background image

Dixell

 

Installing and Operating Instructions 

rel.1.0 –07/03/2002 - cod. 

1592013000

 

1592013000   XM440_460K   GB 

XM440K & XM460K 

          

3/1 

 

6.2

 

TO SET THE TIME AND THE WEEKLY HOLIDAYS 

     

 

    

 

1.

 

Push the 

n

 key for more than 3 seconds  

2.

 

The current time is displayed. 

3.

 

By pushing the SET key, setting the current hour, minutes, day and 

the weekly holidays (up to 3) will be possible.   

4.

 

To exit, press SET + UP or wait 15s without pressing any key. 

6.3

 

TO SET THE DEFROST TIMES  

     

 

Only T640 and V640 keyboards 

1.

 

Push the 

n

 key for more than 3 seconds  

2.

 

The current time is displayed. 

3.

 

By pushing DEF key, the DEF led will start flashing and setting defrost time will 

be possible.   

4.

 

To exit, press SET + UP or wait 15s without pressing any key. 

7.

 

PARAMETER LIST 

REGULATION 
Hy Differential: 

(0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Solenoid 

valve Cut IN is Set Point Plus Differential (Hy). Solenoid valve Cut OUT is when the temperature 

reaches the set point. 

LS  Minimum set point limit: (-50,0°C

÷

SET; -58°F÷SET) Sets the minimum acceptable value for the 

set point. 

US  Maximum set point limit: (SET

÷

110°C; SET÷230°F) Set the maximum acceptable value for set 

point. 

OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of 

the instrument and inhibits any output activation for the period of time set in the parameter. (AUX 

and Light can work) 

AC  Anti-short cycle delay: (0÷30 min) interval between the solenoid valve stop and the following 

restart. 

Con solenoid valve ON time with faulty probe: (0÷255 min) time during which the solenoid valve is 

active in case of faulty thermostat probe. With COn=0 solenoid valve is always OFF. 

COF solenoid valve OFF time with faulty probe: (0÷255 min) time during which the solenoid valve is 

off in case of faulty thermostat probe. With COF=0 solenoid valve is always active. 

DISPLAY 
CF  Temperature measurement unit:
 °C = Celsius; °F = Fahrenheit . When the measurement unit is 

changed the SET point and the values  of the regulation parameters have to be modified 

rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. 

de = 0,1°C; in = 1 °C  

Lod Local display : select which probe is displayed by the remote display (T850)  

P1 = Thermostat probe 

P2 = Evaporator probe 

P3 = auxiliary probe 

1r2 = difference between P1 and P2 (P1-P2) 

DEFROST 
tdF   Defrost type:  

rE = electrical heater (SOLENOID VALVE OFF) 

in = hot gas (SOLENOID VALVE and defrost relays ON) 

EdF Defrost mode:  

 

 rtc 

Real Time Clock mode. Defrost time follows Ld1÷Ld8 parameters on workdays and 

Sd1÷Sd8 on holidays.  

in = interval mode. The defrost starts when the time “Idf” is expired. 

Sd = Smart Defrost mode. The time IdF (interval between defrosts) is increased only when the 

solenoid valve is active (even non consecutively) and only if the evaporator temperature is less 

than the value in "SdF” (set point for SMARTFROST).  

SdF  Set point for SMARTFROST: (-30

÷

30 °C/ -22

÷

86 °F) evaporator temperature which allows the 

IdF counting (interval between defrosts) in SMARTFROST mode. 

 dtE  Defrost  termination  temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the 

evaporator probe is present) sets the temperature measured by the evaporator probe which 

causes the end of defrost. 

IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF  (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the 

defrost duration, when P2P = y, defrost end based on temperature, it sets the maximum length for 

defrost. 

dFd  Display during defrost:  

 rt = real temperature;  

it = temperature reading at the defrost start; 

Set = set point; 

dEF = “dEF” label; 

 dEG = “dEG” label; 

dAd  Defrost display time out: (0

÷

255 min) Sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

Fdt   Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and 

the restoring of the control’s normal operation. This time allows the evaporator to eliminate water 

drops that might have formed due to defrost. 

dPO  First defrost after start-up:   

 y 

= Immediately; n = after the IdF time 

FANS (XM460K) 
FnC Fan operating mode: 

C-n = running with the solenoid valve, OFF during the defrost;  

C-y = running with the solenoid valve, ON during the defrost; 

O-n = continuous mode, OFF during the defrost; 

O-y = continuous mode, ON during the defrost; 

Fnd  Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator 

fans start. 

FSt  Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator 

probe, above which the fan is always OFF. 

ALARMS 
ALC Temperature alarm configuration 

rE = High and Low alarms related to Set Point  

Ab = High and low alarms related to the absolute temperature. 

ALU High temperature alarm setting:  

 

ALC= rE, 0 

÷

 50°C or 90°F 

 

ALC= Ab, ALL 

÷

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

ALL  Low temperature alarm setting: 

 

ALC = rE , 0 

÷

 50 °C or 90°F 

 

ALC = Ab , - 50°C or -58°F 

÷

 ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for 

temperature alarm set point and fan regulation set point, always positive. 

ALd  Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition 

and the corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of 

the temperature alarm condition after the instrument power on and the alarm signalling. 

