background image

 

 

1592020110 XR01-02CX GB r1.2 24.07.2015 

                           XR01-02CX 

1/3 

 

DIGITAL CONTROLLER 

XR01-02CX 

1. 

CONTENTS 

1.

 

Contents ____________________________________________________________________________ 1

 

2.

 

General warnings _____________________________________________________________________ 1

 

3.

 

General description ___________________________________________________________________ 1

 

4.

 

Regulation  __________________________________________________________________________ 1

 

5.

 

Defrost (ONLY XR02CX) _______________________________________________________________ 1

 

6.

 

Front panel commands  ________________________________________________________________ 1

 

7.

 

Parameters __________________________________________________________________________ 2

 

8.

 

Digital inputs _________________________________________________________________________ 2

 

9.

 

Installation and mounting _______________________________________________________________ 2

 

10.

 

Electrical connections  _________________________________________________________________ 2

 

11.

 

How to use the hot key_________________________________________________________________ 2

 

12.

 

Alarm signalling ______________________________________________________________________ 2

 

13.

 

Technical data _______________________________________________________________________ 2

 

14.

 

Connections _________________________________________________________________________ 3

 

15.

 

Default setting values __________________________________________________________________ 3

 

 

2. 

GENERAL WARNINGS 

2.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 
the same and unchanged functionality. 

2.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see 
address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 
inductive loads could be useful. 

3. 

GENERAL DESCRIPTION 

Model 

XR01CX

format  32  x  74  x50

 

mm

  format  is  a  single  stage  temperature  controller  suitable  for 

applications  in the field of refrigeration or heating. It provides a relay output to drive the compressor.  It  is also 
provided  with  1  NTC  probe  input  and  one  configurable  digital  input.  The  instrument  is  fully  configurable 
through special parameters that can be easily programmed through the keyboard or the by HOTKEY. 
 
Model 

XR02CX

format  32  x  74  x  50  mm

,    is  a  digital  thermostat  with  off  cycle  defrost  designed  for 

refrigeration applications at normal temperature. It provides a relay output to drive the compressor.  It is also 
provided  with  1  NTC  probe  input  and  one  configurable  digital  input.  The  instrument  is  fully  configurable 
through special parameters that can be easily programmed through the keyboard or the by HOTKEY. 

4. 

REGULATION 

4.1

 

THE REGULATION OUTPUT 

 

The regulation is performed according to the temperature measured by probe. The XR01CX is provided with 
the 

CH

  programmable  parameter  wich  enables  the  user  to  set  the  regulation  both  for  heating  or  cooling 

applications: 

 

CH=cL

 --> cooling applications; 

 

CH=Ht

 --> heating applications; 

4.2

 

COOLING APPLICATIONS 

 

The  regulation  is  performed  according  to 
the  temperature  measured  by  the 
thermostat probe with a positive differential 
from  the  set  point:  if  the  temperature 
increases  and  reaches  set  point  plus 
differential  the  compressor  is  started  and 
then  turned  off  when  the  temperature 
reaches the set point value again. 

 

 

In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters 

Cy

” and “

Cn

”. 

4.3

 

HEATING APPLICATIONS ( ONLY FOR XR01CX) 

 

The  Hy  value  is  automatically  subtracted  to 
the SET POINT. If the temperature decreases 
and  reaches  set  point  minus  differential  the 
output is started and then turned off when the 
temperature reaches set point value again. 

 

 

5. 

DEFROST (ONLY XR02CX) 

Defrost  is  performed  through  a  simple  stop  of  the  compressor.  Parameter  “i

d

”  controls  the  interval 

between defrost cycles, while its length is controlled by parameter “

Md

”. 

6. 

FRONT PANEL COMMANDS 

 

  

To  display  target  set  point,  in 
programming  mode  it  selects  a 
parameter 

or 

confirm 

an 

operation 

 

To  start  a  manual  defrost    (Only 
XR02CX) 

 

In programming mode it browses 
the parameter codes or increases 
the displayed value 

AUX

 

In programming mode it browses 
the 

parameter 

codes 

or 

decreases the displayed value 

 

KEYS COMBINATION 

 

+

 

 

To lock or unlock the keyboard

 

 

+

 

 

To enter in programming mode 

 

+

 

 

To return to room temperature display

 

 

LED 

MODO 

SIGNIFICATO 

 

On 

Compressore enabled 

Flashing 

Anti short cycle delay enabled (AC parameter) 

 

On 

Defrost in progress 

Flashing 

Dripping in progress 

 

On 

Measurement unit  

Flashing 

Programming mode 

 

On 

Measurement unit 

Flashing 

Programming mode 

6.1

 

HOW TO SEE THE SET POINT 

 

1.

 

Push and immediately release the 

SET 

key, the set point will be showed; 

2.

 

Push and immediately release the 

SET

 key or wait about 5s to return to normal visualisation. 

6.2

 

HOW TO CHANGE THE SETPOINT 

 

1.

 

Push the SET key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value push the o or n arrows within 10s. 

4.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.3

 

HOW TO START A MANUAL DEFROST (ONLY XR02CX) 

 

Push the 

DEF 

 key for more than 2 seconds and a manual defrost will start 

6.4

 

HOW TO CHANGE A PARAMETER VALUE 

 

To change the parameter’s value operate as follows:  

1.

 

Enter  the  Programming  mode  by  pressing  the 

SET

  keys  for  3s  (“

°C”  or  “°F”

  LED  starts 

blinking). 

2.

 

Select the required parameter. Press the “

SET

” key to display its value 

3.

 

Use   or   to change its value. 

4.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET

+   or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.5

 

HIDDEN MENU 

The hidden menu includes all the parameters of the instrument. 

HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter  the  Programming  mode  by  pressing  the 

SET

  keys  for  3s  (“

°C”  or  “°F”

  LED  starts 

blinking). 

2.

 

Released  the  keys,  then  push  again  the 

SET

  keys  for  more  than  7s.  The  L2  label  will  be 

displayed immediately followed from the Hy parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the “

SET

” key to display its value 

5.

 

Use   or   to change its value. 

6.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET

+   or wait 15s without pressing a key. 

NOTE1: 

if none parameter is present in L1, after 3s the “nP” message is displayed.  Keep the keys 

pushed till the L2 message is displayed.  

NOTE2

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE  FIRST 
LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 

level) by pressing 

SET

+  . In HIDDEN MENU when a parameter is present in First Level the decimal 

point is on. 

6.6

 

TO LOCK THE KEYBOARD 

 

1.

 

Keep pressed for more than 3s the   and   keys. 

2.

 

The “

OF

” message will be displayed and the keyboard will be locked. If a key is pressed more 

than 3s the “OF” message will be displayed. 

6.7

 

TO UNLOCK THE KEYBOARD 

 

Keep pressed together for more than 3s the   and   keys till the 

“on” 

message will be displayed. 

 

 

 

 

 