14
EN
IT
2.0 TECHNICAL DATA
• Use
: non-aggressive gases of the three families (dry gases)
• Ambient temperature
: -20 ÷ +60 °C
• Supply voltages (see table 2)
: 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
• Supply voltage tolerance
: -15% ... +10%
• Electric wiring
: cable gland PG 11
• No. cycles/hour**
:
DN 32 - DN 40 - DN 50 - DN 65 - DN 80 - DN 100
~
195 (ON time 5s - OFF time 13.5s)
DN 125 - DN 150
~
90 (ON time 10s - OFF time 30s)
• Absorbed power
: see table 2
• Maximum operating pressure
: 360 mbar
• Opening time
: <1 s
• Closing time
: < 1 s
• Protection rating
: IP65
• Class
: A
• Mechanical resistance
: Group 2
• Rp Threaded connections
: (DN 32 - DN 40 - DN 50) according to EN 10226
• Flanged connections to be coupled with PN 16 flanges : (DN 65 - DN 80 - DN 100 - DN 125 - DN 150) ISO 7005 / EN 1092-1
• NPT threaded or ANSI 150 flanged connections : on request
• Filter element
: 1 mm wire mesh on connections DN 32 - DN 40 - DN 50
filtering
50
µ
m on DN 65 - DN 80 - DN 100
filtering
10
µ
m on DN 125 - DN 150
• In compliance with
: Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
Directive EMC 2014/30/EU - Directive LVD 2014/35/EU
Directive RoHS II 2011/65/EU
* Only single-phase, the device does not work if powered with three-phase voltage.
** For cycles/hours with ON/OFF times different from those indicated, contact our technical office
2.1 MODEL IDENTIFICATION
GCA
= N.C. fast opening solenoid valve
8
= 230 V/50-60 Hz
6
= 110 V/50-60 Hz
4
= 24 V/50 Hz
3
= 24 Vdc
Possible connection diameters (DN):
32-40-50-65-80-100-125-150
/360
(if it is present) = P.max 360 mbar (indicated only for DN 32 - DN 40 - DN 50 diameters)
Eg:
GCA8100
= N.C. fast opening solenoid valve 230 V/50-60 Hz - DN100 - P. max 360 mbar
GCA450/360
= N.C. fast opening solenoid valve 24 V/50 Hz DN 50 - P. max 360 mbar
Содержание DN 100
Страница 23: ...23 IT EN fig 2 DN 32 DN 40 DN 50 ...
Страница 24: ...24 EN IT fig 3 DN 65 DN 80 DN 100 ...
Страница 25: ...25 IT EN fig 4 DN 125 DN 150 ...