TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-121
Monday
, November 26, 2001 1:09 pm
Dwell Time
The callouts (
B
and
C
) in Figure A.144 on page A-122 show the
parameters and specifications that effect Dwell times for a breaker.
B
This is the time when all Main Contacts within a
phase are closed during trip-free operation
(Figure A.142).
Figure A.142 Trip-Free Test Operation for a Phase (Live Tank Breaker)
Within the phase, the Dwell time (Figure A.144 on page A-122) is
measured as the difference between the time required for the first
Main Contact to open and the last Main Contact to close.
C
This is the time when all Main Contacts within the
circuit breaker are closed during trip-free operation
(Figure A.143).
Figure A.143 Trip-Free Test Operation Within a Breaker
(Live Tank Breaker)
Contact #1
Contact #2
Last to close
First to open
Dwell
Time
0
A
Contact #1
Contact #2
Last to close
First to open
Dwell
Time
0
A
0
B
0
C
#1
#2
#3
#4
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...