Digital Monitoring Products, Inc. | 734B Installation and Programming Guide
11
Connect a Magstripe Reader
The 734B is compatible with ABA Track 2 Clock‑and‑Data magnetic stripe readers.
The module provides direct 12/24 VDC, 200 mA output to the reader on the RED
terminal connection. Figure 9 shows a reader with wire colors RED, WHT, GRN, and
BLK connecting to terminals 1, 2, 3, and 4.
The green wire is Data and the white wire is Clock. The red wire connects 12/24 VDC,
200 mA maximum power and the black wire is ground.
The wire colors may be different depending on the reader being installed. Refer to
the literature provided with the reader for wire coding, wire distance, cable type
(such as shielded), and other specifications.
Magstripe Reader LED Operation
To provide visual indication of a valid card read, the magstripe reader can be wired
to illuminate the green LED for the duration of the door strike.
Connect the orange or brown wire to LC terminal 5 to have the green LED stay on
for the duration of the relay activation.
Magstripe Reader Annunciation
Connect the yellow wire to RA terminal 6 to have the remote annunciator turn on
anytime the panel instructs the 734B onboard piezo to turn on.