Operating instructions 

 

cod. 1592001330 

 

1592001330  XC642C GB r1.0 07.06.2004.doc 

 

rel. 1.0  

 

Pa. 16 / 21 

 

Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s  requirements. 
Separate  the  input  connection  cables  from  the  power  supply  cables,  from  the  outputs  and  the  power 
connections. 

Do not exceed the maximum current allowed on each relay

, in case of heavier loads use a 

suitable external relay. 

17.1  PROBES CONNECTION 

Pressure  probe  (4  -  20  mA)

:  respect  the  polarity.  If  using  terminal  ends  be  sure  there  are  no  bear  parts 

which  could  cause  short  circuiting  or  introduce  noise  disturbance  at  high  frequencies.  To  minimise  the 
induced disturbances use shielded cables with the shield connected to earth.  

Temperature  probe:

  it  is  recommended  to  place  the  temperature  probe  away  from  direct  air  streams  to 

correctly measure the temperature. 

18.  RS485 serial link 

All models can be integrated into the monitoring and alarm system XJ500 using the TTL serial port. They use 
the standard ModBus RTU protocol, so they can be fitted in a system integrator using this protocol.  

19.  Technical features 

Housing:    

Self extinguishing ABS. 

Case:  

Front panel 32x74 mm, depth 60mm (“C” format);  

Mounting :

 “C” format panel mounting in a 29x71 mm panel cut-out  

Protection: 

IP65.

 

Frontal protection:

 IP65 with frontal gasket mod RG-C model. 

Connections: 

Removable terminal block 12 and 14 ways;  

Power supply: 

12Vac/dc 

±

 10%, 24Vac/dc 

±

 10%, 50-60Hz.  

Power absorption: 

5VA max.

 

Display:

 3 digits red led and 4 digit orange led.  

 

Inputs:

 2 NTC probes, or 2 PTC probes  and 2 4..20mA transducer. 

Digital inputs

: 5 free voltage 

Relay outputs: 

5 relay SPST 5(3)A, 250Vac 

Open collector:

 alarm output: 12V, 40mA. 

Analogue output:

 4..20mA for fan control, trigger for fan control 

Serial output :

 TTL standard 

Communication protocol:

 ModBus – RTU

 

Data storing:

 on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

normal; 

Software class: 

A. 

Operating temperature: 

0÷60 °C.; 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

 

Measuring range: NTC probe: 

-40÷110°C. 

Resolution: 

0,1 °C or 1°C; 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

20.  Alarms list 

 

Usually alarm conditions are signalled by means of: 
1. 

Activation of alarm output 0-12V 

2. 

Message on proper display 

3. 

Log of alarm: code and duration. 

 

20.1  TYPES OF ALARMS AND SIGNALLING MANAGED 

20.1.1

 

A12: Configuration alarm  

The following configuration parameters are checked after each modification.: 

 

OA1 

÷

÷

÷

÷

 OA4 

Outputs 1- 4 configuration 

P2P 

Second probe presence.    

dSEP 

Dynamic set point enabling 

AOP 

Probe for analog output 

tOP 

Probe for triac  output 

 
When these parameters are set in wrong way an alarm message is generated:  

Содержание XC642C

Страница 1: ...Compressor racks controller XC642C Operating manual...

Страница 2: ...UNNING HOURS OF LOADS _______________________________________________ 8 8 1 How to display the running hours of a load ____________________________________________ 8 8 2 How to reset the running hours...

Страница 3: ...enance Fit the probe where it is not accessible by the End User The instrument must not be opened In case of failure or faulty operation send the instrument back to the distributor or to Dixell S p a...

Страница 4: ...1 use the parameter PA04 Adjustment of read out corresponding to 4mA PA20 Adjustment of read out corresponding to 20mA Practically these parameters has to be set with the start and end scale of the p...

Страница 5: ...nt in programming mode it selects a parameter or confirm an operation Alarm menu By holding it pressed for 3s the current alarm is erased o o o o UP To enter the Alarm menu In programming mode it brow...

Страница 6: ...How to see and modify the set point 5 1 HOW TO SEE THE SET POINT OF COMPRESSORS 1 Push and release the SET key 2 The Lower display will show the SEtC label will the Upper display will show its value...

Страница 7: ...key 5 Repeat operations 2 and 3 for the other digits NOTE each parameter in Pr2 can be removed or put into Pr1 user level by pressing SET n n n n When a parameter is present also in Pr1 decimal point...

Страница 8: ...rs of the first output 3 To see the running hours of the following load press the UP key To exit push the CLOCK key or wait 30 sec 8 2 HOW TO RESET THE RUNNING HOURS OF A LOAD 1 Display the running ho...

Страница 9: ...T KEY DOWNLOAD 1 Turn OFF the instrument 2 Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON 3 Automatically the parameter list of the Hot Key is downloaded into th...

Страница 10: ...f sequence YES rotation this algorithm distributes the working time between the various loads to ensure even run times no fixed sequence the compressors are enabled and disabled in fixed sequence firs...

Страница 11: ...min res 10s doF Time delay between switching off of two different compressors 0 99 5 min res 10s donF Minimum time a stage stays switched ON 0 99 5 min res 10s FdLy don delay enabled also for the firs...

Страница 12: ...ON OFF enabling from keyboard no disabled yES enabled It permits the switching ON OFF of the instrument by pressing the SET key for more than 4s Ad1 Compressors address 1 247 It is used in monitoring...

Страница 13: ...ts If the pressure is greater than SET Pbd 2 the loads are switching on with timing given by parameters don and doF A load is turned on only if the his safety times onon oFon donF are over Regulation...

Страница 14: ...rature is lower than the regulation band all the compressors are off Naturally also for this regulations all the delays don and doF safety times onon oFon and donF are valid Regulation according to th...

Страница 15: ...erminal blocks for wires having section not bigger than 1 0 mm2 14 ways for analogue and digital inputs 12 ways for relays Note terminals 17 19 are connected inside the controller they are the common...

Страница 16: ...ting in a 29x71 mm panel cut out Protection IP65 Frontal protection IP65 with frontal gasket mod RG C model Connections Removable terminal block 12 and 14 ways Power supply 12Vac dc 10 24Vac dc 10 50...

Страница 17: ...suction and condensing sections Terminals Low pressure switch input 9 10 high pressure switch input HP Parameters SEP Low pressure switch polarity It establishes if the input is activated by closing S...

Страница 18: ...ow pressure temperature alarms This alarm signals that the pressure temperature is out of limits established by parameters LAL and HAL for compressors and LAF HAF for fans The tAo and AFd parameters s...

Страница 19: ...isabled Recovery depends on ALMr parameter With ALMr no The instrument restart the standard operating mode when the input is disabled With ALMr yES manual recover for the alarms of compressors and fan...

Страница 20: ...7 134 717 rtY db db db db Pr2 Type of regulation db Pb StY yES yES yES yES Pr2 Compressor rotation no YES Pbc Cur Cur Cur Cur Pr2 Probe 1 setting cur Ptc ntc PA04 0 5 7 0 5 7 Pr2 Adjustment of read ou...

Страница 21: ...point for cooling thermostat Lid 10 18 10 18 Pr2 Differential for cooling thermostat PAo 30 30 30 30 Pr2 Alarm probe exclusion at power on 0 255 min LAL 15 0 30 1 5 21 Pr1 Low pressure temperature ala...

Отзывы: