HOW TO USE THE HOT KEY

11.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)

1.

 

Program one controller with the front keypad.

2.

 

When the controller is ON, insert the “Hot key” and push 

9

9

 key; the  "uPL" message appears

followed a by flashing “End”

3.

 

Push “SET” key and the End will stop flashing.

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again.

NOTE: the “Err” message is displayed for failed programming. In this case push again 

9

9

 key if you

want to restart the upload again or remove the “Hot key” to abort the operation.

11.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)

1.

 

Turn OFF the instrument.

2.

 

Insert  a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.

3.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the
doL” message is blinking followed a by flashing “End”.

4.

 

After 10 seconds the instrument will restart working with the new parameters.

5.

 

Remove the “Hot Key”..

NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if
you want to restart the download again or remove the “Hot key” to abort the operation.

12.

 

DIGITAL INPUT

The controllers have 1  free contact digital input. It is programmable in 5 different configurations by the
i1F” parameter.

12.1

 

INVERT THE KIND OF ACTION: HEATING-COOLING (I1F = C-H)

This function allows to invert the regulation of the controller for both the outputs: from direct to inverse
and viceversa.

12.2

 

REMOTE ON/OFF (I1F = OFF)

This function allows to switch ON and OFF the instrument.

12.3

 

GENERIC ALARM (I1F = EAL)

As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL
alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-
activated.

12.4

 

SERIOUS ALARM MODE (I1F = BAL)

When the digital input is activated, the unit will wait for “did” delay before signalling the “bAL” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.

12.5

 

ENERGY SAVING (I1F = HES)

The Energy Saving function allows to change the set point1 value as the result of the SET1+ HES
(parameter) sum. This function is enabled until the digital input is activated.

13.

 

ALARM SIGNALS

Message Cause

Outputs

“PFo”

Probe broken or absence

Alarm output ON; Output 1 and 2 according
parameters “So1” and “So2” respectively.

“PFc”

Probe short circuited

Alarm output ON; Output 1 and 2 according
parameters “So1” and “So2” respectively.

“HA”

Maximum temperature alarm

Alarm output ON; Other outputs unchanged.

“LA”

Minimum temperature alarm

Alarm output ON; Other outputs unchanged.

“EAL”

External alarm

Output unchanged.

“bAL”

Serious external alarm

Output OFF.

13.1

 

ALARM RELAY STATUS

Status of the instrument

XT121C

XT121D

AS = CL

AS= oP

AS = CL

AS= oP

Instrument off

5-6 closed

5-6 closed

23-24 closed

23-24 closed

Normal operating

5-6 closed

5-6 open

23-24 closed

23-24 open

Alarm present

5-6 open

5-6 closed

23-24 open

23-24 closed

13.2

 

SILENCING BUZZER / ALARM RELAY OUTPUT

Once the alarm signal is detected the buzzer, if present, can be disabled by pressing any key.
XT121C/XT121D: the alarm relay status depends on the tbA parameter: with tbA=yES the relay is
disabled by pressing any key, with tbA=no the alarm relay remains enabled as long as the alarm lasts.
The display signal remains as long as the alarm condition remains.

13.3

 

ALARM RECOVERY

Probe alarms “PFo”, “PFc” start few seconds after the fault in the probe; they automatically stop few
seconds after the probe restarts normal operation. Check connections before replacing the probe.
Max. and min. alarms “HA” and “LA” automatically stop as soon as the variable returns to normal values.
Alarms “bAL” and “EAL” recover as soon as the digital input is disabled.

14.

 

TECHNICAL DATA

Housing: self extinguishing ABS.
Case: XT120C, XT121C frontal 32x74 mm; depth 60mm;

XT120D, XT121D: 4 DIN modules 70x85 mm; depth 61mm.

Mounting:  XT120C, XT121C panel mounting in a 71x29 mm panel cut-out.

XT120D, XT121D: DIN RAIL

Protection: IP20.
Frontal protection: XT110C, XT111C IP65 with frontal gasket RG-C (optional).
Frontal protection: IP65 with frontal gasket RG-C (optional).
Connections: Screw terminal block 

 2,5 mm

2

 heat-resistant wiring.

