Label  Name 

  Range 

Default  Level

OE 

Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 Pr2 

P3P 

Third probe presence (1st cond. 

probe) 

n=not present; Y=pres. 

n Pr2 

O3 

Third probe calibration 

-12

÷

12°C /-120

÷

120°F 

0 Pr2 

P4P 

Fourth probe presence (2nd  cond. 

probe) 

n=not present; Y=pres. 

n Pr2 

O4 

Fourth probe calibration 

-12

÷

12°C /-120

÷

120°F 

0 Pr2 

OdS 

Outputs activation delay at start up 

0÷255 min. 

0 Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

1 Pr1 

Ac1 

Second compressor delay 

0÷255s 

5 Pr2 

rtr 

P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 Pr2 

CCt 

Compressor ON time during fast 

freezing 

0 ÷ 23h 50 min. 

0.0 Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) 

-5 Pr2 

COn 

Compressor ON time with faulty probe 

0÷255 min. 

15 Pr2 

COF 

Compressor OFF time with faulty 

probe 

0÷255 min. 

30 Pr2 

 DISPLAY 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C 

Pr2 

rES 

Resolution (integer/decimal point) 

in ÷ de 

dE 

Pr1 

rEd 

Remote display  

P1 ÷ 1r2 

P1 

Pr2 

dLy 

Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

0 Pr2 

dtr 

P1-P2 percentage for disply 

 1 ÷ 99 

50 Pr2 

 DEFROST 

 

 

tdF 

Defrost type 

EL,  in  

EL Pr1 

dFP 

Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 Pr2 

dtE 

Defrost termination temperature  

-50,0÷110°C / -58÷230°F 

8.0 

Pr1 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF 

(Maximum) length for 1° defrost 

0÷255 min. 

30 

Pr1 

dSd 

Start defrost delay 

0÷99min 

0 Pr2 

dFd 

Displaying during defrost 

rt, it, SEt, dEF, dEG 

it Pr2 

dAd 

MAX display delay after defrost 

0÷255 min. 

30 Pr2 

Fdt 

Draining time 

0÷60 min. 

0 Pr2 

dPO 

First defrost after start up 

n ÷ y 

n Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

0.0 Pr2 

 AUXILIARY 

THERMOSTAT

 

 

 

 

ACH 

Kind of action for auxiliary relay  

CL; Ht 

cL Pr2 

SAA 

Set Point for auxiliary relay 

-50,0÷110°C /  -58÷230°F 

0,0 Pr2 

SHy 

Differential for auxiliary relay 

0,1÷25,5 °C / 1÷45°F 

2,0 Pr2 

ArP 

Probe selection for auxiliary relay 

nP / P1 / P2 / P3 

nP Pr2 

Sdd 

Aux.output working during defrost 

n, y 

n Pr2 

 ALARMS 

 

 

ALP 

Probe setting for temperature alarm 

P1÷P4 

P1 Pr2 

ALC 

Temperature alarms configuration 

rE÷Ab 

rE Pr2 

ALU 

MAXIMUM temperature alarm 

-50,0÷110°C / -58÷230°F 

10,0 Pr1 

ALL 

minimum temperature alarm 

-50,0÷110°C / -58÷230°F 

10,0 Pr1 

AFH 

Temperature alarm and fan differential 

0,1÷25,5 °C / 1÷45°F 

2,0 Pr2 

ALd 

Temperature alarm delay 

0÷255 min. 

15 Pr2 

dAO 

Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 Pr2 

AP2 

Probe for temperat. alarm of 

condenser 

nP; P1; P2; P3; P4 

P4 Pr2 

AL2 

Condenser for low temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

-40 Pr2 

AU2 

Condenser for high temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

110 Pr2 

AH2 

Differ. for condenser temp. alar. 

recovery 

[0,1°C ÷ 25,5°C]  [1°F ÷ 45°F] 

5 Pr2 

Ad2 

Condenser temperature alarm delay  

 0 ÷ 254 (min.) , 255=nU 

15 Pr2 

dA2 

Delay of cond. temper. alarm at start 

up 

0.0 ÷ 23h  50’ 

1,3 Pr2 

bLL 

Compr. off for condenser low 

temperature alarm 

n(0) - Y(1) 

n Pr2 

AC2 

Compr. off for condenser high 

temperature alarm 

n(0) - Y(1) 

n Pr2 

 AUXILIARY 

OUTPUT

 

 

 

 

tbA 

Alarm relay disabling 

n=no; y=yes 

y Pr2 

oA3 

Fourth relay configuration 

ALr = alarm; dEF = do not select it; 

Lig =Light; AUS =AUX; onF=always 

on; Fan= do not select it; db = do 

not select it; dF2 = do not select it 

Lig Pr2 

AoP 

Alarm relay  polarity  (oA3=ALr) 

oP; cL 

cL Pr2 

 DIGITAL 

INPUT 

 

 

 

i1P 

Digital input polarity 

oP=opening;CL=closing 

cL Pr1 

i1F 

Digital input configuration 

EAL, bAL, PAL, dor; dEF; Htr, AUS 

dor Pr1 

did 

Digital input alarm delay 

0÷255min 

15 Pr1 

Nps 

Number of activation of pressure 

switch 

0 ÷15  

15 Pr2 

odc 

Compress and fan status when open 

door 

no; Fan; CPr; F_C 

 

F-c Pr2 

rrd 

Regulation restart with door open 

alarm 

n – Y 

y Pr2 

HES 

Differential for Energy Saving 

 -30°C÷30°C; -54°F÷54°F 

0 Pr2 

 OTHER 

 

 

PbC 

Kind of probe 

Ptc; ntc 

1 Pr2 

Adr 

Serrial address 

1÷247 

ntc Pr1 

onF 

on/off key enabling 

nu, oFF; ES 

oFF Pr2 

dP1 

Room probe display 

-- 

- Pr1 

dP2 

Evaporator probe display 

-- 

- Pr1 

dP3 

Third probe display 

-- 

- Pr1 

Label  Name 

  Range 

Default  Level

dP4 

Fourth probe display 

-- 

- Pr1 

rSE 

Current set point 

-  

  

Pr1 

rEL 

Software release 

- - - 

1,1 Pr2 

Ptb 

Map code 

- - - 

- Pr2 

 

 
 

 
 

 

 
 

 

 
 

 

 

 