func-
tion of an on/off switch of 24 V DC. The following conditions must be met:

1.  The bounce time when the contact closes must not exceed 10 ms.
2.  The maximum permissible contact resistance (Rmax) of the control device is de-

pendent upon the number (n) of the SI components to be triggered simultane-
ously and may not exceed 1000 Ω: Rmax = 1.000 Ω/n.

In the case of commercially available switches with mechanical contacts these re-
quirements are normally met. However, with control devices featuring semiconduc-
tor outputs attention should be paid both to the resistance of the semiconductor and 
the residual voltage drop.

Guarantee

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory guarantee period from the day of purchase by the end user. The guaran-
tee is not applicable to damage incurred during transport or caused by short-circuit, 
overloading  or  improper  use.  In  the  event  of  defects  in  workmanship  or  material, 
which are discovered within the guarantee period, the company will provide a repair 
or replacement free of charge. The guarantee will be rendered null and void if the 
device is opened without authorization.

Technical Data

SIR 16 L

Power supply

24 V DC ± 10 %

Control inputs with impulse function

A2

alternately on/off

A3

off only

A4

on only

Control voltage

24 V DC ± 10 %

Control current

max. 4 mA at switching moment

Length of  
control cable

max. 1000 m, for up to 20 parallel inputs and a dia. of 0.6 mm

Permissible bounce 
time of switch

max. 10 ms

R

equired trigger 

impulse length

min. 20 ms

Combined input/output A1 (1.2)

I

nput function

 control input for monostable on keying  

Output function

  switching synchronous with load contact  

Output voltage  

 as operating voltage  

Load rating

max. 200 mA