Table A.4 lists the test voltages used when testing Main Contacts.
If the command current range selected is too small for the actual current
applied, the current recorded in the masthead reads
*Over*
. The current
on the graphical output appears clipped. The performance of the test is
not affected (Figure A.77).
Figure A.77 Breaker Performance Report Header
Table A.4 Voltages Used When Testing Main Contacts
ITEM TESTED
RANGE SELECTION
TEST VOLTAGE
Resistor, EHV
10 – 300 Ohms
7.5 V
Resistor, EHV
200 – 500 Ohms
15 V
All without resistors
None
15 V