Figure A.97 shows timing for Total Travel and Contact Wipe.
Figure A.97 Total Travel and Contact Wipe Operation
Overtravel,
Rebound – Open
Parameters include:
Overtravel
This is the distance between the maximum
temporary displacement of the Circuit Breaker
Main Contacts beyond the final open position.
Negative tolerance for overtravel must never be
greater than the specified overtravel.
Rebound
This is the distance between the maximum
temporary displacement of the Circuit Breaker
Main Contacts which is short of the final open
position. Negative tolerance for rebound must
never be greater than the specified rebound.
Module #1
Module #1
Module #2
Module #1
Module #2
Module #2
#!
#2
#3
#4
#!
#2
#3
#4
Contact #1
Contact #2
Contact #3
Contact #4
0
A
0
C
0
20
40
60
Time (ms)
0
B
80
Travel 3
100
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...