FT590 SERIES RACK TESTER MANUAL; 11266PA 

 

 

Operation 

1.

 

Disconnect the rack cord from any trailers. Verify the rack monitor is non-permissive. 

2.

 

Connect the rack cord to the FT590 unit. 

3.

 

Verify the rack monitor becomes permissive. This will typically be indicated by a green 
light. 

a.

 

If the rack monitor does not become permissive, this indicates the issue is likely 
related to the terminal side equipment.  
 
Make note of the lights shown on the front of the rack monitor as they may be 
indicative of the failure point. 
 
Refer to the rack monitor and junction box manuals for troubleshooting these 
items.  

4.

 

Optional: Using a dark colored cup filled with fuel oil or diesel, submerge the end of the 
probe on the FT590 

approximately 1” into the liquid

. Verify the rack monitor returns to 

non-permissive. 

5.

 

If the rack monitor performed as expected in steps 3 and 4, the rack monitor is working 
correctly, and the failure is on the trailer overfill system. 

Maintenance 

The FT590 has few parts that will require regular maintenance. The socket may develop 
oxidation or accumulate debris over time which may lead to poor connection to a rack cord. To 
minimize oxidation and debris buildup ensure the FT590 is stored in the orange case it was 
shipped in.  

Over time the socket connection may still become dirty or oxidized leading to intermittent or 
connections to the rack cord. If this occurs the socket face may need cleaning. Dixon sells a 
cleaning brush designed specifically to clean oxidation and debris from trailer sockets. Contact 
your local Dixon sales representative for information about purchasing the FT406 socket 
cleaner. 

 

 

Содержание FT590 Series

Страница 1: ...FT590 SERIES RACK TESTER MANUAL 11266PA REV A 2020 10 15 877 582 3569 1 Maintenance Operating Instructions For Dixon Bayco FT590 Series Products dixonvalve com ...

Страница 2: ...rs for loading Once connected the FT590 unit will induce electrical signals that should cause the rack monitor to become permissive Verifying the rack monitor s ability to reach permissive state will drastically reduce troubleshooting time by narrowing the failure to either rack side or trailer side WARNING THE FT590 RACK TESTER CAN CREATE UNSAFE LOADING CONDITIONS IF USED IMPROPERLY ENSURE IT IS ...

Страница 3: ...T590OGT API 1004 OPTIC 6 PIN 3 J SLOTS FT590TG FT590TGT API 1004 THERMISTOR 10 PIN 4 J SLOTS PHYSICAL OVERFILL SENSORS 1 OVERFILL SENSOR TYPE FT590OG FT590OGT 5 WIRE OPTIC FT590TG FT590TGT 2 WIRE OPTIC SIMULATED SENSORS AS SHOWN ON RACK FT590OG FT590OGT 1 FT590TG FT590TGT 8 DIMENSIONS CASE 15 3 x 12 1 x 6 7 WEIGHT 10 6 lbs SIMULATED GROUNDING DEVICE GROUND BOLT OR GROUND DEVICE COMPATABILITY WITH ...

Страница 4: ...obe on the FT590 approximately 1 into the liquid Verify the rack monitor returns to non permissive 5 If the rack monitor performed as expected in steps 3 and 4 the rack monitor is working correctly and the failure is on the trailer overfill system Maintenance The FT590 has few parts that will require regular maintenance The socket may develop oxidation or accumulate debris over time which may lead...

Страница 5: ...ad The issue is likely in the wiring from the OBM to the trailer socket or the socket itself The rack uses Trailer Identification Modules TIM How can the FT590 rack tester be used to verify TIM reading is working An FT590 model including a TIM will be required FT590OGT and FT590TGT both include a TIM module When the rack tester is initially connected it will be recognized as an un registered trail...

Страница 6: ... 00 DIXON 34966 Fax 01 81 8354 8197 E mail contactenos dixonvalve com mx Canada Dixon Group Canada Limited Innisfil Barrie Ontario Phone 705 436 1125 Fax 705 436 6251 Toll Free 877 963 4966 E mail isales dixongroupcanada com USA Dixon Bayco USA Chestertown Maryland Phone 410 778 2000 Fax 410 778 4702 Toll Free 800 355 1991 E mail dixonbayco dixonvalve com Asia Pacific Dixon Asia Pacific Pty Ltd Wi...

Отзывы: