DEFAULT SETTING VALUES 

 
 

Label  Name 

  Range 

Default  Level 

  REGULATION  

°C/°F  XM470 

Set Set 

point 

LS÷US 

-5/23  Pr1 

Hy 

Differential 

0,1÷25,5 °C / 1÷45°F 

2/4 

Pr1 

LS 

Minimum set point 

 -50,0°C÷SET / -58°F÷SET  -30/-22 

Pr2 

US 

Maximum set point 

SET ÷ 110°C / SET ÷ 230°F  20/68 

Pr2 

OdS  Outputs activation delay at start up 

0÷255 min. 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

COn  solenoid valve on time with faulty probe 

0÷255 min. 

15 

Pr2 

COF  solenoid valve off time with faulty probe 

0÷255 min. 

30 

Pr2 

 DISPLAY 

 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C/°F 

Pr2 

rES  Resolution (integer/decimal point) 

in ÷ de 

de 

Pr1 

Lod  Local display  

P1 ÷ P2 ÷ P3 ÷ 1r2 

P1 

Pr2 

 DEFROST 

 

 

 

tdF 

Defrost type 

rE, in  

rE 

Pr1 

EdF  Defrost mode 

rtc, In, Sd 

In 

Pr2 

SdF  Set point for SMART DEFROST 

-30 ÷ +30°C / -22÷+86°F 

Pr2 

dtE  Defrost termination temperature (1°Evaporator) -50,0÷110°C /-58÷230°F 

8/46 

Pr1 

IdF  Interval between defrost cycles 

1÷120h 

Pr1 

MdF  (Maximum) length for 1° defrost 

0÷255 min. 

30 

Pr1 

dFd  Displaying during defrost 

rt, it, SEt, dEF, dEG 

it 

Pr2 

dAd  MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

Fdt  Draining time 

0÷60 min. 

Pr2 

dPO  First defrost after start up 

n ÷ y 

Pr2 

 FANS 

 

 

 

FnC  Fans operating mode 

C-n, C-y, O-n, O-y  

O-n 

Pr2 

Fnd  Fans delay after defrost 

0÷255 min. 

10 

Pr2 

FSt Fans 

stop 

temperature 

-50,0÷110°C /  -58÷230°F 

2/35 

Pr2 

 ALARMS 

 

 

 

ALC  Temperature alarms configuration rE÷Ab 

rE 

Pr2 

ALU  MAXIMUM temperature alarm -50,0÷110°C/-58÷230°F 

10/20 

Pr1 

ALL  minimum temperature alarm 

-50,0÷110°C/ -58÷230°F 

10/20 

Pr1 

AFH  Temperature alarm and fan differential 

0,1÷25,5 °C/ 1÷45°F 

2/4 

 

ALd  Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO  Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 

Pr2 

EdA  Alarm delay at the end of defrost  

0÷255 min. 

30 

Pr2 

tBA  Alarm relay silencing 

y ÷ n 

Pr2 

 ANALOGUE 

INPUTS 

 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr1 

OE  Evaporator probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr2 

O3 

Auxiliary probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr2 

P2P  Evaporator probe presence 

n ÷ y 

Pr2 

P3P  Auxiliary probe presence 

n ÷ y 

Pr2 

HES  Temperature increase during the Energy Saving 

cycle  

-30÷30°C / -54÷54°F 

Pr2 

  DIGITAL INPUTS 

 

 

 

I1P  Door switch polarity 

CL÷OP 

CL 

Pr2 

I2P  Configurable digital input polarity 

CL÷OP 

CL 

Pr2 

i2F 

Digital input configuration 

EAL, bAL, PAL, 

dFr, AUS, ES, OnF 

EAL Pr2 

dId 

Digital input alarm delay 

0÷255 min. 

Pr2 

  TIME AND WEEKLY HOLIDAYS 

 

 

 

CbP  Clock Board presence 

n ÷ y 

Pr2 

Hur  Current hour 

0 ÷ 23 

Pr2 

Min  Current minute 

0 ÷ 59 

Pr2 

dAY  Current day 

Sun ÷ SAt 

Sun 

Pr2 

Hd1  First weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr2 

Hd2  Second weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr2 

Hd3  Third weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr2 

  ENERGY SAVING TIMES 

 

 

 

ILE  Energy Saving cycle start during workdays 

0 ÷ 23h 50 min. 

Pr2 

dLE  Energy Saving cycle length during workdays 

0 ÷ 24h 00 min. 

Pr2 

ISE  Energy Saving cycle start on holidays 

0 ÷ 23h 50 min. 

Pr2 

dSE  Energy Saving cycle length on holidays 

0 ÷ 24h 00 min. 

Pr2 

HES  Temperature increase during the Energy Saving 

cycle 

-30÷30°C / -54÷54°F 

Pr2 

 

DEFROST TIMES 

 

 

 

Ld1 1

st

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Ld2 2

nd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Ld3 3

rd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Ld4 4

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld5 5

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld6 6

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld7 7

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld8 8

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd1 1

st

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Label  Name 

  Range 

Default  Level 

Sd2 2

nd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Sd3 3

rd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Sd4 4

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd5 5

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd6 6

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd7 7

th

 holiday defrost start 

0 ÷ 23h 50  min. - nu 

nu 

Pr2 

Sd8 8

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

  LAN CONFIGURATION 

 

 

 

LSn  L.A.N. section number   

1 ÷ 5 

1 Pr2 

Lan  L.A.N. serial address 

1 ÷ LSn 

Pr2 

LMd  L.A.N. defrost synchronisation 

n ÷ y 

Pr2 

LSP  L.A.N. Set-point synchronisation 

n ÷ y 

Pr2 

Lds  L.A.N. display synchronisation 

n ÷ y 

Pr2 

LOF  L.A.N. On/Off synchronisation 

n ÷ y 

Pr2 

LLi   L.A.N. Light  synchronisation 

n ÷ y 

Pr2 

LAU  L.A.N. AUX output synchronisation 

n ÷ y 

Pr2 

LES  L.A.N. Energy Saving synchronisation 

n ÷ y 

Pr2 

LSd  Remote probe display 

n ÷ y 

Pr2 

  OTHER  

 

 

Adr  RS485 Serial address 

0÷247 

Pr1 

dP1  Probe 1 value display 

- - - 

- - - 

Pr2 

dP2  Probe 2 value display 

- - - 

- - - 

Pr2 

dP3  Probe 3 value display 

- - - 

- - - 

Pr2 

rEL  Software release 

- - - 

- - - 

Pr2 

Ptb  Map code 

- - - 

- - - 

Pr2 

Pr2   Access parameter list 

- - - 

- - - 

Pr2 

 

 

 

 

 