Power supply: 12Vac/dc, ±10% or: 24Vac/dc 

±

 10%

or 230Vac 

±

 10%, 50/60Hz or 110Vac, 

±

 10%, 50/60Hz

Power absorption: 3VA max.
Display: 3 ½ digits, red LED
Inputs: according to the order: NTC/PTC or NTC/PTC /Pt100 /Thermocouple J, K, S or 4÷20mA/ 0÷1V

/ 0÷10V

Relay outputs:

Output1: relay 8(3)A, 250Vac
Output2: relay 8(3)A, 250Vac
Alarm: (XT121C/XT121D), 8(3)A, 250Vac

Other output: buzzer (optional)
Kind of action: 1B.; Pollution grade: normal;
Software class: A.; Data storing: on the non-volatile memory (EEPROM).
Operating temperature: 0÷60 °C (32÷140°F); Storage temperature: -30÷85 °C  (-22÷185°F).
Relative humidity: 20

÷

85% (no condensing)

Measuring and regulation range: according to the probe
Controller Accuracy a 25°C: better than 

±

0,5% of full scale

15.

 

CONNECTIONS

15.1

 

XT120C – 12V AC/DC OR 24V AC/DC

     

 

   

Hot-KEY

8(3)A250V

8(3)A250V

Line

Input: 4÷ 20mA 

0÷ 1V  / 0÷ 10V 

   

PTC   /  N TC

Probe: Pt100= 7 – 9 (8); Thermocouple J, K, S = 7(+); 9(-)
24Vac/cd supply: 11-12

15.2

 

XT120C – 230V AC OR 115V AC

       

   

Hot-KEY

8(3)A250V

8(3)A250V

Line

Input 4÷ 20m A

0÷ 1V  / 0÷ 10V 

   

PTC   /  N TC

Pt100=9 –11 (10); Thermocouple J, K, S = 9(+) - 11(-)
115Vac supply: 7-8

15.3

 

XT121C – 12VAC/DC OR 24VAC/DC

     

 

   

Hot-KEY

8(3)A250V

8(3)A250V

8(3)A250V

Line

LOAD 1 LOAD 2

ALARM

Input: 4÷ 20mA 

0÷ 1V  / 0÷ 10V 

   

PTC   /  N TC

 

Probe: Pt100= 7 – 9 (8); Thermocouple J, K, S = 7(+); 9(-)
24Vac/cd supply: 11-12

Содержание XT120C

Страница 1: ...r inverse S1C in action output 2 at S2C dir direct or inverse S2C in action E I with OUC ind S1C dir cooling S2C dir cooling 4 2 2 DEPENDENT OUTPUTS OUC DIP With dependent control stages ouC diP SET2 is related to SET1 therefore SET2 is SET1 SET2 output 1 with direct or inverse action according to the S1C parameter output 2 with direct or inverse action according to the S2C E I with ouC diP depend...

Страница 2: ...Y LCI Start of scale only with current or voltage input with rES in dE cE 99 00 199 00 with rES irE 999 1999 Adjustment of read out corresponding to 4mA or 0V input signal UCI End of scale only with current or voltage input with rES in dE cE 99 00 199 00 with rES irE 999 1999 Adjustment of read out corresponding to 20mA or 1V or 10V input signal oPb Probe calibration 999 999 allows to adjust possi...

Страница 3: ...vely HA Maximum temperature alarm Alarm output ON Other outputs unchanged LA Minimum temperature alarm Alarm output ON Other outputs unchanged EAL External alarm Output unchanged bAL Serious external alarm Output OFF 13 1 ALARM RELAY STATUS Status of the instrument XT121C XT121D AS CL AS oP AS CL AS oP Instrument off 5 6 closed 5 6 closed 23 24 closed 23 24 closed Normal operating 5 6 closed 5 6 o...

Страница 4: ... Pr2 ALU Maximum alarm ALC rE ALC Ab 0 Full Sc Set1 ALL Full Scale 10 0 20 Pr2 ALH Alarm recovery differential 0 Full scale 2 0 4 Pr2 ALd Alarm delay 0 999 min 15 Pr2 dAO Alarm delay at start up 0 23h 50min 1 3 Pr2 So1 Out1 status with faulty pr oFF open on closed oFF Pr2 So2 Out2 status with faulty pr oFF open on closed oFF Pr2 tbA1 Alarm relay disabling no yES yES Pr2 AS1 Alarm relay polarity CL...

Отзывы: