Message
Description
DALI fault
display
1)
There is at least one fault on the DALI bus. Press the
middle keys to confirm and access individual messages.
DALI bus idle
There is no active device on the bus.
Inspect the control gear.
Device error
At least one control gear device is not responding. The
display indicates the relevant device number. You can
consult the numbers of other faulty devices by pressing
the far-right key.
Lamp failure
At least one control gear device is reporting a lamp fail-
ure. The display indicates the relevant device number.
You can consult the numbers of other devices affected
by lamp failures by pressing the far-right key.
New dev
detected
Gateway has detected at least one control gear device
that has not yet been taught-in. Perform the "Search for
new device" command in the "Device setup" menu.
DALI error
short circuit
The DALI bus's overcurrent monitoring has responded,
usually due to a short-circuit. The gateway attempts to
restart the bus roughly once every 10 s. This can result
in a further temperature increase and cause subsequent
errors�
DALI overload
fault
A DALI bus overload has been detected. This can be
caused by excessive power being consumed by control
gear or as a result of a short-circuit (see above). Check
the bus for a possible short-circuit and ascertain the
total power demand of all the devices. If applicable,
replace any control gear that has an excessively high
power demand.
Dupline fault/
no bus signal
The Dupline bus signal is not present or is incorrect.
Check the terminals and the operation of the channel
generator.
1)
These control gear faults are displayed during manual device
diagnostics or if the "auto" diagnostic mode was selected in the system
settings.