dixell XR40C Скачать руководство пользователя страница 2

Dixell

 

Installing and Operating Instructions 

1592007230

 

 

1592007230 XR40C GB r1.0 15.05.2003 

XR40C 

2/4 

2.  The value of the set point will be displayed and the 

 LED starts blinking; 

3.  To change the Set value push the 

or 

n

 arrows within 10s. 

4.  To memorise the new set point value push the 

SET

 key again or wait 10s. 

6.3  HOW TO START A MANUAL DEFROST 

 

Push the 

DEF 

key for more than 2 seconds and a manual 

defrost will start. 

6.4  HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows: 

 

1. Enter the Programming mode by pressing the Set and 

DOWN key for 3s (

 and 

 start blinking). 

2.  Select the required parameter. 
3. Press the “

SET

” key to display its value (now only the 

 

LED is blinking). 

4. Use “

UP

” or “

DOWN

” to change its value. 

5. Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the 

time-out to expire. 

6.5  THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.5.1  HOW TO ENTER THE HIDDEN MENU 

 

1.  Enter the Programming mode by pressing the Set + 

n

 

key for 3s (LED 1 and 

 start blinking). 

2.  When a parameter is displayed keep pressed the Set+

n

 

for more than 7s. The Pr2 label will be displayed 
immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU. 

3.  Select the required parameter. 
4.  Press the “

SET

” key to display its value (Now only the 

 LED is blinking). 

5. Use 

or 

n

 to change its value. 

6. Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the 

time-out to expire. 
 

6.5.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE 
FIRST LEVEL” (user level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is 
on. 

6.6  HOW TO LOCK THE KEYBOARD 

 

1. 

 

Keep pressed for more than 3 s the 

and 

n

 keys. 

2. 

 

The “

POF

” message will be displayed and the keyboard will be locked. At this 

point it will be possible only to see the set point or the MAX o Min temperature 
stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.7  TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

 keys, till the 

“Pon” 

message will be displayed. 

6.8  THE CONTINUOUS CYCLE 

 

When defrost is not in progress, it can be activated by 
holding the “

o

” key pressed for about 3 seconds. 

The compressor operates in continuous mode for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the 
same activation key “

o

” for 3 seconds. 

7. PARAMETERS 

NOTE: the parameters preceded by  dots are in the Hidden Menu. 

 

REGULATION 

Hy Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. 

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT 
is when the temperature reaches the set point. 

 

LS  Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum 
acceptable value for the set point. 

 

US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum 
acceptable value for set point. 

Ot  Thermostat probe calibration

: (-12.0÷12.0°C; 

-120÷120°F) allows to adjust possible offset of the thermostat probe. 

P2P Evaporator  probe presence: n

= not present: the defrost stops by time; 

y=

 

present: the defrost stops by temperature. 

 

OE Evaporator probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to 
adjust possible offset of the evaporator probe. 

 

OdS   Outputs  activation delay at start up: (0÷255min) This function is 
enabled at the initial start up of the instrument and inhibits any output 
activation for the period of time set in the parameter.  

AC  Anti-short cycle delay

: (0÷50 min) minimum interval between the 

compressor stop and the following restart. 

 

CCt Compressor ON time during continuous  cycle: (0.0÷24.0h; res. 
10min) Allows to set the length of the continuous cycle: compressor stays on 
without interruption for the CCt time. Can be used, for instance, when the 
room is filled with new products. 

 

COn Compressor ON time with faulty probe: (0÷255 min) time during 
which the compressor is active in case of faulty thermostat probe. With 
COn=0 compressor is always OFF. 

 

COF Compressor OFF time with faulty probe: (0÷255 min) time during 
which the compressor is OFF in case of faulty thermostat probe. With COF=0 

compressor is always active. 

DISPLAY 

 

CF Temperature measurement unit
 °C=Celsius;  °F=Fahrenheit.  WARNING: When the measurement unit is 
changed the SET point and the values  of the parameters Hy, LS, US, Ot, 
ALU and ALL have to be checked and modified if necessary). 

rES Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

 

Lod Display : select which probe is displayed by the instrument: P1 = 
Thermostat probe; P2 = Evaporator probe 

DEFROST 

tdF  Defrost type

: EL = electrical heater; in = hot gas 

dtE  Defrost termination temperature

: (-50÷50 °C/  

-58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by 
the evaporator probe, which causes the end of defrost. 

IdF  Interval between defrost cycles

: (0÷120h) Determines the time interval 

between the beginning of two defrost cycles. 

MdF  (Maximum) length for defrost

: (0÷255min) When 

P2P = n

, (not evaporator 

probe: timed defrost) it sets the defrost duration, when 

P2P = y

 (defrost end 

based on temperature) it sets the maximum length for defrost. 

 

dSd Start defrost delay: ( 0÷99min) This is useful when different defrost start 
times are necessary to avoid overloading the plant.  

 

dFd  Temperature displayed during defrost: (rt = real temperature; it = 
temperature at defrost start; SEt = set point; dEF = “dEF” label) 

 

dAd MAX display delay after defrost: (0÷255min). Sets the maximum time 
between the end of defrost and the restarting of the real room temperature 
display. 

 

Fdt Drip 

time: (0

÷

120 min) time interval between reaching defrost 

termination temperature and the restoring of the control’s normal operation. 
This time allows the evaporator to eliminate water drops that might have 
formed due to defrost. 

 

dPo  First defrost after start-up: y = immediately; n = after the IdF time 

 

dAF  Defrost delay after continuous cycle: (0

÷

23.5h) time interval 

between the end of the fast freezing cycle and the following defrost related to 
it. 

ALARMS 

 

ALC  Temperature alarms configuration: (Ab; rE) 

 

Ab= absolute temperature: alarm temperature is given by the ALL or ALU 
values.   
rE = temperature alarms are referred to the set point. Temperature alarm is 
enabled when the temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this 

temperature is reached  the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET°C;  

-58÷230°F when this temperature is reached  the alarm is enabled, after the 
“ALd” delay time. 

 

ALd  Temperature alarm delay: (0÷255 min) time interval between the 
detection of an alarm condition and alarm signalling. 

 

dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) 
time interval between the detection of the temperature alarm condition after 
instrument power on and alarm signalling. 

DIGITAL INPUT  

i1P Digital input polarity: oP: 

the digital input is activated by opening the 

contact; 

CL: 

the digital input is activated by closing the contact.

 

i1F Digital input configuration:  

EAL 

= external alarm: “EA” message is displayed; 

bAL 

= serious alarm “CA” 

message is displayed. 

PAL 

= pressure switch alarm, “CA” message is 

displayed; 

dor

 = door switch function; 

dEF

 = activation of a defrost cycle; 

LHt 

=not enabled; 

Htr 

= kind of action inversion (cooling – heating).

 

did

:

 

(0

÷

255 min)  

with

 

i1F= EAL or i1F = bAL digital input alarm delay:

 delay between the 

detection of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F = PAL: time for pressure switch function: 

time interval to 

calculate the number of the pressure switch activation. 

nPS Pressure switch number:

 (0 

÷

15) Number of activation of the pressure 

switch, during the “

did

” interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the 
instrument to restart normal regulation. 

 

odc 

Compressor status when open door:  no, Fan = normal; CPr, F_C = 

Compressor OFF  

OTHER 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 

= PBC probe, 

ntC = 

NTC probe. 

 

dP1  First probe display 

 

dP2  Second probe display 

 

rEL Software 

release 

for internal use. 