Operating instruction manual 

1592019010 

 

1592019010 XEV11D GB r1.2 2008.07.08.doc 

                           

XEV11D 

3/4 

PPr 

Pressure probe value (read only

): it shows pressure probe value. The value depends on 

PrM

tP2 

temperature from P2 (read only

): it shows temperature obtained from conversion of 

pressure value 

d1S 

Free of voltage digital input State (read only): 

it shows

 

the free of voltage digital input; 

d2S 

High voltage digital input State (read only): 

it shows the high voltage digital input state; 

Adr  

RS485 Serial Address: 

(1÷247) Identifies the instrument address when connected to a 

ModBUS compatible monitoring system. 

Mod  ModBus: 

(AdU÷StD) 

AdU=

 (Only for XWEB3000 system) in this case XEV and 

thermostatic controller are considered an alone instrument (it requires a  custom library for 
XWEB); 

StD= 

to use XEV in stand-alone mode, in this case normal Modbus-RTU protocol 

is used; 

Ptb  

  Parameters map:

 

(read only)

 it identifies parameters map written by factory 

rEL  

Release 

Firmware:

 

(read only) 

it shows

 

firmware release 

Pr2  

  Second level menu 

7.

 

DIGITAL INPUTS 

There are two digital inputs. One of them is free of voltage and the other is at supply voltage and both 
can be configured as cooling call. In this way the cooling call can arrive via instruments with direct load 
outputs or via instruments with output without voltage. 

One of these inputs must be configured as 

cooling call. 

8.

 

PLANT STARTING FUNCTION 

If necessary, by pressing and holding 

o

SET

 keys combination for 5 seconds the driver opens 

completely the valve and shows on display the “

ON

” label. To disable this function press and hold 

another time 

o

SET

 keys combination 

or

 activate digital input configured as CCL 

or

 wait 

FOt 

time 

out. 

9.

 

ELECTRICAL CONNECTIONS 

The instrument are provided with screw terminal block to connect cables with a cross section up to 2,5 
mm

2

. Heat-resistant cables have to be used. Before connecting cables make sure the power supply 

complies with the instrument’s requirements. Separate the probe cables from the power supply cables, 
from the outputs and the power connections. Do not exceed the maximum current allowed on each 
relay, in case of heavier loads use a suitable external relay. 

9.1

 

PROBES 

 

Advised temperature probe placement is 
illustrated in the figure. Between 0 and 180 
inclination degrees respect to horizontal pipe 
section. For suction pressure probe there 
aren’t particular prescriptions 

 

10.

 

RS485 SERIAL LINE 

All models can be connected to the monitoring and supervising system XWEB3000. If 

Mod=Std

 

standard ModBUS-RTU protocol is used, if 

Mod=AdU

 custom XWEB library is required. 

11.

 

HOW TO USE THE HOT KEY  

11.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the remote keypad; 

2.

 

When the controller is ON, insert the “

Hot key

”; the four LEDs in the front of instrument panel 

blink for about 5 seconds to indicate that transfer operation will start; 

3.

 

The upload starts automatically and 

Alarm

 and 

Tx/Rx

 LEDs are active during operation; 

4.

 

At the end, the instrument turn ON for about 10 seconds: 

 

the 

Tx/Rx

 LED if the operation is well done; 

 

the 

Alarm

 LED if the operation is wrong. 

 

11.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

6)

 

Turn OFF the instrument. 

7)

 

Insert  a 

programmed “Hot Key” into the 5 PIN connector 

and then turn the Controller ON. 

8)

 

Automatically the download starts and the LEDs 

Alarm

 e 

Tx/Rx

 are active during operation

.

 

9)

 

At the end, the instrument turn ON for about 10 seconds: 

 

the 

Tx/Rx

 LED if the operation is well done; 

 

the 

Alarm

 LED if the operation is wrong. 

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then on 

if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

12.

 

DISPLAY MESSAGES 

Mess. 

