Test Plan Items
A-40
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
If, in the example shown in Figure A.40, the range selected was 20 A
instead of 5 A, then 30% FS = 0.3 X 20 = 6 A, which is a value that close
current never reaches. Consequently, the Instrument will not record any
time in the tabulations.
Figure A.40 Close Timing from Close Current Measurement
Analog:
Current/Voltage
Magnitude
Timing a close test based on current/voltage magnitude for a particular
channel is achieved through the combination of the Close Pulse, Timing
Event, Timing Trigger, Timing Channel parameters (Figure A.41).
Figure A.41 Set Magnitude of Analog Measurement
Close Current
30% FS = 3 X 5 = 1.5 A
3 Amp
Amps
5
0
t
2
t
1
0
10
20
30
40
50
60
Time (ms)