Transmitter Supervision Time

For listed installations, program the transmitter supervision time in panel zone programming 

as listed in the following table. Refer to the panel programming guide for complete wireless 

programming information.

UL STANDARD

LISTED ACCESSORIES

SUPERVISION 

TIME

UL 268 Smoke‑Automatic Fire 

Detectors

•  1100R Repeater
•  1164 Wireless Synchronized Smoke 

Detector

3

UL 365 Police Station 

Connected Burglar Accessory

•  1100R Repeater
•  1103 Universal Transmitter

60

UL 521 Heat Detectors for Fire 

Protective Signaling Systems

•  1100R Repeater
•  1183‑135F, 1183‑135R

3

UL 609 Local Burglar Alarm 

Units and System Accessory

•  1100R Repeater
•  1103 Universal Transmitter

60

UL 634 Connections and 

Switches for use with Burglar 

Alarm Systems Accessory

•  1100R Repeater
•  1101, 1102, 1103, 1106 Universal 

Transmitters

60

UL 636 Holdup Alarm Units and 

Systems Accessory

•  1142 Two‑Button Holdup Transmitter

60

UL 639 Intrusion Detection 

Units Accessory

•  1100R Repeater
•  1127W, 1127C PIR Motion Detectors

60

UL 985 Household Fire Warning 

System Accessory

•  1100R Repeater
•  1135 Wireless Sounder
•  9060, 9063, 9862 Wireless Keypads

240

UL 1023 Household Burglary 

System Units Accessory

•  1100R Repeater
•  1101, 1102, 1103, 1106 Universal 

Transmitters

•  1127W, 1127C PIR Motion Detectors
•  1135 Wireless Sounder
•  1142 Two‑Button Holdup Transmitter
•  9060, 9063, 9862 Wireless Keypads

60

UL 1076 Proprietary Burglar 

Alarm Units Accessory

•  1100R Repeater
•  1103 Universal Transmitter

60

UL 1610 Central Station Burglar 

Alarm Units Accessory

•  1100R Repeater
•  1103 Universal Transmitter
•  1135 Wireless Sounder
•  9060, 9063, 9862 Wireless Keypads

60

Table 2: Wireless Transmitter Supervision TImes