background image

CellComSL

 

Series Universal Communicator Installation and Programming Guide 

Digital Monitoring Products

1

IntroductIon

CellComSL™ Series Universal Alarm Communicator

Description

The 

CellComSL™ Series Alarm Communicator provides a fully supervised alarm communication path for any 

burglary or residential fire control panel. The CellComSL Series can be connected to a control panel’s dialer 

output and used to capture Contact ID messages 

based on SIA DC-05-1999.09-DCS

. The CellComSLC has a 

built-in CDMA cellular module to send messages to DMP Model SCS-1R or SCS-VR Central Station Receivers. The 

communicator also provides four input zones and two open-collector outputs for connection to burglary or 

residential fire control panel outputs and zones. The CellComSL Series Communicator Zone 4 allows a connection 

to the bell output of an existing burglary control panel. The communicator operates in a variety of applications: 

CID Dialer Connection, Zones 1-4 Input Connections, or Zone 4 Bell Connection (See Applications on page 5). The 

CellComSL

CZ

™ Alarm Communicator includes an onboard Z-Wave controller for home automation applications.

What is Included

The 

CellComSL Series Universal Alarm Communicator includes the following:

•  PCB with Enclosure
•  3.7 Vdc 800 mAh Lithium Ion System Battery
•  Hardware Pack

System Components

1.1 

Terminals (J9)

Power Connection Terminals

Power is provided from the Nominal 12 Vdc auxiliary output of the burglary control panel.
OBSERVE POLARITY (See Figure 1 and Backlit Logo)
Using 18 - 22 AWG wire, connect the 

communicator

 

te12 to the positive terminal on the 

control panel 

auxiliary output.

Connect the communicator terminal G (Ground) to the negative terminal on the control panel auxiliary output.

Control Panel Standby Power

During a power outage, the CellComSL draws power from the control panel’s backup battery. The CellComSL must 

be included in the standby battery calculations for the control panel.

Zones 1-4

Terminals Z1 to Z3, G (Ground), Z4+ and Z4- provide four zones to connect to individual relay outputs on 

the control panel. Zone 4 (Z4+ and Z4-) can be connected to the control panel bell output. See Zone 4 Bell 

Connection.

Open-Collector Outputs

The two outputs, terminals O1 and O2 (see Figure 1), can be programmed to indicate the activity of the zones 

Figure 1: CellComSL Series Communicator

R

B

J8

S3

J9

RESET

LOAD

S1

S2

J19

J26

system components

Содержание CellCom SLC

Страница 1: ...CellComsl Series Universal Alarm Communica tor Installation and programming Guide...

Страница 2: ...nterference Problems This booklet is available from the U S Government Printing Office Washington D C 20402 Stock No 004 000 00345 4 2015 Digital Monitoring Products Inc Information furnished by DMP i...

Страница 3: ...on 5 3 3 Zone 4 Bell Connection 6 Remote Arming Disarming 7 4 1 DMP Virtual Keypad App Virtual Keypad Browser 7 Programming the CellComSL Series Universal Alarm Communicator 8 5 1 Before You Begin 8 P...

Страница 4: ...ress 13 7 26 Second IP Port 13 Messaging Setup 14 8 1 Messaging Setup 14 8 2 Enable Messaging 14 8 3 System Name 14 8 4 Destination 1 14 8 5 Destination 1 User Number 14 8 6 Destination 2 14 8 7 Desti...

Страница 5: ...ssignment 19 14 7 Style 19 14 8 Next Zone 19 14 9 Alarm Action 19 14 10 Disarmed Open 19 14 11 Message To Transmit 19 14 12 Output Number 20 14 13 Output Action 20 14 14 Swinger Bypass 20 14 15 Cross...

Страница 6: ...ion 28 Contact ID Recvd 28 Exiting the Diagnostics program 28 18 3 Using the 984 Command Function 28 CELL 28 18 4 Using the Walk Test 28 Walk Test 28 Trip Counter for Walk Test STD 28 Test End Warning...

Страница 7: ...controller for home automation applications What is Included The CellComSL Series Universal Alarm Communicator includes the following PCB with Enclosure 3 7 Vdc 800 mAh Lithium Ion System Battery Hard...

Страница 8: ...ix Plug in the internal lithium system battery in the BAT connector Use 9000BAT DMP recommends replacing the battery every 3 years under normal use Use the following steps to replace the system batter...

Страница 9: ...odel 400 USB Flash Module 1 Remove the yellow and green wires from keypad bus terminals 8 and 9 2 Place a jumper across the Reset J16 header 3 Place a jumper across the Load J18 header 4 Connect the U...

Страница 10: ...e mounted using the provided 6 screws in the four mounting holes See Figure 7 Mount the enclosure in a secure dry place to protect the communicator from damage due to tampering or the elements It is n...

Страница 11: ...panel turns on and trips the CellComSL zone a message will be sent to an SCS 1R or SCS VR receiver at Central Station You could use the zone name programming to describe which control panel zone indi...

Страница 12: ...one name to send to the Central Station Zones 5 and 6 cannot be preprogrammed in Zone Information Note CID Dialer Connection cannot be used when using Zone 4 Bell Connection Use 18 22 AWG for Power Su...

Страница 13: ...ation can be used to access the CellComSL Series Communicator A burglary control panel zone may be programmed as an arming zone and connected to a CellComSL output O1 or O2 See Figure 13 Program the o...

