background image

Operating Instructions XWA11V 

dIXEL

V8.8-KIT 

1

Weiss Instruments,

LLC

. 905 Waverly Ave. Holtsville

 

, NY 11742  631-207-1200 www.weissinstruments.com 

XWA11V-KIT 

Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring 

1. GENERAL DESCRIPTION

Model 

XWA11V-KIT, 100x64 mm 

format, is a microprocessor based light and alarm management controller, suitable for

temperature monitoring in a walk-in cooler or freezer. It is provided with two (2) relay outputs that supply 120 Volts to
control lights and signal an alarm. It is also provided with one (1) NTC probe input for temperature measurement. To
ease installation on existing walk-in coolers the unit has been installed in a VBOX pre-wired with an outboard buzzer,
magnetic door switch (MDS), a 9V battery harness, a pigtail harness for the unit power and the light. There is also a five
pin port that allows the user to program the parameter list with a 

“Hot Key”.

Note: The default settings are listed in the back of this manual. They are set for Coolers (Medium
Temp). For Freezers (Low Temp) you MUST Change the ALL and ALU settings. See Section 4.0

We have responded to many requests to make a change in the way the light key operates. It now
overrides the Digital Input to allow a manual OFF prior to the “Lht” being exhausted.

2. GENERAL WARNINGS

2.1 

PLEASE READ BEFORE USING THIS PRODUCT 

This manual is part of the product and should be kept close to the instrument for easy and quick
reference.

The instrument shall not be used for purposes different from those described hereunder. It cannot be used
as a safety device.

Check the application limits before proceeding.

2.2 

SAFETY PRECAUTIONS **READ ME FIRST!** 

Check if the supply voltage is correct before connecting the instrument.

Do not expose the back of the instrument to water or moisture

: use the controller only within the operating limits

avoiding sudden temperature changes with high atmospheric humidity to prevent the formation of condensation.

Be sure to seal any J-Box with RTV sealant to prevent cold and moisture intrusion.

Warning: disconnect all electrical connections before performing any maintenance operation.

Fit the probe where it is not damaged by the end-user. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor (see address) with a detailed
description of the fault.

Consider the maximum current that can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from each other,
without crossing or intertwining or you may get bad temp readings.

 

(UL SPEC 0873)

The box supplied is not suitable for exterior use. If a water tight box is required contact the distributor.

Содержание XWA11V

Страница 1: ...usted 2 GENERAL WARNINGS 2 1 PLEASE READ BEFORE USING THIS PRODUCT This manual is part of the product and should be kept close to the instrument for easy and quick reference The instrument shall not b...

Страница 2: ...rameter LOW Press to see the LOW Temp ALARM ALL parameter In Programming Mode press to browse parameter codes Press to increase the displayed value Press to mute the buzzer relay when an ALARM is happ...

Страница 3: ...e UP or DOWN to change its value Press SET to store the new value and move to the following parameter To exit Press SET UP or wait 15 seconds without pressing a key NOTE the set value is stored even w...

Страница 4: ...all the following conditions happen the LHt timer is exhausted the door is closed i1F dor DOOR SWITCH PRESENT the presence sensor is de activated i2F LHt OCCUPANCY SENSOR PRESENT Light button regulat...

Страница 5: ...ad 2 When the controller is ON insert the Hot key and push UP key the uPL message appears followed a by flashing End 3 Push SET key and the End will stop flashing 4 Turn OFF the instrument and remove...

Страница 6: ...ing self extinguishing ABS Case face 100x64 mm 3 94 x2 52 Depth 45 5mm 1 79 Mounting J box or wall mount in suitable enclosure Frontal protection IP65 CONTROL ONLY the box is not water proof Connectio...

Страница 7: ...Waverly Ave Holtsville NY 11742 631 207 1200 www weissinstruments com 13 AGENCY APPROVALS LISTINGS AND SUPPORT INFORMATION Weiss Instruments LLC 905 Waverly Ave Holtsville NY 11742 Phone 631 207 1200...

Страница 8: ...on of the temperature alarm condition at the end of defrost and the alarm signaling dot Delay of Temp alarm after closing the door 0 255 min Time delay to signal the temperature alarm condition after...

Страница 9: ...ity 1 2 CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact i1L Door switch to turn light ON 1 2 y n To turn the light ON automatically wh...

Отзывы: