
TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-59
Monday
, November 26, 2001 1:09 pm
The Transfer Function is shown in Figure A.70.
Figure A.70 Transfer Function Resolution
If the Main Contacts have moved 30"
, th
at means that for every 0.00125"
movement of the Transducer connecting rod, the Main Contacts would
move 0.00375". Consequently, when the Transfer Function 3:1 is used,
the resolution becomes 0.00125 x 3 = 0.00375".
Practical considerations limit the value of the Transfer Function values.
The Instrument checks to ensure that linear-to-linear Transfer Function is
less than or equal to 50:1.
Figure A.71 shows an example of the rotary-to-linear Transfer Function.
Figure A.71 Rotary-To-Linear Transfer Function
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...