Specifications
Dimensions 3-3/8” L x 7/8” W x 1/2” H
Certifications
FCC Part 15
CellCom-LTE-V, XTLplus, XTLC
1. Connect the USB flash drive containing the RU file to the Model
400 and connect the assembly to the panels Programming PROG
header. The LED on the Model 400 will flash then display steady
green.
2. Press and hold the Load switch on the panel. While holding the
Load switch, press and release the Reset switch, then release the
Load switch.
3. Press and release the load button on the Model 400 to initiate the
firmware update. The LED on the Model 400 will flash slowly. If
the LED displays fast flashes it means the firmware update was
unsuccessful. The update will take approximately 4.5 minutes
and when complete the LED on the Model 400 will display steady
green.
4. Press and release the Reset switch then remove the USB flash
drive and Model 400 assembly.
In the event the Model 400 USB Flash Module is inadvertently removed
from the panel before the update finishes, repeat steps 1 through 4.
Verify the Firmware
1. At a keypad, enter the Diagnostic code
2313
(DIAG), and press
CMD
.
2. Press
CMD
until
Panel Settings
displays. Press any select key.
3. Press
CMD
until
Firmware Version
displays. Verify the panel firmware version is correct.
4. Press
CMD
until
Stop
displays. Press any select key to exit the Diagnostic menu.