Cause 

Outputs 

“OFF”   None of digital inputs configured as CCL are 

activated 

Valve closed 

“ON”  Plant start function is activated 

Valve opened 

“P1”  Temperature probe fault 

according to 

PEo

 and 

PEd

 

“P2”  Pressure transducer fault 

according to 

PEo

 and 

PEd

 

“HSH”  High superheat alarm 

By PI 

“LSH”  Low superheat alarm 

Valve Closed 

“LPL”  Low pressure limit 

see 

LPL

 parameter 

“MOP”  Maximum Operating Pressure 

see 

dML 

parameter 

“LOP”  Lowest Operating Pressure 

see 

dML 

parameter 

“StF”  Start Function enabled 

see 

ESF 

parameter 

“StP”  Regulation stop caused by Std and Sti 

Valve closed 

“dEF”  Defrost in progress 

Valve closed 

“EE” Memory 

anomaly 

12.1

 

ALARM RECOVERY  

Probe alarms “

P1

”, “

P2

” start few seconds after the fault in the probe; they automatically stop few 

seconds after the probe restarts normal operation. Check connections before replacing the probe. 
Max. and min. alarms “

HSH

” “

LSH

” “

MOP

” “

LOP

” automatically stop as soon as the variable returns to 

normal values. 

12.2

 

ALARM “EE” 

The instrument is provided with an internal check verifying memory integrity. Alarm “

EE

” flashes when 

a failure in the internal memory is detected. In such case call the service. 

13.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

4 DIN modules 70x85 mm; depth 61mm

 

Mounting: 

DIN RAIL mounted in a omega (3) din rail 

Protection

: IP20. 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply:

 24Vac ±10%; 110Vac ±10%; 230Vac 

±

10% 50/60Hz  50/60Hz 

Power absorption: 6

VA max 

Display

: three digits with icons, red LEDs, height 14,2 mm.  

Inputs

:   1 temperature probe Pt1000 or NTC; 

 

1 pressure transducer  4÷20mA o 0÷5V; 

Digital inputs:  

1

 

free of voltage  

 

 

 

 

1 at Main voltage 

Outputs for valve: 

30W max 

Data storage:

 on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

normal; S

oftware Class:

 

Operating temperature: 

0÷60°C; 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Resolution: 

 0,1 °C or 1 °F; 

Precision a 25°C:

:  ±0,7 °C ±1 digit 

14.

 

WIRING CONNECTIONS 

 

 

 

24-110Vac Models: 

Power supply, high voltage digital input and valve output are respectively 24Vac 

or 110Vac. 

15.

 

STANDARD VALUES 

 

Label 

Description 

Range 

Default 

Level 

FtY 

Kind of gas 

R22 , 134 , 404, 407, 

410, 507, CO2 

404 Pr2 

PEo 

Probe Error opening percentage 

0 ÷ 100 % 

50 

Pr2 

PEd 

Probe Error delay before stopping 
regulation 

0 ÷ 239 s - On 

On 

Pr2 

ESF 

Enable Start Function 

n ÷ Y 

Pr2 

OPE 

Start opening Percentage 

0 ÷ 100 % 

85 

Pr2

 

SFd 

Start Function duration 

0.0÷42.0

 

minutes: tens 

of seconds

 

1.3 

Pr2

 

ind 

injection delay 

0.0÷42.0

 

minutes: tens 

of seconds

 

10.0 

Pr2

 

dSH 

delta SuperHeat 

0.1 ÷ 10°C / 1÷50°F 

0.1 

Pr2

 

dOP 

delta Opening Percentage 

0 ÷ 100 % 

100 

Pr2

 

inb 

injection behaviour 

cL ÷ rEG 

rEG 

Pr2

 

Sti 

Stop regulation interval 

0.0÷24.0

 

hours: tens of 

minutes

 

1.3 

Pr2

 

Std 

Stop duration 

0 ÷ 60 min. 

Pr2

 

MnF 

Maximum opening percentage 

0 ÷ 100 % 

100 

Pr2

 

FOt 

Forced Opening time-out 

0.0÷24.0

 

hours: tens of 

minutes

 

0.1 

Pr2

 