Страница 14: ...program of an existing communicator use the Initialization function described in Section 6 Initializing clears the communicator s memory of any old data and sets the highest numbered user number to us...

Страница 15: ...ntly in communicator memory by pressing the appropriate Select key under or on the display You then enter the new information using the keypad data entry digit keys When there are more than four re sp...

Страница 16: ...eypad Displays Current Programming Each programming option displayed at the keypad shows the currently selected option in the communicator memory These options are either shown as a number a blank or...

Страница 17: ...ramming NO leaves existing zone information intact YES sets all zones in the system to UNUSED 6 6 Clear Communication NO Leaves existing communication programming intact YES Clears communication to fa...

Страница 18: ...k ins before logging that the panel is missing For example if CELL checkin is 20 and Fail TIME is 30 the SCS 1R receiver only indicates a Panel Not Responding after 30 minutes The Fail TIME must be eq...

Страница 19: ...is NO 7 21 Opening Closing and User Reports YES enables Opening Closing Schedule and Code Changes and Bypass reports by user to be sent to this receiver Default is NO 7 22 Test Report YES enables the...

Страница 20: ...ming or disarming back to the CellComSL using MyAccess text messaging from the same cell phone The user number must have the authority to perform the commands Entering 0 zero disables this option Defa...

Страница 21: ...rals immediately System Options 11 1 System Options This section allows you to select system wide parameters used in the operation of the communicator system A description of each System Option follow...

Страница 22: ...r to send time changes it must be programmed to send time changes and must be receiving time change updates from the host automation computer at least every 24 hours Default is YES When time zone is p...

Страница 23: ...sarms Enter 0 zero to disable this output 12 5 Remote Arming Output When the system is armed or disarmed remotely from the Virtual Keypad App Virtual Keypad Browser MyAccess RemoteLink or from a sched...

Страница 24: ...COMMAND to enter a zone name Refer to the Enter Alpha Characters section 14 3 Zone Name Press any Select key and enter up to 16 characters for the zone name A name must be given to each zone in the sy...

Страница 25: ...state a trouble is reported If opened from a shorted armed state an alarm is reported and the zone is disabled until you disarm the area from either the Virtual Keypad App MyAccess Virtual Keypad Brow...

Страница 26: ...ction the zone remains normal for one hour and the Reset Swinger Bypass is YES If the zone trips fewer than the specified times within one hour of the first trip the bypass trip counter returns to 0 z...

Страница 27: ...ing the Lockout Code You can change this code at any time to any combination of numbers from 1 to 5 digits long 1 to 65535 Do not use leading zeros for the lockout code 1 Press any Select key The disp...

Страница 28: ...ny Select key The keypad displays ADD LIST REMOVE Select ADD PROCESSING may briefly display When PRESS BUTTON ON DEVICE TO ADD displays press the program button on the Z Wave device See the Z Wave dev...

Страница 29: ...4 Select REMOVE PROCESSING may briefly display When PRESS BUTTON ON DEVICE TO REMOVE displays press the program button on the Z Wave device the device name and REMOVED is displayed to indicate the Z W...

Страница 30: ...enter the new level 1 10 and Press COMMAND 4 The Favorite name and the next Z Wave device stored in the system displays Doors 1 Press any Select key at SETTING and LOCK UNLOCK for Doors and OPEN CLOS...

Страница 31: ...te REMOVE DEVICE FROM FAV NO YES displays When YES is selected the device is removed from the Favorite 17 12 Transfer Controller XFER This option allows the transfer of all existing Z Wave devices tha...

Страница 32: ...nu 2 Press COMMAND until ZWAVE SETUP displays 3 Press any Select key The keypad displays ADD LIST REMOVE 4 Press COMMAND again to display FAV XFER OPT 5 Select OPT the keypad displays OPTIMIZE while t...

Страница 33: ...icator When the communicator is roaming or not in contact with a Verizon owned tower ROAM will be displayed on the top line of the keypad along with the signal strength If the cellular communicator is...

Страница 34: ...a walk test feature that allows a single technician to test all the zones on the system Conduct the Walk Test within 30 minutes of resetting the communicator The Walk Test automatically ends if no zo...

Страница 35: ...ry controller The XFER feature allows an existing 3rd party network to be transferred into the CellComSLCZ The CellComSLCZ can support Z Wave products from different vendors and product categories It...

Страница 36: ...s Enter 00 to exit 6 Define Output 17 actions Enter or displays Press and Field displays Enter 80 and program the following a Program Output 17 to turn on when armed Stay Output Funct Enter 01 press t...

Страница 37: ...18 VISTA 20P ONLY Ademco Vista 20P GND OUT2 Z1 1K Remote Arming out to Keyswitch Arming Zone Armed Output of Vista to CellComSL Arming Zone R B J8 S3 J9 RESET LOAD S1 S2 J19 J26 AC 1 2 3 4 5 6 7 8 10...

Страница 38: ...ellComSL 18 11 Programming for Ademco Vista 20P ECP to CellComSL The following steps describe how to configure Ademco Honeywell control panels to accept arm and disarm commands from a CellComSL using...

Страница 39: ...CellComSL Series Universal Communicator Installation and Programming Guide Digital Monitoring Products 33 Appendix...

Страница 40: ...Housing 5 5 W x 3 75 L x 1 H Color CellComSLC White CellComSLCF Red Ordering Information CellComSLC CDMA Communicator CellComSLCZ CDMA Communicator with Z Wave Certifications California State Fire Mar...

Отзывы: