Installing and Operating Instructions 

 

 

XR20CE2probecooling 

XR20C 

2/2  

• 

COF  Compressor OFF time with faulty probe
(0÷255 min) time during which the compressor is OFF 
in case of faulty thermostat probe. With COF=0 
compressor is always active. 

DISPLAY 

• 

CF  Temperature measurement unit:  °C = 
Celsius; °F= Fahrenheit. WARNING: When the 
measurement unit is changed the SET point and the 
values  of the parameters Hy, LS, US and Ot have to be 
checked and modified if necessary). 

rES  Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows the 

decimal point displaying. 

DEFROST 

    

dtE  Defrost termination temperature: (-50÷50 °C/  

-58÷122°F) (Enabled only when P2P=y) sets the 
temperature measured by the evaporator probe, which 
causes the end of defrost. 

IdF   Interval between defrost cycles: (1÷120h) Determines 

the time interval between the beginning of two defrost 
cycles. 

MdF  Length for defrost: (0÷255min) It sets the defrost 

duration. 

• 

dFd  Temperature displayed during defrost: (rt = real 
temperature; it = temperature at defrost start; SEt = set 
point; dEF = “dEF” label) 

• 

dAd  MAX display delay after defrost: (0÷255min). 
Sets the maximum time between the end of defrost and 
the restarting of the real room temperature display. 

DIGITAL INPUT  
i1P  Digital input polarity: oP: 
the digital input is activated 

by opening the contact; CL: the digital input is activated 
by closing the contact. 

did: (0÷255 min) door open signalling delay 

• 

odc Compressor status when open door: 
no=Digital Input not used  CPr= Compressor OFF.  

OTHER 
rEL Software release 
for internal use. 
Ptb  Parameter table index: readable only. For internal use. 

7. DIGITAL 

INPUT 

7.1  DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “i1P” parameter. 
i1P=CL: the input is activated by closing the contact. 
i1P=OP
: the input is activated by opening the contact 

8.  INSTALLATION AND MOUNTING 

Instrument  XR20C shall be mounted on panel, in a 29x71 
mm hole, and fixed using the special brackets supplied.  

 

To obtain an IP65 protection grade use the front panel rubber 
gasket (mod. RG-C) as shown in figure.  

 

The temperature range allowed for correct operation is 0

÷

60 

°C. Avoid places subject to strong vibrations, corrosive 
gases, excessive dirt or moisture.
 The same 
recommendations apply to probes. Let air circulate by the 
cooling holes. 

9. ELECTRICAL 

CONNECTIONS 

The instruments are provided with screw terminal block to 
connect cables with a cross section up to 2,5 mm

2

. Heat-

resistant cables have to be used. Before connecting cables 
make sure the power supply complies with the instrument’s 

requirements. Separate the probe cables from the power 
supply cables, from the outputs and the power 
connections.  
Do not exceed the maximum current allowed 
on each relay, in case of heavier loads use a suitable 
external relay. 

9.1 PROBE 

CONNECTION 

The probes shall be mounted with the bulb upwards to 
prevent damages due to casual liquid infiltration.
 It is 
recommended to place the probe away from air streams to 
correctly measure the average room temperature. 

10.  HOW TO USE THE HOT KEY  

10.1  HOW TO PROGRAM A HOT KEY FROM THE 

INSTRUMENT (UPLOAD) 

1. 

Program one controller with the front keypad. 

2. 

When the controller is ON, insert the “Hot key” and 
push 

o

 key; the  "uPL" message appears followed a 

The word  “End” 

3. Push 

SET” key and the End will stop being displayed. 

4. 

Turn OFF the instrument remove the “Hot Key”, then 
turn it ON again. 

NOTE: the “Err” message is displayed for failed 
programming. In this case push again 

o

 key if you want to 

restart the upload again or remove the “Hot key” to abort the 
operation. 

10.2  HOW TO PROGRAM AN INSTRUMENT 

USING A HOT KEY (DOWNLOAD) 

1. 

Turn OFF the instrument. 

2. 

Insert  a programmed “Hot Key” into the 5 PIN 
receptacle 
and then turn the Controller ON. 

3. 

Automatically the parameter list of the “Hot Key” is 
downloaded into the Controller memory, the “doL” 
message is blinking followed a by  “End”. 

4. 

After 10 seconds the instrument will restart working 
with the new parameters.  

5. Remove 

the 

“Hot Key”. 

NOTE the message “Err” is displayed for failed programming. 
In this case turn the unit off and then on if you want to restart 
the download again or remove the “Hot key” to abort the 
operation. 

11. ALARM 

SIGNALS 

Message  

Cause 

Output 

“EE”  

Data or memory failure 

“P1” 
 

Room probe  failure 

Output according to par. 
“Con” and “COF” 

“P2” 
 

2

nd

 probe  failure 

Output unchanged 

“dA” 

Door open 

Regulation restarts  

11.1 ALARM 

“EE” 

The instrument is provided with an internal check verifying 
memory integrity. Alarm “EE” flashes when a failure in the 
internal memory is detected. In such case call the service. 

11.2  ALARM RECOVERY  

Probe alarm “P1 & P2” start some seconds after the fault in 
the related probe; it automatically stops some seconds after 
the probe restarts normal operation. Check connections 
before replacing the probe. 
Alarm dA will recover as soon as the digital input is disabled. 

12. TECHNICAL 

DATA 

Housing: self extinguishing ABS. 
Case: XR20C 
frontal 32x74 mm; depth 60mm; 
Mounting 

XR20C panel mounting in a 71x29mm panel cut-out 

Protection: IP20. 
Frontal protection:
  
 

XR20C IP65 with frontal gasket RG-C (optional). 

Connections: Screw terminal block 

 2,5 mm

2

 heat- 

 resistant  wiring. 
Power supply: according to the model: 12Vac/dc, ±10%; 
24Vac/dc, ±10%; 230Vac 

±

10%, 50/60Hz, 110Vac 

±

10%, 

50/60Hz 
Power absorption: 
3VA max 
Display
: 3 digits, red LED, 14,2 mm high.  
Inputs: 2 NTC probes. 1 Digital input 
Relay outputs
 
 Compressor: 
 

SPST relay 16FLA/96LRA 

Data storing: on the non-volatile memory (EEPROM). 
Kind of action: 1B. 
Pollution grade: normal 
Software class: A. 
Operating temperature: 
0÷60 °C. 
Storage temperature: -25÷60 °C.  
Relative humidity: 20

÷

85% (no condensing) 

Measuring and regulation range:  

NTC probe: -40÷110°C (-58÷230°F) 

Resolution: 0,1 °C or 1°C or 1 °F (selectable). 
Accuracy (ambient temp. 25°C):  ±0,7 °C ±1 digit 

13. CONNECTIONS 

13.1  XR20C: 16FLA COMPRESSOR  

4 5

6

7

9 10 11 12

Comp

R

oom

8

Hot Key

Line

Supply

 120V~

120Vac supply: connect to the terminals 7 and 8. 
OPTIONAL: 

12Vac/dc supply: connect to the terminals 7 and 8. 
24Vac/dc supply: connect to the terminals 7 and 8. 
230Vac supply: connect to the terminals 7 and 8. 

14.  DEFAULT SETTING VALUES  

Label

Name 

Range 

°C/°F 

Set  Set point 

LS÷US 

3/37

Hy  Differential 

0,1

÷

25.5°C/ 

1

÷

 45°F 

2/4 

LS  Minimum set point 

-50°C

÷

SET/ 

-58°F

÷

SET 

-40/ 
- 40 

US  Maximum set point 

SET

÷

150°C/ 

SET 

÷

 230°F 

110/

230 

Ot  Thermostat probe calibration 

-12

÷

 12°C /   

-21 

÷

 21°F 

0/0 

P2P  2

nd

 probe presence 

Y/N 

OE  2

nd

 probe calibration 

-12

÷

12°C /-

120

÷

120°F

 

 

OdS  Outputs delay at start up 

0÷255 min 

AC  Anti-short cycle delay 

÷

 50 min 

COn  Compressor ON time with faulty 

probe 

÷

 255 min 

15 

COF  Compressor OFF time with faulty 

probe 

÷

 255 min 

30 

CF  Temperature measurement unit 

°C 

÷

 °F 

°C/°F

rES  Resolution 

in 

÷

 dE 

dE/- 

dtE  Defrost end temp 

-50 

÷

 50 °C

 

46 

IdF  Interval between defrost cycles 

÷

 120 hour 

MdF  (Maximum) length for defrost 

÷

 255 min 

20 

dFd  Displaying during defrost 

rt, it, SEt, 

DEF 

it 

dAd  MAX display delay after defrost 

0 ÷ 255 min 

30 

i1P  Digital input polarity 

oP=opening;

CL=closing 

cL 

did  Digital input alarm delay 

0÷255min 

odc  Compressor status with open door: 

No=No Digital 

input used. 

CPr; = 

Compressor  

off

 

no 

rEL  Software release 

-- 

Ptb  Map code 

-- 

Hidden parameters 

 

 