Test Plan Items
A-72
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Main Contact
Timing – Close
Parameters include:
Minimum
The minimum time for the Main Contacts to make.
Maximum
The maximum time for the Main Contacts to make.
Figure A.84 shows how contact timing occurs on a module-by-module
level.
Module (A)
The maximum allowable difference in time
between the closing of the two Main Contacts in
any module.
Phase (B)
The maximum allowable difference in time
between the closing of any two Main Contacts in a
phase.
Breaker (C)
The maximum allowable difference in time
between the closing of any two Main Contacts in a
circuit breaker.
Figure A.84 Main Contact Timing – Close Breaker
Module #1
Module #1
Module #2
Module #1
Module #2
Module #2
#!
#2
#3
#4
#!
#2
#3
#4
Contact #1
Contact #2
Contact #3
Contact #4
Main Contact
opening time
C
0
A
0
B
0
C
0
20
40
60
80
100
Time (ms)
First Switch to Last Switch
B
A
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...