Dixell
Installing and Operating Instructions
rel.1.0 –07/03/2002 - cod.
1592013010
1592013010 XM470K GB
XM470K
6/6
16.
DEFAULT SETTING VALUES
Label Name
Range
Default Level
REGULATION
°C/°F XM470
Set Set
point
LS÷US
-5/23 Pr1
Hy
Differential
0,1÷25,5 °C / 1÷45°F
2/4
Pr1
LS
Minimum set point
-50,0°C÷SET / -58°F÷SET -30/-22
Pr2
US
Maximum set point
SET ÷ 110°C / SET ÷ 230°F 20/68
Pr2
OdS Outputs activation delay at start up
0÷255 min.
1
Pr2
AC
Anti-short cycle delay
0÷30 min.
1
Pr1
COn solenoid valve on time with faulty probe
0÷255 min.
15
Pr2
COF solenoid valve off time with faulty probe
0÷255 min.
30
Pr2
DISPLAY
CF
Temperature measurement unit
°C ÷ °F
°C/°F
Pr2
rES Resolution (integer/decimal point)
in ÷ de
de
Pr1
Lod Local display
P1 ÷ P2 ÷ P3 ÷ 1r2
P1
Pr2
DEFROST
tdF
Defrost type
rE, in
rE
Pr1
EdF Defrost mode
rtc, In, Sd
In
Pr2
SdF Set point for SMART DEFROST
-30 ÷ +30°C / -22÷+86°F
0
Pr2
dtE Defrost termination temperature (1°Evaporator) -50,0÷110°C /-58÷230°F
8/46
Pr1
IdF Interval between defrost cycles
1÷120h
6
Pr1
MdF (Maximum) length for 1° defrost
0÷255 min.
30
Pr1
dFd Displaying during defrost
rt, it, SEt, dEF, dEG
it
Pr2
dAd MAX display delay after defrost
0÷255 min.
30
Pr2
Fdt Draining time
0÷60 min.
0
Pr2
dPO First defrost after start up
n ÷ y
n
Pr2
FANS
FnC Fans operating mode
C-n, C-y, O-n, O-y
O-n
Pr2
Fnd Fans delay after defrost
0÷255 min.
10
Pr2
FSt Fans
stop
temperature
-50,0÷110°C / -58÷230°F
2/35
Pr2
ALARMS
ALC Temperature alarms configuration rE÷Ab
rE
Pr2
ALU MAXIMUM temperature alarm -50,0÷110°C/-58÷230°F
10/20
Pr1
ALL minimum temperature alarm
-50,0÷110°C/ -58÷230°F
10/20
Pr1
AFH Temperature alarm and fan differential
0,1÷25,5 °C/ 1÷45°F
2/4
ALd Temperature alarm delay
0÷255 min.
15
Pr2
dAO Delay of temperature alarm at start up
0 ÷ 23h 50 min.
1,3
Pr2
EdA Alarm delay at the end of defrost
0÷255 min.
30
Pr2
tBA Alarm relay silencing
y ÷ n
y
Pr2
ANALOGUE
INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr1
OE Evaporator probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
O3
Auxiliary probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
P2P Evaporator probe presence
n ÷ y
y
Pr2
P3P Auxiliary probe presence
n ÷ y
n
Pr2
HES Temperature increase during the Energy Saving
cycle
-30÷30°C / -54÷54°F
0
Pr2
DIGITAL INPUTS
I1P Door switch polarity
CL÷OP
CL
Pr2
I2P Configurable digital input polarity
CL÷OP
CL
Pr2
i2F
Digital input configuration
EAL, bAL, PAL,
dFr, AUS, ES, OnF
EAL Pr2
dId
Digital input alarm delay
0÷255 min.
5
Pr2
TIME AND WEEKLY HOLIDAYS
CbP Clock Board presence
n ÷ y
n
Pr2
Hur Current hour
0 ÷ 23
0
Pr2
Min Current minute
0 ÷ 59
0
Pr2
dAY Current day
Sun ÷ SAt
Sun
Pr2
Hd1 First weekly holiday
Sun ÷ SAt – nu
nu
Pr2
Hd2 Second weekly holiday
Sun ÷ SAt – nu
nu
Pr2
Hd3 Third weekly holiday
Sun ÷ SAt – nu
nu
Pr2
ENERGY SAVING TIMES
ILE Energy Saving cycle start during workdays
0 ÷ 23h 50 min.
0
Pr2
dLE Energy Saving cycle length during workdays
0 ÷ 24h 00 min.
0
Pr2
ISE Energy Saving cycle start on holidays
0 ÷ 23h 50 min.
0
Pr2
dSE Energy Saving cycle length on holidays
0 ÷ 24h 00 min.
0
Pr2
HES Temperature increase during the Energy Saving
cycle
-30÷30°C / -54÷54°F
0
Pr2
DEFROST TIMES
Ld1 1
st
workdays defrost start
0 ÷ 23h 50 min. - nu
6.0
Pr2
Ld2 2
nd
workdays defrost start
0 ÷ 23h 50 min. - nu
13.0
Pr2
Ld3 3
rd
workdays defrost start
0 ÷ 23h 50 min. - nu
21.0
Pr2
Ld4 4
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld5 5
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld6 6
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld7 7
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld8 8
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd1 1
st
holiday defrost start
0 ÷ 23h 50 min. - nu
6.0
Pr2
Label Name
Range
Default Level
Sd2 2
nd
holiday defrost start
0 ÷ 23h 50 min. - nu
13.0
Pr2
Sd3 3
rd
holiday defrost start
0 ÷ 23h 50 min. - nu
21.0
Pr2
Sd4 4
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd5 5
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd6 6
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd7 7
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd8 8
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
LAN CONFIGURATION
LSn L.A.N. section number
1 ÷ 5
1 Pr2
Lan L.A.N. serial address
1 ÷ LSn
1
Pr2
LMd L.A.N. defrost synchronisation
n ÷ y
n
Pr2
LSP L.A.N. Set-point synchronisation
n ÷ y
n
Pr2
Lds L.A.N. display synchronisation
n ÷ y
n
Pr2
LOF L.A.N. On/Off synchronisation
n ÷ y
n
Pr2
LLi L.A.N. Light synchronisation
n ÷ y
n
Pr2
LAU L.A.N. AUX output synchronisation
n ÷ y
n
Pr2
LES L.A.N. Energy Saving synchronisation
n ÷ y
n
Pr2
LSd Remote probe display
n ÷ y
n
Pr2
OTHER
Adr RS485 Serial address
0÷247
1
Pr1
dP1 Probe 1 value display
- - -
- - -
Pr2
dP2 Probe 2 value display
- - -
- - -
Pr2
dP3 Probe 3 value display
- - -
- - -
Pr2
rEL Software release
- - -
- - -
Pr2
Ptb Map code
- - -
- - -
Pr2
Pr2 Access parameter list
- - -
- - -
Pr2
Dixell s.r.l. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail:[email protected] - http://www.dixell.com