Installation and Operating Manual

for twilight switches EDS 16 and EDS 2 E with light 
sensor LF 1

Intended use and mounting

The EDS 16/EDS 2 E is a twilight switch for distribution board installation with light 
sensor LF 1, which is designed for outdoor use. It is possible to install the switch and 
external light sensor anywhere, regardless of the lighting to be switched; the distri­
bution board easily handles the settings for the switch-on/switch-off thresholds. The 
twilight switch may only be installed by an authorised, trained technician.  Any instal­
lation position may be used. Snap onto mounting rail according to DIN EN 60715 in 
the distribution board. 

Operating more than one twilight switch: up to 10 twilight switches (EDS 16/EDS 2 E) 
can be operated in parallel with one light sensor LF 1. Light sensor LF 1 is connected 
to an EDS 2 E at terminals S1/S2. From this EDS, terminals S3/S4 are then bridged to 
the other S3/S4 terminals on subsequent EDS devices. It is beneficial to install light 
sensor LF 1 on an outdoor wall that is protected from direct sunlight. North or east-
facing walls are ideal. The cable entry point must always be directed downwards in 
order to protect the sensor from moisture damage. If the switch should only switch 
on when it is as dark as possible, ensure that the amount of light reaching the sensor 
is not disrupted by overhanging roofs or similar installations. Ensure that the lighting 
to be switched on does not influence the sensor so strongly that the twilight switch is 
switched off again due to the increased brightness.

EDS 16

Functionality: the twilight switch compares the current illuminance with the set 
switch-on  threshold.  If  the  illuminance  reaches  the  desired  switch-on  threshold, 
a delay time starts. Once the delay time has expired the load relay of the twilight 
switch is switched on. If the switch-off threshold is reached due to increasing illu­
minance,  the  relay  switches  off  again  after  the  delay  time  has  expired.  The  delay 
ensures that the load relay of the twilight switch does not respond to brief lighting 
fluctuations (e.g. lightning, car headlights). 

Commissioning: during commissioning, after connecting the light sensor and oper­
ating voltage, turn the potentiometer to the left stop to set the switch-on threshold. 
If one or both of the control diodes illuminates, these will go off within the switch-off 
delay time of 60 s. If both control diodes are off and the outdoor brightness is at the 
desired level, the potentiometer should slowly be turned right until the green control 
diode  illuminates.  This  process  sets  the  switch-on  threshold  to  the  desired  illumi­
nance. The load relay switches on after the switch-on threshold has been reached 
and the delay time has expired. The red control diode indicates the switching status. 

The switching hysteresis defines the ratio of switch-off threshold Eoff to switch­on 
threshold Eon. On EDS 16 models, this fixed parameter is set by the factory. 

EDS 2 E

Functionality:  the EDS 2 E compares the brightness, which it measures in regular 
intervals, with the set switch-on/switch-off threshold. If the brightness falls below 
the set switch-on threshold, the load relay of the EDS 2 E switches on after the de­
lay time has expired. If the brightness exceeds the set switch-off threshold, the relay 
switches off once the delay time has expired. The delay ensures that the load relay 
of the twilight switch does not respond to brief lighting fluctuations (e.g. lightning, 
car headlights).

Commissioning:  after  the  light  sensor  and  operating  voltage  are  connected,  the 
EDS 2 E then starts an initialisation phase. This phase lasts approx. 30 min. during 
which  the  EDS  2  E  detects  the  increasing/decreasing  ambient  brightness  curves. 
Once the initialisation phase is complete,. the EDS 2 E defines its operating point in 
the day/night rhythm, which assigns the set thresholds to the corresponding curve. 
The desired switching thresholds can be set separately using a potentiometer. Turn­
ing the potentiometer anti-clockwise makes the switching threshold darker. Turning 
the potentiometer clockwise makes the switching threshold lighter. 

When the switch-on/switch-off threshold is reached, this is indicated by an instanta­
neous LED that has been assigned accordingly. A delay time starts when the switch-
on/switch-off threshold is reached. Once the delay time has expired the load relay 
switches on or off. A red LED indicates the switching status of the load relay.

Important: the EDS 2 E functions predominately in switch-on mode during the ini­
tialisation phase due to safety reasons. During this time the load relay is switched 
on without delays if the brightness falls below the switch-on threshold, and stays on 
until the initialisation phase is complete, even if the switch-off threshold is exceeded 
later. The switch can only be reset prematurely by interrupting the operating voltage.

Technical Data

Twilight switch EDS 16/EDS2 E 

Twilight switch

EDS 16

EDS 2 E

Operating voltage

230 V AC +10%/50–60 Hz

Internal consumption

1.6 W

Adjust­
ment 
ranges 
(loga­
rithmic 
setting)

Switch­on 

threshold

2–1000 lux

0.1–1000 lux

Switch-off 

threshold

0.1–1000 lux

Switching 

hysteresis

Fixed parameter set by 

factory to 1.5 times the 

switch-on threshold

Output

Design

Relay, 1 NO contact (potential-free)

Switch-on/

switch-off 

delay

60 s

Nominal 

data

~230 V/16 A

Switching 
status 
indica­
tors

Switch­on 
threshold, 

instantane­

ous

Green LED

Relay status, 

delayed

Red LED

Switch-off 

threshold, 

instantane­

ous

Green LED

Protection class

IP40 when installed in distribution board

Housing

Polycarbonate (PC)

Mounting

On mounting rail DIN EN 60715

Ambient temperature

 -10°C to 45°C

Light sensor LF 1 

Internal consumption

Max. 10 mA

Max. cable length

100 m with Ø 0.6 mm

Protection class

 IP44

Safety class

III (ELV)

Housing

Polycarbonate (PC)

Ambient temperature

 -25°C to +60°C

Guarantee

All professionally installed, unaltered devices are covered by warranty during the stat­
utory guarantee period from the day of purchase by the end user. The guarantee is not 
applicable to damage incurred during transport or caused by short-circuit, overloading 
or improper use. In the event of defects in workmanship or material, which are discov­
ered within the guarantee period, the company will provide a repair or replacement 
free of charge. The guarantee will be rendered null and void if the device is opened 
without authorisation.

Wiring diagram

S3

S4

S1

S2

EDS 16 / EDS 2 E

2.7

2.3

1.3

1.7

L1
N

2.1

2.5

15

18

L

2.4

N

2.8

15

18

weitere EDS

(further EDS)

LF 1

S 1 S 2

Doepke

3932101 | 11/2013 | Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden

DE EN