Figure A.98 shows how overtravel and rebound operate during a circuit
breaker opening operation.
Figure A.98 Overtravel/Rebound Open
Overtravel,
Rebound – Close
Parameters include:
Overtravel
The distance between the maximum temporary
displacement of the Circuit Breaker Main Contact
beyond the final closed position. Negative
tolerance for overtravel must never be greater than
the specified overtravel.
Rebound
The distance between the maximum temporary
displacement of the Circuit Breaker Main Contacts,
which is short of the final closed position. Negative
tolerance for rebound must never be greater than
the specified rebound.
Figure A.99 shows how overtravel and rebound operates for a circuit
breaker closing operation.
Figure A.99 Overtravel/Rebound Closed
Starting Closed
Overtravel
Rebound
Final Open
Position
Position
Starting Closed
Final Closed
Overtravel
Rebound
Position
Position
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...