Transmitter Supervision Time
For listed installations, program the transmitter supervision time in panel zone programming as listed in the following
table. Refer to the panel programming guide for complete wireless programming information.
UL Listing
Listed Accessories
Supervision Time
UL 268 Smoke-Automatic Fire Detectors
1164 Synchronized Smoke Detector
1164NS Smoke Detector with No Sounder
1168 Smoke/CO/Low Temp Detector
3
UL 365 Police Station Connected Burglar Accessory
1103 Universal Transmitter
60
UL 521 Heat Detectors for Fire Protective Signaling
Systems
1183-135F, 1183-135R Heat Detector
3
UL 609 Local Burglar Alarm Units and System Accessory
1103 Universal Transmitter
60
UL 634 Connections and Switches for use with Burglar
Alarm Systems Accessory
1101, 1102, 1103, 1106 Universal Transmitters
60
UL 636 Holdup Alarm Units and Systems Accessory
1142 Two-Button Holdup Transmitter
60
UL 639 Intrusion Detection Units Accessory
1127W, 1127C PIR Motion Detectors
60
UL 864 Fire Protective Signaling Systems
1103 Universal Transmitter
3
UL 985 Household Fire Warning System Accessory
1135 Siren
9060, 9063, 9862 Wireless Keypads
240
UL 1023 Household Burglary System Units Accessory
1101, 1102, 1103, 1106 Universal Transmitters
1127W, 1127C PIR Motion Detectors
1135 Siren
1142 Two-Button Holdup Transmitter
9060, 9063, 9862 Wireless Keypads
60
UL 1076 Proprietary Burglar Alarm Units Accessory
1103 Universal Transmitter
9862 Wireless Graphic Touchscreen Keypad
60
UL 1610 Central Station Burglar Alarm Units Accessory
1103 Universal Transmitter
1135 Siren
9060, 9063, 9862 Wireless Keypads
60
UL 2075 Gas and Vapor Detectors and Sensors
1184 Wireless Carbon Monoxide Detector
1168 Wireless Smoke/CO/Low Temp Detector
240
1100X LED Operation
The six labeled LEDs on the 1100X PCB display wireless receiver operation
and activity. See Table 2 for LED locations and Table 1 for LED indications.
House Code Explained
The house code identifies the panel, receiver, and transmitters to each
other. The 1100X automatically sends the specified house code to wireless
transmitters when transmitter serial numbers are programmed into the
panel. The 1100X only listens for transmissions using the specified house
code or the programmed transmitters’ serial numbers.
Table 3: Wireless Transmitter Supervision Times
Note:
The 1100R Wireless Repeater and 1100T Wireless Translator follow the Receiver Supervision times for Listed
Accessories.
LED
INDICATIONS
RF RX
Flashing yellow indicates
data is being received from a
transmitter.
RF TX
Flashing green indicates data is
being sent to a transmitter.
PANEL RX Flashing yellow indicates data
is being received from a panel.
PANEL TX Flashing green indicates data is
being sent to the panel.
STATUS
Solid red indicates memory is
being uploaded. Turns off when
complete.
PWR
Solid green indicates there is
power to the wireless receiver.
Table 2: LED Indications
Note:
The status LED light will remian solid red when wireless
jamming is enabled or if there is a large amount of RF activity in
the vicinity of the receiver.