Connecting the TDR9000
™
4-4
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Configuring Analog/Auxiliary Channels for First Trip/Close Tests
Connecting leads for a First Trip/Close test consist of:
• TDR9000 Connections
• Circuit Breaker Connections
Connecting the TDR9000
™
Table 4.1 and Table 4.2 list the connections to the TDR9000 required
for a minimum set of channels and a recommended set of channels,
respectively. Since this is an external trigger test, no control cables are
used.
*Connect to an Event module if using Aux Contact trigger source, and to
the Trigger In jacks on the System module if using the Trigger In source.
Table 4.1 TDR9000
™
Using a Minimum Set of Channels
Item
Signal
Type
TDR9000 Module
Connection
1
Main Contact
(from CT secondary)
Analog
Event
2
Trip relay coil
current
Analog
Event
3
DC Supply voltage
Analog
Event
4
52CS/T contact state
(for Trigger In source)
Auxiliary Contact Event or Trigger In*
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...