EdA  Alarm delay at the end of defrost: (0

÷

255 min) Time interval between the detection of the 

temperature alarm condition at the end of defrost and the alarm signalling. 

tbA   Buzzer and alarm relay silencing: by pushing one of the keypad buttons. 

 

n= Only the Buzzer is silenced; 

 

y= Buzzer and relay are silenced. 

PROBE INPUTS 
Ot  Thermostat probe calibration: 
(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the 

thermostat probe. 

OE    Evaporator probe calibration: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the 

evaporator probe. 

O3  Auxiliary probe calibration: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the 

evaporator probe. 

P2P  Evaporator probe presence:  

n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and 

time. 

P3P  Auxiliary probe presence: n= not present; y= present. 

HES Temperature increase during the Energy Saving cycle : (-30÷30°C / -54÷54°F) sets the 

increasing value of the set point during the Energy Saving cycle.  

 

 

 

DIGITAL INPUTS 
I1P  Energy saving digital input polarity:
 

 

CL : the digital input is activated by closing the contact; 

 

OP : the digital input is activated by opening the contact. 

I2P  Configurable digital input polarity: 

 

CL : the digital input is activated by closing the contact; 

 

OP : the digital input is activated by opening the contact 

I2F  Digital input operating mode: configure the digital input function: 

 EAL 

= generic alarm; 

 bAL 

= serious alarm mode; 

 dFr 

= Start defrost; 

 AUS 

= Relay AUX actuation; 

 

onF = remote On/OFF.  

 Hdf 

= Holiday function. 

did   Time interval/delay for digital input alarm:(0

÷

255 min.) Time interval to calculate the number of 

the pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter 

defines the time delay between the detection and the successive signalling of the alarm. 

bbC  Type of keyboard: (4bb

÷

8bb min.) State the kind of keyboard used: 4bb=4 keys, 6bb= 6 keys, 

8bb= 8 keys 

TO SET CURRENT TIME AND WEEKLY HOLIDAYS 
CbP  Clock board present 
(y ÷ n) Presence of the RTC  

Hur Current hour (0 ÷ 23 h) 

Min Current minute (0 ÷ 59min) 

dAY Current day (Sun ÷ SAt) 

Hd1 First weekly holiday (Sun ÷ nu) Set the first day of the week which follows the holiday times. 

Hd2 Second weekly holiday (Sun ÷ nu) Set the second day of the week which follows the holiday 

times. 

Hd3 Third weekly holiday (Sun ÷ nu) Set the third day of the week which follows the holiday times. 

 

N.B.  Hd1,Hd2,Hd3 can be set also as “nu” value (Not Used).  

 

TO SET DEFROST TIMES 
Ld1÷Ld8 Workday defrost start
 (0 ÷ 23h 50 min.) These parameters set the beginning of the eight 

programmable defrost cycles during workdays. Ex. When Ld2 = 12.4 the second defrost starts at 

12.40 during workdays.  

Sd1÷Sd8 Holiday defrost start (0 ÷ 23h 50 min.) These parameters set the beginning of the eight 

programmable defrost cycles on holidays. Ex. When Sd2 = 3.4 the second defrost starts at 3.40 on 

holidays.  

N.B. : 

To disable a defrost cycle set it to “nu”(not used).  

Ex.  If Ld6=nu ;  the sixth defrost cycle is disabled 

 

L.A.N. CONFIGURATION 
LSn  L.A.N. section number 
 (1 ÷ 5)  States the number of sections available in the L.A.N. 

Lan  L.A.N. serial address  (1 ÷ LSn)  Identifies the instrument address inside local network of 

multiplexed cabinet controller. 

LSP  L.A.N. set-point  synchronisation   

y= the section set-point, when modified, is updated to the same value on all the other sections 

n= the set-point value is modified only in the local section 

Содержание XM440K

Страница 1: ...o defrost modes are available through the tdF parameter defrost with electrical heater and hot gas defrost The defrost interval is control by means of parameter EdF EdF rtc the defrost is made in real...

Страница 2: ...display its value and LED starts blinking 4 Use o or n to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP or wait 15s without pressing a k...

Страница 3: ...min The time interval between the defrost end and evaporator fans start FSt Fan stop temperature 50 110 C 58 230 F setting of temperature detected by evaporator probe above which the fan is always OFF...

Страница 4: ...SET HES parameter sum This function is enabled until the digital input is activated 8 2 CONFIGURABLE INPUT GENERIC ALARM EAL As soon as the digital input is activated the unit will wait for did time...

Страница 5: ...m output ON Other outputs unchanged HA Maximum temperature alarm Alarm output ON Other outputs unchanged LA Minimum temperature alarm Alarm output ON Other outputs unchanged EE Data or memory failure...

Страница 6: ...12 0 C 21 21 F 0 Pr2 Pr2 O3 Auxiliary probe calibration 12 0 12 0 C 21 21 F 0 Pr2 Pr2 P2P Evaporator probe presence n y y Pr2 Pr2 P3P Auxiliary probe presence n y n Pr2 Pr2 HES Temperature increase d...

Страница 7: ...Range Default XM440 XM460 dP2 Probe 2 value display Pr2 Pr2 dP3 Probe 3 value display Pr2 Pr2 rEL Software release Pr2 Pr2 Ptb Map code Pr2 Pr2 Pr2 Access parameter list Pr2 Pr2 Dixell s r l Via dell...

Отзывы: